Open on pair 1,2. The open is 21.7 m
from the tester and 61.4 m from the
remote. The open may be on either or
both wires.
AC wire maps show the wire pair numbers next to each other if there is a fault on the cable.
AC wire maps do not show the shield connection unless there is a short to the shield.
amd52.bmp
Short between pairs 1,2 and 3,6. The
short is 1.7 m from the tester. The short
may be between two, three, or all four
wires.
Notes
Figure 4-3. AC Wire Map Examples
Testing Twisted Pair Through a PoE Device
AC Wire Map Results
amd50.bmp
Split pair on pairs 1,2 and 3,6. The
split pair starts 30.0 m and ends
52.2 m from the main tester.
4
amd45.bmp
4-5

Hide quick links: