Specifications - ABB FV4000 Operating Instruction

Vortex/swirl flowmeter
Table of Contents

Advertisement

Specifications

12 Specifications
Change from one to two columns
A
12.1 Nominal diameter selection
The nominal diameter is selected on the basis of the maximum
operating flow Qv max. If maximum spans are to be achieved, this
should not be less than half the maximum flowrate for each nominal
diameter
(Qv max DN),
0.15 Qv max DN is possible. The linear lower range limit value is
dependent upon the Reynolds number (see accuracy information).
If the flow to be measured is the standard flow (standard condition:
0 °C (32 °F), 1,013 mbar) or mass flowrate, this must be converted to
the operating flow and the most appropriate nominal device diameter
must be selected from the flow range tables (Tables 1, 2, 3).
= Operating density (kg/m 3 )
ρ
ρ N = Standard density (kg/m 3 )
P
= Operating pressure (bar)
T
= Operating temperature (°C)
Qv = Operating flow (m 3 /h)
Qn = Standard flow (m 3 /h)
Qm = Mass flowrate (kg/h)
η
= Dynamic viscosity (Pas)
= Kinematic viscosity (m 2 /s)
ν
1. Conversion of standard density (ρn) --> operating density (ρ)
+
ρ
1
,
013
273
ρ
=
ρ
×
×
n
+
1
,
013
273
T
2. Conversion to operating flow (Qv)
a) From standard flow (Qn) -->
ρ
1
,
013
n
=
=
×
Q
Q
Q
V
n
n
ρ
+
1
,
013
p
b) From mass flowrate (Qm) -->
Q
m
=
Q
V
ρ
3. Dynamic viscosity ( η ) --> kinematic viscosity ( ν )
η
ν
=
ρ
Calculating the Reynolds number:
Q
=
Re
(
)
⋅ ν
2827
d
Q = Flow in m 3 /h
d = Pipe diameter in m
ν = Kinematic viscosity m 2 /s (1 cst = 10 -6 m 2 /s)
The current Reynolds number can also be calculated using our AP-
Calc calculation program.
108
although
reduction
to
+
273
T
273
12.2 Measured value deviation for flow
measurement
Deviation in percentage terms from the measured value under
reference conditions (including the transmitter) in the linear
approx.
measuring range between Re min and Qmax (see "Measuring
ranges" table).
Fluids
Gases / Steam
Current output
Additional
measurement
uncertainty
Temperature effect
Misalignment associated with installation or deinstallation may affect
the measuring error.
Additional measuring errors may occur if there are deviations from
the reference conditions.
12.2.1 Reproducibility as a percentage of the
measured value
DN
15
25 ... 250
200 ... 300
12.3 Measured value deviation for temperature
Measured value deviation (including transmitter)
± 2 °C
Reproducibility
≤ 0.2 % of measured value
Product selection and dimensioning program
Important
The ABB "AP-Calc" program can be used free of charge
when selecting an appropriate flowmeter for a given
application. The program runs in a Microsoft WINDOWS ®
environment.
FV4000 / FS4000
FV4000-VT4/VR4
FS4000-ST4/SR4
≤ ± 0,75 %
≤ ± 1 %
< 0,1 %
< 0,05 % / 10 K
Inch
FV4000-
VT4/VR4
1/2"
0,3 %
1" ... 6"
0,2 %
8" ... 12"
0,25 %
D184B097U02
± 0,5 %
FS4000-
ST4/SR4
0,2 %

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fs4000

Table of Contents