Inputs; In.a1/In.a2/In.a3 Analog Inputs - gefran GFW 400-600A Configuration And Programming Manual

Modular power controller
Hide thumbs Also See for GFW 400-600A:
Table of Contents

Advertisement

IN.A1/IN.A2/IN.A3 ANALOG INPUTS

The modular power controller has three analog inputs with the functionality of power control.
Probe type
573
tP.A1
837
tP.A2
844
tP.A3
Scale limits
574
LS.A1
838
LS.A2
845
LS.A3
575
kS.A1
839
kS.A2
846
kS.A3
Examples of LS.A and HS.A parameter settings
Ou .P
Example:
10 0.0 %
V
= 0...10V
IN
tyP. = 1
LS.A1 = 0.0
HS.A1 = 100.0
0.0 %
10

INPUTS

R/W
Analog input 1
R/W
Analog input 2
R/W
Analog input 3
Minimum scale limit
R/W
analog input 1
Minimum scale limit
R/W
analog input2
Minimum scale limit
R/W
analog input 3
Maximum scale limit
R/W
analog input 1
Maximum scale limit
R/W
analog input 2
Maximum scale limit
R/W
analog input 3
P.V .
H S .A = 1 00 .0
LS .A = 0.0
0 V
0
Disable
1
0...10V
2
0...5V / Potentiometer
3
0...20mA
4
4...20mA
-100.0...200.0
-100.0...200.0
-100.0...200.0
LS.A1...200.0
LS.A2...200.0
LS.A3...200.0
The default values (LS.A = 0.0 and HS.A = 100.0) can be chan-
ged to obtain the required scale of the PV in engineering value
corresponding to the minimum and maximum of the physical
input (V/mA).
In automatic mode, the engineering value (PV) is attributed to
power Ou.P for values between 0.0 and 100.0.
10 V
V
IN
Table of analog input
80997D_MSW_GFW_400-600_04-2021_ENG
1
1
1
0.0
0.0
0.0
100.0
100.0
100.0