Setting The Bus Address (Foundation Fieldbus) - ABB FV4000 Operating Instruction

Vortex/swirl flowmeter
Table of Contents

Advertisement

Definition of the address mode
Setting of switch 8
Off (bus)
On (local)
Important
In the case of local addressing, address settings are not applied until the device is switched
on.
Example
Setting of bus address 81:
Switch
Setting
The bus address is set by adding together the corresponding address values of switches 1 to 7.
To set bus address 81, switches 1, 5, and 7 have to be set to "On", since the corresponding
address values 1, 16, and 64 add together to make 81.
Switch 8 must be set to "On" in order that the bus address can be set with the miniature switch.
6.5

Setting the bus address (FOUNDATION Fieldbus)

On the FOUNDATION Fieldbus, the bus address is set automatically via the LAS
(LinkActiveScheduler). Addresses are detected via a unique number (DEVICE_ID) made up of
the manufacturer ID, the device ID and the device serial number.
D184B097U02
Address mode
Addressing is via the bus.
Addressing is via miniature switches 1 to 7.
1
2
3
On
Off
Off
FV4000 / FS4000
4
5
6
Off
On
Off
Commissioning
7
8
On
On
51