Installation Guidelines
Connection with IM 304/IM 314 Interface Modules
Plug the IM 304 interface module into a CR 700-2/-3-0LB central rack to connect as many as four
EUs per interface to the CC. Plug an IM 314 into each ER 701-2 or ER 701-3 expansion rack. Connect
the interface modules with the 6ES5 721-.... connecting cable as shown in Figure 3-20.
Connections with the IM 304/IM 314 interface modules have the following special features:
Using the IM 304/IM 314 symmetrical interface modules, you can connect EUs on ER 701-2 or
ER 701-3 expansion racks with full address bus to CCs of the S5-115U, S5-135U, S5-150U, and
S5-150S and S5-155U systems.
Connection to EU 183, EU 185 and EU 186 is possible.
You can use the extended address set for the programmable controllers mentioned above
(see the IM 304/IM 314 manual).
Always insert a 6ES5 760-1AA11 termination connector in the receptacle for the lower front
connector (X4) on the last IM 314.
The potential difference between CC and EU must not exceed 7 V. An equipotential bonding
conductor should therefore be provided!
CR 700-2/-3
P
C
S
P
U
IM 304
*
IM 314
*
Interface Module
IM 306 Interface Module
You can connect up to three ER 701-1 expansion racks here.
In adapter casing
*
Figure 3- 20. Distributed Configuration with IM 304/IM 314
3-22
721 Connecting cable
ER 701-2/-3
P
S
721 Connecting cable
ER 701-2/-3
P
S
721 Connecting cable
ER 701-2/-3
P
S
721 Connecting cable
ER 701-2/-3
P
S
Termination connector 6ES5 760-1AA11
EWA 4NEB 811 6130-02b
S5-115U Manual