Communication Module Connections; Hart Module; Foundation Fieldbus Module; Profibus Pa Module - ABB AWT210 Operating Instruction

2-wire conductivity, ph/orp pion transmitter
Hide thumbs Also See for AWT210:
Table of Contents

Advertisement

18
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. C
...6 Electrical installation

Communication module connections

HART module

Power
+
1
2
Non IS installations
12 to 42 V DC
IS installations
12 to 30 V DC
Functional earth
Ammeter connection for loop current test

FOUNDATION Fieldbus module

Connected internally
A
B
1
2
Non IS installations
9 to 32 V DC
IS installations
9 to 24 V DC
Functional earth

Profibus PA module

Connected internally
A
B
1
2
Non IS installations
9 to 32 V DC
IS installations
9 to 24 V DC
Functional earth
Ammeter
+
3
4
5
A
B
3
4
5
A
B
3
4
5

Ground connection

Normal grounding practice is to terminate all grounds at the
control room side, in which case the field side of the screen
should be adequately protected to avoid contact with metallic
objects. The transmitter case should be grounded.
WARNING
Bodily injury
If conduit hubs are used, they will not provide a bonding of
the enclosure or system.
Referring to Figure 16, ground connections are provided:
internally
A
and externally
Figure 16 AWT210 ground connections
For IS systems the grounding should be at the safety barrier
earth connection. For bus-powered systems the grounding of
the screen should be close to the power supply unit. The
specific noise immunity and emitted interference are only
guaranteed when bus screening is fully effective – for example,
ensuring that screening is maintained through any existing
junction boxes. Appropriate equipotential bonding must be
provided to avoid differences in potential among the individual
plant components.
To ensure fault-free communication on Fieldbus (FF or PA)
installations, the bus must be properly terminated at both
ends. Only approved bus terminators must be used for
intrinsically safe circuits.
NOTICE
HART, Profibus and Fieldbus protocols are not secure.
Therefore, the intended application should be assessed
before implementation to ensure these protocols are
suitable.

Gland entries

For hazardous area installations, suitable Ex glands and
blanking elements must be used to seal the entry holes.
B
.