SETTINGS
CHAPTER 8: APPLICATION OF SETTINGS
8.2.8 Overexcitation
This protection is to be set to coordinate with the manufacturer's excitation capability curves. For the example system, the
combined generator/GSU limit curve is shown as follows.
Figure 8-5: Generator/GSU limit curve
Program the volts per hertz 1 element with an inverse characteristic (curve A), a pickup of 1.05, and a TDM of 40. Program
the volts per hertz 2 element with a definite time characteristic, a pickup of 1.23, and a time delay of 2 seconds. Both
elements are thus set to issue a trip. The volts per hertz 1 pickup is to be used to generate an alarm. Either source can be
assigned in this example. Make the following changes in the EnerVista software or the front panel
SETTINGS GROUPED
menus.
ELEMENTS SETTING GROUP 1 VOLTAGE ELEMENTS VOLTS/HZ 1(2)
8
8.2.9 Inputs/outputs
The following inputs and outputs are used in this example. Make the following changes in the EnerVista software or the
front panel
menus.
SETTINGS INPUTS/OUTPUTS CONTACT INPUTS CONTACT INPUT H7a(H7c)
8-12
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL