Models designed for hazardous areas with American approval
Models
VT43 / ST43 / VR43 / SR43
11.1.2 Fieldbus devices
Models: VT4A, VR4A, ST4A, SR4A
The hazardous area design of the device is based on the PTB's FISCO model (FISCO =
fieldbus intrinsically safe concept).
Proof of intrinsic safety for interconnection with other intrinsically safe equipment is not required
under the boundary conditions specified.
•
All nodes must have FISCO approval, e.g., from the PTB, TÜV, BVS, KEMA.
•
The maximum cable length in a segment is restricted to 1,000 m for EEx ia and 1,900 m for
EX ib.
•
The bus cable (type A) has to exhibit the following values: R' = 15 Ω/km,
L' = 0.4 ... 1 mH/km, C' = 80 ... 200 nF/km
•
The following applies for every field device (U
•
All nodes act as passive current sinks.
•
No power is fed in when a bus node is sending.
There is only one active device per segment (supply unit / segment coupler).
Designation: II 2G EEx ia IIC T4
D184B097U02
Approvals
•
Explosion-proof
XP/Class I/Div 1/BCD/T4 Ta = 70 °C Type 4X
•
Dust-ignition-proof
DIP/Class II,III/Div 1/EFG/T4 Ta = 70 °C Type 4X
DIP/Class II,III /Div 2 /EFG /T4 Ta=70°C Type 4X
•
Intrinsic safety
IS/Class I, II,III/Div 1 ABCDEFG/T4 Ta = 70 °C Entity Type
4X
•
Non-incendive
NI/Class I/Div 2/ABCD/T4 Ta = 70 °C Type 4X
, I
, P
l
l
FV4000 / FS4000
Ex relevant specifications
): U
≤ U
, I
≤ I
, P
≤ P
i
0
l
0
l
0
i
97