S5-115U Manual
OB No. Function
OB must be user-programmed and be called by the operating system
OB1
Cyclic program scanning
OBs for interrupt-driven and time-controlled program scanning
OB2
Interrupt A:
OB3
Interrupt B:
OB4
Interrupt C:
OB5
Interrupt D:
OB6
Interrupt generated by internal timers
OB10
Time-controlled
OB11
program scanning
OB12
(variable in each case: 10 msec. to 10 min.)
OB13
OBs for controlling restart characteristics
OB21
Manual switch on (STOP RUN)
OB22
Automatic switch on when power is restored
OBs for handling programming errors and PLC faults
OB19
When a block is called which has not been loaded
OB23
Time-out during individual access to the S5 bus
(e.g. LPB, LIR, etc.)
OB24
Time-out during update of the process image and the
interprocessor communication flags
OB27
Substitution error
OB32
Transfer errors in DB or with GDB operation
OB34
Battery failure
OBs which offer operating functions
OB31
Scan time triggering
OB160
Programmable time loop
OB251
PID algorithm
OB254
Read in process I/O image
OB255
Output process I/O image
OB available
EWA 4NEB 811 6130-02b
Table 7-3. Overview of Organization Blocks
Digital input module -434
and IP generate interrupt
IP generates interrupt
IP generates interrupt
IP generates interrupt
Introduction to STEP 5
OB integrated in CPU
941
942
943
944
7-9