Siemens SIMATIC S5-115U User Manual page 222

Simatic s5 series cpu 941-7ub11 cpu 942-7ub11 cpu 943-7ub11 and cpu 943-7ub21 cpu 944-7ub11 and cpu 944-7ub21
Table of Contents

Advertisement

STEP 5 Operations
On-delay
Example:
Output Q 4.2 is set 9 sec. after input I 3.5. It remains set as long as the input is "1".
Timing Diagram
Signal states
1
0
1
0
9
STL
A
I
3.5
L
KT
9.2
SD
T
3
NOP 0
NOP 0
NOP 0
A
T
3
=
Q
4.2
Note
The time value "9 sec." will have a sharper tolerance if you load the timer with the
statement "L KT 900.0".
8-22
I 3.5
Q 4.2
Time in sec.
9
CSF
T 3
T
0
I 3.5
KT 9.2
TV
BI
DE
R
Q
Q 4.2
S5-115U Manual
Circuit Diagram
I 3.5
T 3
Q 4.2
LAD
T 3
I 3.5
T
0
KT 9.2
TV
BI
DE
Q 4.2
R
Q
EWA 4NEB 811 6130-02b