LION System

Analog Output Modules

Types of Analog Output Modules and Terminal
Socket
Type
Description
CLIOP822
Panel Bus analog
output module
CLIOPR822 Panel Bus analog
output module with
manual overrides
L
W
CLIOL822
ON
ORKS
output module
CLIOLR822 L
W
ON
ORKS
output module with
manual overrides
XS821-22
Terminal socket
XSU821-22
Table 46 LION Analog Output Modules
Features
• 8 analog outputs; can also be configured per output as
binary outputs (0 ... 10 V, 2 ... 10 V, ON/OFF, or floating)
• Corresponding output status LEDs (red)
• ... R 822: 8 manual overrides, see figure below
1
3
Fig. 65
CLIOP822A Analog Output Module with terminal
socket
Legend
1
Service button S1
2
Hex switch S2
3
Manual overrides
4
Output LEDs
5
Service LED
6
Power LED
Housing
Light gray
Light gray
Bus analog
Dark gray
Bus analog
Dark gray
Light gray
2
4
5 6
Functionality of service LED and power LED: see Table 77
to Table 79 on page 78 and following.
In the event of communication problems, the analog outputs
will move to the safety positions you have configured using
the engineering tool, see analog output point description in
the CARE – User Guide, 74-5587/EN2B-0182GE51.
Terminals
Fig. 66
Terminal assignment and internal connections of
the analog output modules
Ter-
Signal
minal
71, 75
COM a
72, 76
COM b
73, 77
24 V~
74, 78
24 V~0
1...8
AO1...AO8 Analog outputs 1...8
9...18
GND
21, 22
N.C.
25, 26
Table 47 Description of the analog output module terminals
Notes
• Shield connection to be used for shielded I/O cables only.
It is not allowed to connect a L
L
W
requires a resistor and a capacitor.
ON
ORKS
• If additional shield terminals are needed, the
XS814 Auxiliary Terminal Package can be installed.
45
Description of the I/O Modules
COMMENT
2-wire communication bus
(LON/Panel Bus)
2-wire communication bus
(LON/Panel Bus)
Power supply
Power supply
Ground. All grounds are connected
internally to each other
Do not use!
Shield connection (functional earth),
internally connected to the DIN rail
W
shield, since
ON
ORKS
EN1Z-0921GE51 R0709