The following is a description of the switch and jumper settings for the IM 304-3UA1. and for the
IM 304-3UB1.
Switch and Jumper Settings on the IM 304-3UA1. for Distributed Connection
Figure 3-21 shows the position of the switches and jumpers on the IM 304 module. If you use the
IM 304 interface module for distributed configuration, please set the jumpers as shown on jumper
block X11.
All switches must be in the "ON" position on block S3.
IM 304-3UA1.
7
1
X12
S2
S3
1
4
OFF ON
S1
Figure 3-21. Switch and Jumper Settings on the IM 304-3UA1. for Distributed Configurations
Switches S1 and S2 must be in the "ON" position when the relevant interface is in use.
EWA 4NEB 811 6130-02b
15
16
8
2
1
2
X11
3
2
1
X15
X14
X13
3
3
1
1
Installation Guidelines
15
16
13
14
11
12
9
10
7
8
5
6
3
4
1
2
X11
3-23