Fluke DTX-1800 Technical Reference Handbook page 280

Dtx series cable analyzer
Hide thumbs Also See for DTX-1800:
Table of Contents

Advertisement

DTX Series CableAnalyzer
Technical Reference Handbook
Largest Event fails
The event is a dirty or damaged connector. Check the OTDR trace or event table for high-loss reflective events.
A patch cord, launch fiber, or fiber segment has the wrong core size, backscatter coefficient, or mode field diameter. If
the patch cords and launch fiber are the correct type, check the OTDR trace for mismatched cable in the cabling.
The event is a bad fusion or mechanical splice or a sharp bend. Use the OTDR trace or event table to locate these faults.
The launch fibers have PC or UPC connectors, but the link being tested has APC connectors.
Fiber Length fails, a known length of cabling measures too long or too short, or the distance to an event is wrong.
The fiber is broken or there is an open connection where the trace shows the fiber end.
The wrong fiber type is selected on the Cable tab in Setup.
The index of refraction needs adjustment. Change n on the Cable tab in Setup.
The wrong test limit is selected on the OTDR tab in Setup.
An event shows a FAIL result, but the event does not exceed any limit.
The segment before the event exceeds a limit. To see results for the segment,
the OTDR Results screen
10-6
Table 10-3. Diagnosing OTDR Test Failures (cont.)