Siemens SIMATIC S5-115U User Manual page 571

Simatic s5 series cpu 941-7ub11 cpu 942-7ub11 cpu 943-7ub11 and cpu 943-7ub21 cpu 944-7ub11 and cpu 944-7ub21
Table of Contents

Advertisement

S5-115U Manual
Relay Output Module for Measuring Currents 16 x 24 V DC
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
Terminal Assignment
B
U
S
Block diagram
EWA 4NEB 811 6130-02b
Technical Specifications
Number of outputs
- contact bridge
- galvanic isolation
- in groups of
- relay type
Limiting continuous current
per contact
+
Parallel connection of
outputs
Permissible total current
of outputs
Switching frequency
- resistive load
- inductive load
Switching voltage
Switching capacity
of the contacts
- resistive load
- inductive load
Number of contact operating
+
cycles according to VDE 0660,
Part 200
- DC 11
Supply voltage L+
(for relay)
- rated value
- permissible range
- surge voltage at t<0.5 sec.
M
- ripple
6ES5 458-7LA11
Cable length
- shielded
- unshielded
Isolation rating
RELAY
Rated isolation voltage
OUTPUT
(between contacts)
16x24V UC
- isolation group
- tested with
Rated isolation voltage
(contacts to L+)
- isolation group
- tested with
L+ Aux.
Rated isolation voltage
(contacts to
- isolation group
- tested with
Current consumption
M ext.
- from 5 V (internal)
- fromL+(for relay)
Power losses of
the module
Weight
Technical Specifications
(6ES5 458-7LA11)
16
no
yes
1
3700-2501-011
(Günther)
0.5 A
possible
100 %
maximum 60 Hz
not permissible
maximum 30 V DC
10 W at 0.5 A;
not permissible
9
1 x 10
24 V DC
20 to 30 V
35 V
maximum 3.6 V
1000 m (3281 ft.)
300 m (984 ft.)
according to VDE 0160
30 V DC
C
500 V AC
30 V DC
C
500 V AC
)
30 V DC
C
500 V AC
maximum 50 mA
240 mA
typically
5W
approx.
0.8 kg (1.76 lb.)