Rxgoose Status; Rxgoose Statistics; Digital Counters - GE G30 Instruction Manual

Generator protection system 7.6x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CHAPTER 6: ACTUAL VALUES

6.3.8 RxGOOSE status

ACTUAL VALUES  STATUS  RxGOOSE STATUS
 RxGOOSE
 STATUS
The G30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the
time of ordering. See the Order Codes section of chapter 2 for details.
The
actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
All RxGOOSE Online
Input.

6.3.9 RxGOOSE statistics

ACTUAL VALUES  STATUS  RxGOOSE STATISTICS  RxGOOSE 1(64)
 RxGOOSE 1
The G30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the
time of ordering. See the Order Codes section of chapter 2 for details.
— State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
— Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.
— Multicast (SSM and ASM) modes of R-GOOSE reception require that the G30 device subscribe to a multicast group
IGMP
over the Internet Group Management Protocol (IGMP) enabled network. R-RxGOOSE## IGMP status On indicates that IGMP
negotiation with a network device (for example a router) was successful. In the case where setting R-RxGOOSE1 DST IP is
configured to a multicast address and this status indicates Off, R-GOOSE reception cannot be successful, and therefore
communication network diagnosis needs to be carried out. This status is relevant to R-GOOSE reception when configured
for SSM or ASM reception modes. It is not relevant for GOOSE or for R-GOOSE in unicast reception mode.

6.3.10 Digital counters

ACTUAL VALUES  STATUS  DIGITAL COUNTERS  DIGITAL COUNTERS Counter 1(8)
 DIGITAL COUNTERS
 Counter 1
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
All RxGOOSE Online:
Yes
RxGOOSE 1 Status:
Offline
RxGOOSE 64 Status:
Offline
RxGOOSE 1
stNum:
0
RxGOOSE 1
sqNum:
0
R-RxGOOSE 1
IGMP:
Off
Counter 1
ACCUM:
0
Counter 1 FROZEN:
0
Range: Yes, No
Range: Online, Offline
Range: Online, Offline
Range: 0 up to 4,294,967,295
Range: 0 up to 4,294,967,295
Range: On, Off