Reference Table For Initializing Db1 - Siemens SIMATIC S5-115U User Manual

Simatic s5 series cpu 941-7ub11 cpu 942-7ub11 cpu 943-7ub11 and cpu 943-7ub21 cpu 944-7ub11 and cpu 944-7ub21
Table of Contents

Advertisement

Integral Blocks

11.3.7 Reference Table for Initializing DB1

Parameter
Block Identifier: SL1:
SLN
SM
RM
CBR
CBS
PGN
Block Identifier:SDP:
WD
RDLY
RT
RC
RF
PROT
PIO
PII
PRIO
Block Identifier: TFB:
OB10
OB11
OB12
OB13
1 Additionally, set switch for Default/Overall Reset on the control panel of the CPU to "RE"
11-54
Argument
" SL ave N umber" (p=1 to 30)
p
Position of the S end M ailbox (start of SF)
Position of the R eceive M ailbox (start of EF)
DBxDWy or
Position of the C oordination B yte R eceive
FBy
Position of the C oordination B yte S end
(x=2 to 255; y=0 to 255)
PG bus N umber (p=1 to 30)
p
Note: CBS and CBR are in a flag byte or in the high-
order byte of the specified data word (DL)!
" W atch D og" (scan time monitoring)
p
can be set in milliseconds but only in steps of 10 msec.
(p=0 to 2550)
" R un D e L a Y " restart delay after POWER ON in msec.
r
(r=0 to 65535)
Note: RDLY only becomes effective in the case of
backup operation: in the case of EPROM operation,
the setting is fixed at 1000 ms!
" R esident T imers"(if "Y", all timers are retentive, if
Y/N
"N", only the first half are retentive)
" R esident C ounters" (if "Y", all counters are
Y/N
retentive, if "N", only the first half are retentive)
" R esident F lags" (if "Y", all flags are retentive, if "N",
Y/N
only the first half are retentive)
" PROT ection" activate software protection?
Y/N
(input/output of program no longer possible)
" P rocess I mage O utput" disable output of process
Y/N
image?
" P rocess I mage I nput" disable read in of process
Y/N
image?
OB6 PRIO rity (the following is the descending order
s
of priority:)
s=0 OB6, OB2 to 5, OB13 to 10
s=1 OB2 to 5, OB6, OB13 to 10
(OBs 2 to 6 cannot be interrupted!)
N=No
Y=Yes
Interval (msec.) during which OB10 to 13 is called and
p
processed
p
(p=0 to 65535 (programmable in 10-msec. intervals))
p
p
Meaning
SINEC L1
p=0 to 30 in the case of
CPU 943/944 with 2 interfaces)
System-Dependent -Parameters
1
1
Timer-Function Block
S5-115U Manual
1
EWA 4NEB 811 6130-02b