Overview Of Technical Design And Setting Parameters - ABB FV4000 Operating Instruction

Vortex/swirl flowmeter
Table of Contents

Advertisement

14.3 Overview of technical design and setting parameters

Measuring point:
Sensor model:
Order no.
Medium:
Parameter
Prog. protection code:
Language:
Nominal size:
Operating mode:
Q
max
Standard factor:
Reference density:
Density unit:
Unit Q
vol
Unit Q
m
Unit totalizer:
Max. alarm:
Min. alarm:
Pulse factor:
Pulse width:
Low flow (Q
):
min
Damping:
1st display line:
2nd display line:
2nd multiplex line:
Communication:
D184B097U02
HART protocol
PROFIBUS PA
FV4000 / FS4000
TAG no.:
Device no.:
Voltage supply:
Setting range
0-9999 (0=factory setting)
DN 15 - 400
0.15 Q
DN to 1.15 Q
max
0.001 - 1,000 (operating density / standard density)
g/ml, g/cm3, g/l, kg/l, kg/m3, lb/ft3, lb/ugl
l/s, l/min, l/h, l/d, m³/s, m³/min, m³/h, m³/d,
ft3/s, ft3/m, ft3/h, ft3/d, bbl/s, bbl/min, bbl/h, bls/d,
Usgps, USgpm, USgph, Usmgd, igps, igpm, igph, igpd
kg/s, kg/min, kg/h, kg/d, t/min, t/h, t/d, g/s, g/min, g/h,
lb/s, lb/min, lb/h, lb/d
l, m³, igal, USgal, ft3, bbl, kg, t, g, lb
%
%
0.001 to 1,000 pulse/phys. unit
0.100 - 2,000 ms
2 - 25 % of flow range upper range value
0.5 - 99.99 seconds
Q (%), Q (unit), totalizer, temperature
Q (%), Q (unit), totalizer, temperature
ON / OFF
FOUNDATION Fieldbus FF
Appendix
DN
max
121

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fs4000