Electrical connections
5.2.3.1
Bus Connection
The fieldbus transmitter is suitable for connection to the ABB multibarrier, the segment coupler
(PROFIBUS PA design only) and special power supply units or a linking device (FOUNDATION
Fieldbus design only). As well as the bus connection (terminals 31 / 32) there is also a freely
configurable switching output (terminals 41 / 42) available.
Electrical variable
Supply voltage
Current (normal operation)
Current (in the event of an error / FDE)
VT4A / ST4A models
Fig. 30: Electrical connection, FV4000-VT4A / FS4000-ST4A
1 Flowmeter sensor and transmitter
2 Other bus nodes
3 Switching amplifier (NAMUR DIN 19234)
40
1
b) a)
E9
E9
42
T
C9
C9
41
PA-
FF-
32
F
PA+
FF+
31
II 2G EEx ia IIC T4
PA
PA
Hazardous area
FV4000 / FS4000
Value
U = 14 ... 32 V DC
I = 10 mA
I = 13 mA
2
NAMUR
EEx ia
4 PROFIBUS PA:
Intrinsically safe segment coupler
FOUNDATION Fieldbus:
Intrinsically safe supply isolator,
zener barrier/power supply unit
3
4
Non-hazardous area
D184B097U02
G00728