Models designed for hazardous areas with American approval
Models
VT43 / ST43 / VR43 / SR43

11.1.2 Fieldbus devices

Models: VT4A, VR4A, ST4A, SR4A
The hazardous area design of the device is based on the PTB's FISCO model (FISCO =
fieldbus intrinsically safe concept).
Proof of intrinsic safety for interconnection with other intrinsically safe equipment is not required
under the boundary conditions specified.
All nodes must have FISCO approval, e.g., from the PTB, TÜV, BVS, KEMA.
The maximum cable length in a segment is restricted to 1,000 m for EEx ia and 1,900 m for
EX ib.
The bus cable (type A) has to exhibit the following values: R' = 15 Ω/km,
L' = 0.4 ... 1 mH/km, C' = 80 ... 200 nF/km
The following applies for every field device (U
All nodes act as passive current sinks.
No power is fed in when a bus node is sending.
There is only one active device per segment (supply unit / segment coupler).
Designation: II 2G EEx ia IIC T4
D184B097U02
Approvals
Explosion-proof
XP/Class I/Div 1/BCD/T4 Ta = 70 °C Type 4X
Dust-ignition-proof
DIP/Class II,III/Div 1/EFG/T4 Ta = 70 °C Type 4X
DIP/Class II,III /Div 2 /EFG /T4 Ta=70°C Type 4X
Intrinsic safety
IS/Class I, II,III/Div 1 ABCDEFG/T4 Ta = 70 °C Entity Type
4X
Non-incendive
NI/Class I/Div 2/ABCD/T4 Ta = 70 °C Type 4X
, I
, P
l
l
FV4000 / FS4000
Ex relevant specifications
): U
≤ U
, I
≤ I
, P
≤ P
i
0
l
0
l
0
i
97