Force Contact Inputs; Force Contact Outputs - GE G30 Instruction Manual

Generator protection system 7.6x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Table 5-41: Test mode operation
TEST MODE
In-service
FUNCTION
LED
Disabled
Unaffected
Isolated
Off
Forcible
Off
On restart, the
TEST MODE FORCING
their default states.

5.11.3 Force contact inputs

SETTINGS  TESTING  FORCE CONTACT INPUTS
 FORCE CONTACT
 INPUTS
The force contact inputs feature provides a method of performing checks on the function of all contact inputs.
While in Forcible test mode, the relay contact inputs can be pre-programmed to respond in the following ways:
If set to "Normal," the input remains fully operational. It is controlled by the voltage across its input terminals and can
be turned on and off by external circuitry. Select this value if a given input must be operational during the test. This
includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence.
If set to "Open," the input is forced to report as opened (Logic 0) while the operand selected by
setting is On, regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
If set to "Closed," the input is forced to report as closed (Logic 1) while the operand selected by
setting is On regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
On restart, the
TEST MODE FORCING
their default states.

5.11.4 Force contact outputs

SETTINGS  TESTING  FORCE CONTACT OUTPUTS
 FORCE CONTACT
 OUTPUTS
The force contact outputs feature provides a method of performing checks on the function of all contact outputs.
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Test mode
Critical fail
TEST MODE
LED
relay
FORCING
Off
Normal
No effect
On
De-energized No effect
Flashing
De-energized Off
On
setting and the force contact input and force contact output settings revert to
FORCE Cont Ip 1
: Normal
FORCE Cont Ip 2
: Normal
FORCE Cont Ip xx
: Normal
setting and the force contact input and force contact output settings revert to
FORCE Cont Op 1
: Normal
FORCE Cont Op 2
: Normal
FORCE Cont Op xx
: Normal
Contact input and output behavior
Normal
Contact outputs disabled
Normal
Controlled by forcing features
Range: Normal, Open, Closed
Range: Normal, Open, Closed
Range: Normal, Open, Closed
TEST MODE FORCING
TEST MODE FORCING
Range: Normal, Energized, De-energized, Freeze
Range: Normal, Energized, De-energized, Freeze
Range: Normal, Energized, De-energized, Freeze
TESTING
5
5-323