Approval Data For Hazardous Areas - ABB FV4000 Operating Instruction

Vortex/swirl flowmeter
Table of Contents

Advertisement

11.5.3 Approval data for hazardous areas

II 2D T 85 °C ... T med IP 67 /
T amb = -20 °C ... 60 °C
Power supply circuit
Terminals 31, 32
II 2G EEx ia IIC T4 /
T amb = (-40 °C) -20 ... 70 °C
U i = 24 V
Type of protection
I i = 380 mA
P i = 9.12 mW
The effective internal capacitance and
inductance are negligibly low.
Power supply circuit
Terminals 41, 42
II 2G EEx ia IIC T4
U i = 15 V
I i = 30 mA
P i = 115 mW
Type of protection
Effective internal capacitance:3.6 nF
Effective internal capacitance
to ground:
Effective internal inductance: 0.14 mH
VR4A / SR4A only
Type of protection
II 2G EEx ia IIC T4
U 0 = 8.5 V
Piezo sensor
I 0 = 1,073 mA
Terminals 85, 86, 86, 87
Pt100 circuit, terminals
P 0 = 2,280 mW
81, 82, 83, 84
Change from one to two columns
D184B097U02
11.5.4 Medium temperatures / Temperature
classes
For the supply circuit "Terminals 31, 32" and the switching outputs
"Terminals 41, 42", cables suitable for temperatures up to T = 110 °C
(T = 230 °F) can be used without restriction.
Category 2/3G
For cables suitable only for temperatures up to T= 80 °C (T = 176 °F),
the interconnection of both circuits needs to be taken into account in
the event of a fault. Otherwise, the restricted temperature ranges
listed in the following table shall apply.
Category 2D
For cables suitable only for temperatures up to T= 80 °C (T = 176 °F),
the restricted temperature ranges listed in the following table shall
apply.
Ambient
temperature
3.6 nF
(-30) -20 ... 70 °C
((-22) -4 ... 158 °F)
(-30) -20 ... 70 °C
((-22) -4 ... 158 °F)
(-30) -20 ... 60 °C
((-22) -4 ... 140 °F)
(-30) -20 ... 55 °C
((-22) -4 ... 131 °F)
(-30) -20 ... 50 °C
((-22) -4 ... 122 °F)
(-30) -20 ... 40 °C
((-22) -4 ... 104 °F)
1)
Medium temperatures > 280 °C (> 536 °F) with FV4000 Vortex flowmeter only
2)
The permissible limits for the ambient temperature are approval- and order-specific
(standard: -20 °C (-4 °F)).
Maximum medium
temperature
130 °C (266 °F)
195 °C (383 °F)
290 °C (554 °F)
400 °C (752 °F)
FV4000 / FS4000
Ex relevant specifications
Max. temperature
2)
at used
connecting cable,
"Terminals 31,
32", "Terminals
41, 42"
110 °C (230 °F)
80 °C (176 °F)
Temperature class
Max. permissible
medium
temperature
280 °C / 400 °C
1)
(536 °C / 752 °F)
1)
160 °C (320 °F)
240 °C (464 °F)
280 °C (536 °F)
1)
320 °C (608 °F)
1)
400 °C (752 °F)
T4
T3
T2
T1
107

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fs4000

Table of Contents