Commissioning
6.4

Setting the bus address (PROFIBUS PA)

If no bus address information is supplied by the customer, the unit will be shipped with an
address setting of "126" (addressing via the bus). The address has to be set to within the valid
range (0, 2 ... 125) during installation and start-up.
Important
The set address may only appear once in the segment.
The address can be set either locally on the unit (via the miniature switch 8 on the digital board),
using system tools, or via a PROFIBUS DP master class 2 such as SMART VISION.
Switch 8 is factory-set to "Off"; in other words, addressing is via the fieldbus.
Fig. 40: Position of the miniature switch
Setting the bus address
1
2.
Switch
Setting
Off
On
3.
50
Unscrew the front cover from the transmitter housing.
Set the bus address using the following table.
1
2
0
0
1
2
Screw the cover back into place.
C/CE
Data/
Step
Enter
3
4
5
Device address
0
0
0
4
8
16
FV4000 / FS4000
6
7
Address mode
0
0
Bus
32
64
Local
D184B097U02
G00733
8