ABB FV4000 Operating Instruction page 56

Vortex/swirl flowmeter
Table of Contents

Advertisement

Communication
The maximum number of bus nodes in a segment is listed in the following table.
DP / PA segment coupler
Area of application
Supply voltage
Supply current Is
Loop resistance Rs
Cable length, type B
AWG 20 (0.5 mm
Cable length, type A
AWG 18 (0.8 mm
No. of nodes at 10 mA
Brochure "PROFIBUS - Solutions from ABB" (no. 30/FB-10) contains more detailed information
about configuration. Accessories such as terminal blocks, connectors, and cables are listed in
data sheet 10/63-6.44. Supplementary information also appears both on the ABB homepage at
http://www.abb.com and on the homepage of the PROFIBUS User Organization at
http://www.profibus.com.
System integration
The use of the PROFIBUS PA Profile B, V3.0, means that the meters are not only interoperable
(in other words, devices from different manufacturers can be physically connected to one and
the same bus and communicate on it), they are also interchangeable (in other words, devices
from different manufacturers can be interchanged without having to modify the configuration in
the process control system).
To support interchangeability, ABB provides three different GSD (generic station description)
files for system integration. During system integration, users decide whether to install the full
range of functions or only part. Devices are interchanged using the ID number selector
parameter, which can only be modified on an acyclic basis. The following table describes the
available GSD files:
Number and type of
function blocks
and all manufacturer-
specific parameters
The GSD files appear on the CD included in the scope of supply. The standard GSD files
"PA1397xx.gsd"
http://www.profibus.com.
The GSD files, along with the "PROFIBUS PA interface description" for the device (part no.
D184B093Uxx) appear on the CD included in the scope of supply (part no. D699D002Uxx). The
CD can be ordered separately from ABB at any time free of charge if required.
56
2
)
2
)
1 x Al
1 x Al; 1 x TOT
2 x AI; 1 x TOT
are
available
Type I
Type II
EEx ia/ib IIC
EX ib IIC
13.5 V
13.5 V
≤ 110 mA
≤ 110 mA
≤ 40 Ω
≤ 40 Ω
≤ 500 m
≤ 500 m
≤ 900 m
≤ 900 m
8
8
ID number
GSD file name
0 x 9700
PA 139700.gsd
0 x 9740
0 x 05DC
ABB_05DC.gsd
for
download
FV4000 / FS4000
Type III
EX ib IIC
13.5 V
≤ 250 mA
≤ 18 Ω
≤ 250 m
≤ 400 m
19
ABB05DCb.bmp
PA 139740.gsd
ABB05DCn.bmp
ABB05DCs.bmp
from
the
PNO
Type IV
Non-
hazardous
24 V
≤ 500 mA
≤ 130 Ω
≤ 1700 m
≤ 1900 m
32
Bitmaps
homepage
at
D184B097U02