Setting the Reference
The reference procedure sets a baseline for insertion loss,
ACR-F, and dc resistance measurements.
Run the tester's reference procedure at the following times:
•
When you want to use the tester with a different smart
remote. You can reference the tester to two different
smart remotes.
•
Every 30 days. Doing so ensures maximum accuracy of
test results.
You do not need to set the reference after changing link
interface adapters.
To set the reference:
Turn on the tester and smart remote and let them
sit for 1 minute before setting the reference. Set
the reference only after the testers have reached an
ambient temperature between 10
°
°
(50
F and 104
F).
Chapter 3: Certifying Twisted Pair Cabling
Note
°
°
C and 40
C
1
Attach permanent link and channel adapters and make
the connections shown in Figure 3-1.
For the DTX-ELT and DTX-CLT, which do not include
permanent link adapters, use the reference module
included to connect the main and remote testers, as
shown in Figure 3-2. (You may use the reference
module, if available, to make reference connections for
any DTX model.)
2
Turn the rotary switch to SPECIAL FUNCTIONS.
3
Highlight Set Reference; then press
fiber module and copper adapter are attached, select
Link Interface Adapter next.
P
4
Press
.
H
. If both a
3-1