GE G30 Instruction Manual

GE G30 Instruction Manual

Ur series generator protection system
Hide thumbs Also See for G30:
Table of Contents

Advertisement

GE
Digital Energy
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEDigitalEnergy.com
*1601-0166-Y4*
GEK-113668C
G30 Generator Protection System
UR Series Instruction Manual
Manual P/N: 1601-0166-Y4 (GEK-113668C)
IND.CONT. EQ.
G30 Revision: 7.0x
E83849
LISTED
52TL
830745A1.CDR
GE Multilin's Quality Management
System is registered to ISO
9001:2008
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading

Summary of Contents for GE G30

  • Page 1 Digital Energy GEK-113668C G30 Generator Protection System UR Series Instruction Manual G30 Revision: 7.0x Manual P/N: 1601-0166-Y4 (GEK-113668C) 830745A1.CDR E83849 GE Digital Energy LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1 System is registered to ISO...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3: Table Of Contents

    1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 PC REQUIREMENTS ..................1-6 1.3.2 INSTALLATION....................1-6 1.3.3 CONFIGURING THE G30 FOR SOFTWARE ACCESS ........1-7 1.3.4 USING THE QUICK CONNECT FEATURE............. 1-10 1.3.5 CONNECTING TO THE G30 RELAY .............. 1-15 1.4 UR HARDWARE 1.4.1...
  • Page 4 USER-PROGRAMMABLE SELF TESTS ............5-61 5.2.13 CONTROL PUSHBUTTONS ................5-62 5.2.14 USER-PROGRAMMABLE PUSHBUTTONS............5-63 5.2.15 FLEX STATE PARAMETERS ................5-69 5.2.16 USER-DEFINABLE DISPLAYS ................5-69 5.2.17 DIRECT INPUTS/OUTPUTS ................5-72 5.2.18 TELEPROTECTION ..................5-79 5.2.19 INSTALLATION ....................5-80 5.3 REMOTE RESOURCES 5.3.1 REMOTE RESOURCES CONFIGURATION............5-81 G30 Generator Protection System GE Multilin...
  • Page 5 TELEPROTECTION INPUTS AND OUTPUTS..........5-239 5.8.12 IEC 61850 GOOSE ANALOGS..............5-241 5.8.13 IEC 61850 GOOSE INTEGERS..............5-242 5.9 TRANSDUCER INPUTS AND OUTPUTS 5.9.1 DCMA INPUTS ....................5-243 5.9.2 RTD INPUTS....................5-244 5.9.3 DCMA OUTPUTS ..................5-246 GE Multilin G30 Generator Protection System...
  • Page 6 7. COMMANDS AND 7.1 COMMANDS TARGETS 7.1.1 COMMANDS MENU ...................7-1 7.1.2 VIRTUAL INPUTS ....................7-1 7.1.3 CLEAR RECORDS .....................7-2 7.1.4 SET DATE AND TIME ..................7-2 7.1.5 RELAY MAINTENANCE ..................7-3 7.1.6 SECURITY......................7-4 7.2 TARGETS 7.2.1 TARGETS MENU ....................7-5 G30 Generator Protection System GE Multilin...
  • Page 7 UNINSTALL AND CLEAR FILES AND DATA..........11-7 11.4 REPAIRS 11.4.1 REPAIRS ......................11-8 11.5 STORAGE 11.5.1 STORAGE......................11-9 11.6 DISPOSAL 11.6.1 DISPOSAL ..................... 11-10 A. FLEXANALOG AND A.1 PARAMETER LISTS FLEXINTEGER A.1.1 FLEXANALOG ITEMS ..................A-1 A.1.2 FLEXINTEGER ITEMS ..................A-23 PARAMETERS GE Multilin G30 Generator Protection System...
  • Page 8 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP......C-21 C.6 ACSI CONFORMANCE C.6.1 ACSI BASIC CONFORMANCE STATEMENT ..........C-23 C.6.2 ACSI MODELS CONFORMANCE STATEMENT ..........C-23 C.6.3 ACSI SERVICES CONFORMANCE STATEMENT ......... C-24 viii G30 Generator Protection System GE Multilin...
  • Page 9 COUNTERS .....................E-10 E.2.4 ANALOG INPUTS ....................E-11 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY ..................F-1 F.1.2 CHANGES TO THE G30 MANUAL ..............F-1 F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ................. F-4 F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY ................F-6 INDEX...
  • Page 10 TABLE OF CONTENTS G30 Generator Protection System GE Multilin...
  • Page 11: Getting Started

    1.1 IMPORTANT PROCEDURES 1 GETTING STARTED 1.1IMPORTANT PROCEDURES Read this chapter to help guide you through the initial setup of your new G30 Generator Protection System. 1.1.1 CAUTIONS AND WARNINGS Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime.
  • Page 12: Inspection Procedure

    For product information, instruction manual updates, and the latest software updates, visit the GE Digital Energy website at http://www.gedigitalenergy.com. If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Digital Energy immediately.
  • Page 13: Ur Overview

    This new generation of equipment is easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Uni- versal Relay (UR) series meets these goals.
  • Page 14 The UR-series devices operate in a cyclic scan fashion. The device reads the inputs into an input status table, solves the logic program (FlexLogic equation), and then sets each output to the appropriate state in an output status table. Any result- ing task execution is priority interrupt-driven. Figure 1–3: UR-SERIES SCAN OPERATION G30 Generator Protection System GE Multilin...
  • Page 15: Software Architecture

    Employing OOD/OOP in the software architecture of the G30 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functional classes.
  • Page 16: Enervista Ur Setup Software

    Ethernet port of the same type as one of the UR CPU ports or a LAN connection to the UR • Internet access or a DVD drive The following qualified modems have been tested to be compliant with the G30 and the EnerVista UR Setup software: • US Robotics external 56K FaxModem 5686 •...
  • Page 17: Configuring The G30 For Software Access

    OVERVIEW The user can connect remotely to the G30 through the rear RS485 port or the rear Ethernet port with a computer running the EnerVista UR Setup software. The G30 can also be accessed locally with a computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
  • Page 18 A computer with an RS232 port and a serial cable is required. To use the RS485 port at the back of the relay, a GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
  • Page 19 11. Click the Read Order Code button to connect to the G30 device and upload the order code. If a communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to the relay setting values.
  • Page 20: Using The Quick Connect Feature

    USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the G30 from a computer through Ethernet, first assign an IP address to the relay from the front panel keyboard. Press the MENU key until the SETTINGS menu displays.
  • Page 21 Now, assign the computer an IP address compatible with the relay’s IP address. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con- nections window. Right-click the Local Area Connection icon and select Properties. GE Multilin G30 Generator Protection System 1-11...
  • Page 22 Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button. Click the “Use the following IP address” box. Enter an IP address with the first three numbers the same as the IP address of the G30 relay and the last number dif- ferent (in this example, 1.1.1.2).
  • Page 23 Minimum = 0ms, Maximum = 0ms, Average = 0 ms Pinging 1.1.1.1 with 32 bytes of data: verify the physical connection between the G30 and the computer, and double-check the programmed IP address in setting, then repeat step 2. ...
  • Page 24 Click the Quick Connect button to open the Quick Connect dialog box. Select the Ethernet interface and enter the IP address assigned to the G30, then click the Connect button. The EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Connect”...
  • Page 25: Connecting To The G30 Relay

    Device Setup menu. This feature allows the user to identify and interrogate all UR-series devices at a loca- tion. 1.3.5 CONNECTING TO THE G30 RELAY When unable to connect because of an "ACCESS VIOLATION," access Device Setup and refresh the order code for the device.
  • Page 26 The EnerVista UR Setup software has several quick action buttons to provide instant access to several functions that are often performed when using G30 relays. From the online window, users can select the relay to interrogate from a pull-down window, then click the button for the action they want to perform. The following quick action functions are available: •...
  • Page 27: Ur Hardware

    This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the G30 rear communications port. The converter terminals (+, –, GND) are connected to the G30 communication module (+, –, COM) terminals. See the CPU communica- tions ports section in chapter 3 for details.
  • Page 28: Using The Relay

    To put the relay in the “Programmed” state, press either of the VALUE keys once and then press ENTER. The face- plate Trouble LED turns off and the In Service LED turns on. 1-18 G30 Generator Protection System GE Multilin...
  • Page 29: Relay Passwords

    See the Changing Settings section in Chapter 4 for complete instructions on setting security-level passwords. 1.5.6 FLEXLOGIC CUSTOMIZATION NOTE FlexLogic equation editing is required for setting user-defined logic for customizing the relay operations. See the FlexLogic section in Chapter 5. GE Multilin G30 Generator Protection System 1-19...
  • Page 30: Commissioning

    The G30 performs a number of continual self-tests and takes the necessary action in case of any major errors (see the Relay Self-tests section in chapter 7). However, it is recommended that G30 maintenance be scheduled with other system maintenance.
  • Page 31: Product Description

    TFTP protocols, PTP (according to IEEE Std. 1588-2008 or IEC 61588), and allows access to the relay via any stan- dard web browser (G30 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the same time.
  • Page 32 2.1 INTRODUCTION 2 PRODUCT DESCRIPTION Figure 2–1: SINGLE LINE DIAGRAM, PTS ON TRANSFORMER HV SIDE (SUBSCRIPT INDICATES NUMBER) G30 Generator Protection System GE Multilin...
  • Page 33 2 PRODUCT DESCRIPTION 2.1 INTRODUCTION Figure 2–2: SINGLE LINE DIAGRAM, PTS ON TRANSFORMER LV SIDE (PROTECTION ASSIGNED TO GENERATOR NEUTRAL CTS) GE Multilin G30 Generator Protection System...
  • Page 34 Non-volatile selector switch Virtual outputs (96) Disconnect switches Percent differential VT fuse failure DNP 3.0 or IEC 60870-5-104 protocol Setting groups (6) Ethernet Global Data Protocol (optional) Time synchronization over IRIG-B or IEEE 1588 G30 Generator Protection System GE Multilin...
  • Page 35: Ordering

    2.1.2 ORDERING a) OVERVIEW The G30 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod- ules: power supply, CPU, CT/VT, contact input and output, transducer input and output, and inter-relay communications.
  • Page 36 RS422, 1 Channel RS422, 2 Channels The order codes for the reduced size vertical mount units are shown below. Table 2–4: G30 ORDER CODES (REDUCED SIZE VERTICAL UNITS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below)
  • Page 37 RS422, 2 Channels c) ORDER CODES WITH PROCESS BUS MODULES The order codes for the horizontal mount units with the process bus module are shown below. Table 2–5: G30 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS) * - F - W/X...
  • Page 38 RS422, 2 Channels The order codes for the reduced size vertical mount units with the process bus module are shown below. Table 2–6: G30 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below)
  • Page 39 2 PRODUCT DESCRIPTION 2.1 INTRODUCTION Table 2–6: G30 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below) POWER SUPPLY 125 / 250 V AC/DC power supply 24 to 48 V (DC only) power supply...
  • Page 40: Replacement Modules

    Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the serial number of your existing unit. Not all replacement modules may be applicable to the G30 relay. Only the modules specified in the order codes are available as replacement modules.
  • Page 41 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed) 8 RTD inputs INPUTS/OUTPUTS 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed) 4 DCmA inputs, 4 RTD inputs 8 DCmA inputs GE Multilin G30 Generator Protection System 2-11...
  • Page 42: Specifications

    IEEE Moderately/Very/Extremely harmonic inhibit function: Adaptive, Traditional, Disabled Inverse; IEC (and BS) A/B/C and Short harmonic inhibit mode: Per-phase, 2-out-of-3, Average Inverse; GE IAC Inverse, Short/Very/ harmonic inhibit range: 1.0 to 40.0% in steps of 0.1 Extremely Inverse; I t; FlexCurves™...
  • Page 43 97 to 98% Curve timing accuracy <16 ms at 3 × pickup at 60 Hz Operation time: at <0.90 x pickup: ±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate GE Multilin G30 Generator Protection System 2-13...
  • Page 44 ±0.5% of reading from 10 to 208 V Level accuracy: ±0.5% of reading from 10 to 208 V Curve shapes: GE IAV Inverse, Definite Time Pickup delay: 0 to 600.00 s in steps of 0.01 Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01 Reset delay: 0 to 600.00 s in steps of 0.01...
  • Page 45: User-Programmable Elements

    80 (1 through 20 of pickup) NAND (2 to 16 inputs), latch (reset-domi- Time delay: 0 to 65535 ms in steps of 1 nant), edge detectors, timers Inputs: any logical variable, contact, or virtual input GE Multilin G30 Generator Protection System 2-15...
  • Page 46: Monitoring

    USER-PROGRAMMABLE FAULT REPORT tact input state; contact output state Number of elements: Data storage: in non-volatile memory Pre-fault trigger: any FlexLogic operand Fault trigger: any FlexLogic operand Recorder quantities: 32 (any FlexAnalog value) 2-16 G30 Generator Protection System GE Multilin...
  • Page 47: Metering

    ±0.01 Hz (when voltage signal is used for frequency measurement) Parameters: three-phase only I = 0.1 to 0.25 pu: ±0.05 Hz Update rate: 50 ms I > 0.25 pu: ±0.02 Hz (when current signal is used for frequency measurement) GE Multilin G30 Generator Protection System 2-17...
  • Page 48: Inputs

    LOW RANGE Maximum DC voltage: 60 V Nominal DC voltage: 24 to 48 V Voltage loss hold-up: 20 ms duration at nominal Minimum DC voltage: 20 V NOTE: Low range is DC only. 2-18 G30 Generator Protection System GE Multilin...
  • Page 49: Outputs

    Operate time: < 0.6 ms FORM-A VOLTAGE MONITOR Internal Limiting Resistor: 100 Ω, 2 W Applicable voltage: approx. 15 to 250 V DC Trickle current: approx. 1 to 2.5 mA GE Multilin G30 Generator Protection System 2-19...
  • Page 50: Communication Protocols

    –14 dBm power Typical distance 2 km Duplex full/half Redundancy ETHERNET (10/100 MB TWISTED PAIR) Modes: 10 MB, 10/100 MB (auto-detect) Connector: RJ45 SIMPLE NETWORK TIME PROTOCOL (SNTP) clock synchronization error: <10 ms (typical) 2-20 G30 Generator Protection System GE Multilin...
  • Page 51: Inter-Relay Communications

    – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Noise: 0 dB Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days). GE Multilin G30 Generator Protection System 2-21...
  • Page 52: Type Tests

    NKCR Safety IEC 60255-27 Insulation: class 1, Pollution degree: 2, Over voltage cat II 2.2.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. 2-22 G30 Generator Protection System GE Multilin...
  • Page 53: Approvals

    To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. GE Multilin G30 Generator Protection System 2-23...
  • Page 54 2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2-24 G30 Generator Protection System GE Multilin...
  • Page 55: Hardware

    HORIZONTAL UNITS The G30 Generator Protection System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains addi- tional user-programmable pushbuttons and LED indicators.
  • Page 56 VERTICAL UNITS The G30 Generator Protection System is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 57 3 HARDWARE 3.1 DESCRIPTION Figure 3–4: G30 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin G30 Generator Protection System...
  • Page 58 3.1 DESCRIPTION 3 HARDWARE Figure 3–5: G30 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For side mounting G30 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Digital Energy website: • GEK-113180: UR-Series UR-V Side-Mounting Front Panel Assembly Instructions •...
  • Page 59 3 HARDWARE 3.1 DESCRIPTION Figure 3–6: G30 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin G30 Generator Protection System...
  • Page 60 3.1 DESCRIPTION 3 HARDWARE Figure 3–7: G30 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL) G30 Generator Protection System GE Multilin...
  • Page 61: Rear Terminal Layout

    (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments. Figure 3–9: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin G30 Generator Protection System...
  • Page 62: Wiring

    3.2 WIRING 3 HARDWARE 3.2WIRING 3.2.1 TYPICAL WIRING Figure 3–10: TYPICAL WIRING DIAGRAM (T MODULE SHOWN FOR CPU) G30 Generator Protection System GE Multilin...
  • Page 63 3 HARDWARE 3.2 WIRING Figure 3–11: TYPICAL WIRING DIAGRAM, PTS ON THE TRANSFORMER LV-SIDE (T MODULE SHOWN FOR CPU) GE Multilin G30 Generator Protection System...
  • Page 64 3.2 WIRING 3 HARDWARE Figure 3–12: TYPICAL WIRING DIAGRAM, NO TRANSFORMER (T MODULE SHOWN FOR CPU) 3-10 G30 Generator Protection System GE Multilin...
  • Page 65: Dielectric Strength

    (see the Self-test errors section in chapter 7) or control power is lost, the relay is de-energize. For high reliability systems, the G30 has a redundant option in which two G30 power supplies are placed in parallel on the bus.
  • Page 66: Ct/Vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown as follows. Twisted-pair cabling on the zero-sequence CT is recommended. 3-12 G30 Generator Protection System GE Multilin...
  • Page 67 Substitute the tilde “~” symbol with the slot position of the module in the following figure. NOTE Current inputs Voltage inputs 8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs) Current inputs 8H, 8J, 8N, and 8R modules (8 CTs) 842766A3.CDR Figure 3–15: CT/VT MODULE WIRING GE Multilin G30 Generator Protection System 3-13...
  • Page 68: Process Bus Modules

    3.2.5 PROCESS BUS MODULES The G30 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bidirectional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
  • Page 69 Logic operand driving the contact output should be given a reset delay of 10 ms to prevent damage of the output contact (in situations when the element initiating the contact output is bouncing, at val- ues in the region of the pickup value). GE Multilin G30 Generator Protection System 3-15...
  • Page 70 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs 3-16 G30 Generator Protection System GE Multilin...
  • Page 71 Not Used ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin G30 Generator Protection System 3-17...
  • Page 72 3.2 WIRING 3 HARDWARE Figure 3–17: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) 3-18 G30 Generator Protection System GE Multilin...
  • Page 73 3 HARDWARE 3.2 WIRING Figure 3–18: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output con- nections. GE Multilin G30 Generator Protection System 3-19...
  • Page 74 Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. 3-20 G30 Generator Protection System GE Multilin...
  • Page 75 CONTACT INPUT 2 AUTO-BURNISH = OFF CONTACT INPUT 1 AUTO-BURNISH = OFF CONTACT INPUT 2 AUTO-BURNISH = ON CONTACT INPUT 1 AUTO-BURNISH = ON CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–21: AUTO-BURNISH DIP SWITCHES GE Multilin G30 Generator Protection System 3-21...
  • Page 76 3.2 WIRING 3 HARDWARE The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, check the auto- burnish functionality using an oscilloscope. NOTE 3-22 G30 Generator Protection System GE Multilin...
  • Page 77: Transducer Inputs/Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–22: TRANSDUCER INPUT/OUTPUT MODULE WIRING The following figure show how to connect RTDs. GE Multilin G30 Generator Protection System 3-23...
  • Page 78 3.2 WIRING 3 HARDWARE Figure 3–23: RTD CONNECTIONS 3-24 G30 Generator Protection System GE Multilin...
  • Page 79: Rs232 Faceplate Port

    3.2.8 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the G30 faceplate for programming with a computer. All that is required to use this interface is a computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
  • Page 80 This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the G30 COM terminal (#3); others function cor- rectly only if the common wire is connected to the G30 COM terminal, but insulated from the shield.
  • Page 81 NOTE The fiber optic communication ports allow for fast and efficient communications between relays at 100 Mbps. Optical fiber can be connected to the relay supporting a wavelength of 1310 nm in multi-mode. GE Multilin G30 Generator Protection System 3-27...
  • Page 82: Irig-B

    IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the G30 operates an internal oscillator with 1 µs resolution and accuracy.
  • Page 83: Direct Input/Output Communications

    1 to channel 2 on UR2, the setting should be “Enabled” on UR2. This DIRECT I/O CHANNEL CROSSOVER forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1. GE Multilin G30 Generator Protection System 3-29...
  • Page 84 These modules are listed in the following table. All fiber modules use ST type connectors. Not all the direct input and output communications modules outlined in the table are applicable to the G30. Use your order code with the tables in chapter 2 to determine applicable options.
  • Page 85: Fiber: Led And Eled Transmitters

    The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules. Figure 3–31: LED AND ELED FIBER MODULES 3.3.3 FIBER-LASER TRANSMITTERS The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module. Figure 3–32: LASER FIBER MODULES GE Multilin G30 Generator Protection System 3-31...
  • Page 86 Observing any fiber transmitter output can injure the eye. When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver. 3-32 G30 Generator Protection System GE Multilin...
  • Page 87: Interface

    Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. Replace the top cover and the cover screw. GE Multilin G30 Generator Protection System 3-33...
  • Page 88 For connection to a higher order system (UR- to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). 3-34 G30 Generator Protection System GE Multilin...
  • Page 89 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–37: G.703 DUAL LOOPBACK MODE GE Multilin G30 Generator Protection System 3-35...
  • Page 90: Rs422 Interface

    UR–RS422 channels is synchronized via the send timing leads on data module 1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. 3-36 G30 Generator Protection System GE Multilin...
  • Page 91 Figure 3–40: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION Data module 1 provides timing to the G30 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they vary by manufacturer.
  • Page 92: Rs422 And Fiber Interface

    G.703 and fiber interfaces. When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the maximum optical input power to the receiver. Figure 3–43: G.703 AND FIBER INTERFACE CONNECTION 3-38 G30 Generator Protection System GE Multilin...
  • Page 93: Ieee C37.94 Interface

    5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of G30 communi- cation for two and three terminal applications.
  • Page 94 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. 3-40 G30 Generator Protection System GE Multilin...
  • Page 95 3 HARDWARE 3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS Figure 3–44: IEEE C37.94 TIMING SELECTION SWITCH SETTING GE Multilin G30 Generator Protection System 3-41...
  • Page 96 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid 3-42 G30 Generator Protection System GE Multilin...
  • Page 97: C37.94Sm Interface

    5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of G30 communi- cation for two and three terminal applications.
  • Page 98 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. 3-44 G30 Generator Protection System GE Multilin...
  • Page 99 Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow- ing figure. Figure 3–47: STATUS LEDS The clock configuration LED status is as follows: • Flashing green — loop timing mode while receiving a valid data packet GE Multilin G30 Generator Protection System 3-45...
  • Page 100 Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid 3-46 G30 Generator Protection System GE Multilin...
  • Page 101: Human Interfaces

    In online mode, you can communicate with the device in real-time. The EnerVista UR Setup software is provided with every G30 relay and runs on Microsoft Windows 95, 98, NT, 2000, ME, and XP. This chapter provides a summary of the basic EnerVista UR Setup software interface features. The EnerVista UR Setup Help File provides details for getting started and using the EnerVista UR Setup software interface.
  • Page 102 Site List window are automatically sent to the online communicating device. g) FIRMWARE UPGRADES The firmware of a G30 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
  • Page 103: Enervista Ur Setup Main Window

    Settings list control bar window Device data view windows, with common tool bar Settings file data view windows, with common tool bar Workspace area with data view tabs Status bar 10. Quick action hot links GE Multilin G30 Generator Protection System...
  • Page 104 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW G30 Generator Protection System GE Multilin...
  • Page 105: Extended Enervista Ur Setup Features

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. GE Multilin G30 Generator Protection System...
  • Page 106 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. G30 Generator Protection System GE Multilin...
  • Page 107 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND GE Multilin G30 Generator Protection System...
  • Page 108 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. G30 Generator Protection System GE Multilin...
  • Page 109: Securing And Locking Flexlogic Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic equation. GE Multilin G30 Generator Protection System...
  • Page 110 FlexLogic entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. 4-10 G30 Generator Protection System GE Multilin...
  • Page 111: Settings File Traceability

    When a settings file is transferred to a G30 device, the date, time, and serial number of the G30 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the G30 actual values at any later date to determine if security has been compromised.
  • Page 112 4 HUMAN INTERFACES The transfer date of a setting file written to a G30 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 113 ONLINE DEVICE TRACEABILITY INFORMATION The G30 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 114: Faceplate Interface

    The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over the faceplate that must be removed in order to access the keypad panel. The following figure shows the horizontal arrange- ment of the faceplate panels. Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS 4-14 G30 Generator Protection System GE Multilin...
  • Page 115: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. GE Multilin G30 Generator Protection System 4-15...
  • Page 116 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack- age of every G30, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
  • Page 117 User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program the operation of the LEDs on these panels. GE Multilin G30 Generator Protection System 4-17...
  • Page 118: Custom Labeling Of Leds

    EnerVista UR Setup software is installed and operational • The G30 settings have been saved to a settings file • The G30 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc and printed •...
  • Page 119 Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the G30 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
  • Page 120 4 HUMAN INTERFACES Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the G30 enhanced front panel and insert the custom labels. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay.
  • Page 121 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the G30 enhanced front panel and insert the custom labels.
  • Page 122 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This attaches the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. 4-22 G30 Generator Protection System GE Multilin...
  • Page 123: Display

    INTRODUCTION The G30 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, that can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initi- ated from faceplate keypad or automatically initiated from a FlexLogic operand.
  • Page 124: Menus

    Press the MENU key to select a header display page (top-level menu). The header title appears momentarily followed by a header display page menu item. Each press of the MENU key advances through the following main heading pages: • Actual values • Settings 4-24 G30 Generator Protection System GE Multilin...
  • Page 125 4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE • Commands • Targets • User displays (when enabled) GE Multilin G30 Generator Protection System 4-25...
  • Page 126 Pressing the MESSAGE DOWN key displays the second setting sub-header associ-  PROPERTIES ated with the Product Setup header.  Press the MESSAGE RIGHT key once more to display the first setting for Display FLASH MESSAGE Properties. TIME: 1.0 s 4-26 G30 Generator Protection System GE Multilin...
  • Page 127: Changing Settings

    ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length, but user-defined in character. They can be upper case letters, lower case letters, numerals, and a selection of special characters. GE Multilin G30 Generator Protection System 4-27...
  • Page 128: Settings

    When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the In Service LED turns on. e) ENTERING INITIAL PASSWORDS The G30 supports password entry from a local or remote connection. 4-28 G30 Generator Protection System...
  • Page 129 By default, when an incorrect Command or Setting password has been entered via the faceplate interface three times within three minutes, the FlexLogic™ operand is set to “On” and the G30 does not allow settings or LOCAL ACCESS DENIED command level access via the faceplate interface for the next five minutes.
  • Page 130 4 HUMAN INTERFACES By default, when an incorrect Command or Setting password has been entered via any external communications interface three times within three minutes, the FlexLogic™ operand is set to and the G30 does not REMOTE ACCESS DENIED “ ”...
  • Page 131: Overview

    See page 5-79.   INSTALLATION See page 5-80.   SETTINGS  AC INPUTS See page 5-82.  SYSTEM SETUP   POWER SYSTEM See page 5-83.   SIGNAL SOURCES See page 5-84.  GE Multilin G30 Generator Protection System...
  • Page 132 See page 5-205.   FREQUENCY RATE See page 5-206.  OF CHANGE  FREQUENCY OOB See page 5-208.  ACCUMULATION  SYNCHROCHECK See page 5-210.   DIGITAL ELEMENTS See page 5-214.  G30 Generator Protection System GE Multilin...
  • Page 133  DCMA INPUTS See page 5-243.  TRANSDUCER I/O   RTD INPUTS See page 5-244.   DCMA OUTPUTS See page 5-246.   SETTINGS TEST MODE See page 5-250.  TESTING FUNCTION: Disabled GE Multilin G30 Generator Protection System...
  • Page 134: Introduction To Elements

    For wye-connected VTs, the primary and secondary bases quanitities are as before, but the secondary voltage (here a phase-to-phase ground value) is: 13800 --------------- - × --------- - 66.4 V (EQ 5.2) 14400 Many settings are common to most elements and are discussed below: G30 Generator Protection System GE Multilin...
  • Page 135: Introduction To Ac Sources

    The same considerations apply to transformer winding 2. The protection elements require access to the net current for transformer protection, but some elements may need access to the individual currents from CT1 and CT2. GE Multilin G30 Generator Protection System...
  • Page 136 INCREASING SLOT POSITION LETTER --> CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 < bank 1 > < bank 3 > < bank 5 > < bank 2 > < bank 4 > < bank 6 > G30 Generator Protection System GE Multilin...
  • Page 137 Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and will display them in the appropriate section in the sequence of the banks (as described above) as follows for a maximum configuration: F1, F5, M1, M5, U1, and U5. GE Multilin G30 Generator Protection System...
  • Page 138: Product Setup

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the G30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 139 NOTE If a remote connection is established, local passcodes are not visible. NOTE c) REMOTE PASSWORDS The remote password settings are visible only from a remote connection via the EnerVista UR Setup software. GE Multilin G30 Generator Protection System...
  • Page 140 INVALID ATTEMPTS BEFORE LOCKOUT The G30 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.
  • Page 141 ACCESS AUTH TIMEOUT immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. GE Multilin G30 Generator Protection System 5-11...
  • Page 142: Cybersentry Security

    Ethernet-to-RS485 gateway is not supported. Because these gateways do not support the secure protocols necessary to communicate with such devices, the connection cannot be established. Use the device as a non-CyberSentry device. 5-12 G30 Generator Protection System GE Multilin...
  • Page 143 UR device for successful authentication, and the shortname is a short, optional alias that can be used in place of the IP address. client 10.0.0.2/24 { secret = testing123 shortname = private-network-1 e. In the <Path_to_Radius>\etc\raddb folder, create a file called dictionary.ge and add the following content. # ########################################################## # GE VSA's ############################################################ VENDOR...
  • Page 144 Set up the RADIUS parameters on the UR as follows. Access Device > Settings > Product Setup > Security. Con- figure the IP address and ports for the RADIUS server. Leave the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf file.
  • Page 145 The “login setting” in this menu is similar to the login setting described in PATH: SETTINGS > PRODUCT SETUP > SECU- RITY except for the factory role. Passwords are stored in text format. No encryption is applied. Notes: NOTE GE Multilin G30 Generator Protection System 5-15...
  • Page 146 Range: Enabled, Disabled FACTORY SERVICE: MESSAGE MODE: Disabled  SELF TESTS MESSAGE See below  Range: Enabled, Disabled SUPERVISOR ROLE: MESSAGE Disabled Range: 1 to 9999 minutes SERIAL INACTIVITY MESSAGE TIMEOUT: 1 min 5-16 G30 Generator Protection System GE Multilin...
  • Page 147 Example: If this setting is "Yes" and an attempt is made to change settings or upgrade the firmware, the UR device denies the setting changes and denies upgrading the firmware. If this setting is "No", the UR device accepts setting changes and firmware upgrade. This role is disabled by default. GE Multilin G30 Generator Protection System 5-17...
  • Page 148 Username — 255 chars maximum, but in the security log it is truncated to 20 characters IP address — Device IP address Role — 16 bit unsigned, of type format F617 ENUMERATION ROLE None Administrator Supervisor Engineer Operator Factory 5-18 G30 Generator Protection System GE Multilin...
  • Page 149: Display Properties

    DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough during programming or reading of actual values. GE Multilin G30 Generator Protection System 5-19...
  • Page 150 Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The G30 applies a cut- off value to the magnitudes and angles of the measured currents.
  • Page 151: Clear Relay Records

    Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programma- ble pushbuttons to clear specific records are typical applications for these commands. Since the G30 responds to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
  • Page 152: Communications

    0 ms The G30 is equipped with two independent serial communication ports. The faceplate RS232 port is intended for local use and is fixed at 19200 baud and no parity. The rear COM2 port is RS485. The RS485 port has settings for baud rate and par- ity.
  • Page 153 EnerVista, and access to the public network shared on the same LAN. No redundancy is provided. Figure 5–3: NETWORK CONFIGURATION FOR SINGLE LAN Public Network SCADA EnerVista Software LAN1 ML3000 IP1/ MAC1 859708A2.vsd GE Multilin G30 Generator Protection System 5-23...
  • Page 154 LAN3, to which port 3 (P3) is connected. There is no redundancy. Figure 5–5: MULTIPLE LANS, NO REDUNDANCY Public Network SCADA EnerVista Software LAN1 LAN2 LAN3 ML3000 ML3000 ML3000 IP1/ IP2/ IP3/ MAC2 MAC3 MAC1 859710A2.vsd 5-24 G30 Generator Protection System GE Multilin...
  • Page 155 IP address. The client software (EnerVista UR Setup, for example) must be configured to use the correct port number if these settings are used. GE Multilin G30 Generator Protection System 5-25...
  • Page 156 This allows the EnerVista UR Setup software to be used on the port. The UR operates as a Modbus slave device only. When using Modbus protocol on the RS232 port, the G30 responds regardless of the pro- MODBUS SLAVE ADDRESS grammed.
  • Page 157 DEADBAND: 30000 Range: 0 to 100000000 in steps of 1 DNP OTHER DEFAULT MESSAGE DEADBAND: 30000 Range: 1 to 10080 min. in steps of 1 DNP TIME SYNC IIN MESSAGE PERIOD: 1440 min GE Multilin G30 Generator Protection System 5-27...
  • Page 158 TIMEOUT: 120 s The G30 supports the Distributed Network Protocol (DNP) version 3.0. The G30 can be used as a DNP slave device con- nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the G30 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the G30 at one time.
  • Page 159 DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the G30 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.
  • Page 160 (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP master can operate a single point for both trip and close, or raise and lower, operations. The G30 can be configured to support paired control points, with each paired control point operating two virtual inputs.
  • Page 161 The G30 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over Ethernet. The G30 operates as an IEC 61850 server. The Remote inputs and out- puts section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
  • Page 162 IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In G30 releases previous to 5.0x, this name string was repre- sented by the setting.
  • Page 163 DESTINATION MAC address; the least significant bit of the first byte must be set. In G30 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the G30) and setting the multicast bit.
  • Page 164 The G30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 165 Configure the transmission dataset. Configure the GOOSE service settings. Configure the data. The general steps required for reception configuration are: Configure the reception dataset. Configure the GOOSE service settings. Configure the data. GE Multilin G30 Generator Protection System 5-35...
  • Page 166 MMXU1 HZ DEADBAND change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency. The G30 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. Configure the reception dataset by making the following changes in the ...
  • Page 167 IEC61850 GOOSE ANALOG INPUT 1 UNITS The GOOSE analog input 1 can now be used as a FlexAnalog value in a FlexElement or in other settings. The G30 must be rebooted (control power removed and re-applied) before these settings take effect.
  • Page 168 DNA and UserSt bit pairs that are included in GSSE messages. To set up a G30 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and “GGIO3.ST.Ind2.stVal”.
  • Page 169 CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta- tus values in the G30. Clients will still be able to connect to the server (G30 relay), but most data values will not be updated.
  • Page 170 (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard. Changes to the logical node prefixes will not take effect until the G30 is restarted. The main menu for the IEC 61850 MMXU deadbands is shown below.
  • Page 171 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the G30 virtual inputs.
  • Page 172 GGIO1 (binary status values). The settings allow the selection of FlexInteger values for each GGIO5 integer value point. It is intended that clients use GGIO5 to access generic integer values from the G30. Additional settings are provided to allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger values to the GGIO5 integer inputs.
  • Page 173 ITEM 64 attributes supported by the G30. Changes to the dataset will only take effect when the G30 is restarted. It is recommended to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1, GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
  • Page 174 Menu”. Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the UR and a computer to an Ethernet network, then enter the IP address of the G30 into the “Address”...
  • Page 175 NUMBER: The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the G30 over a network. The G30 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the G30 contains a list and description of all available files (event records, oscillography, etc.).
  • Page 176 IEC ------- DEFAULT THRESHOLD M_ME_NC_1 analog data. These settings group the G30 analog data into types: current, voltage, power, energy, and other. Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger...
  • Page 177 MESSAGE (Modbus register address range) Fast exchanges (50 to 1000 ms) are generally used in control schemes. The G30 has one fast exchange (exchange 1) and two slow exchanges (exchange 2 and 3). The settings menu for the slow EGD exchanges is shown below: ...
  • Page 178: Modbus User Map

    EXCH 1 DATA ITEM 1 to 20/50: These settings specify the data items that are part of this EGD exchange. Almost any data from the G30 memory map can be configured to be included in an EGD exchange. The settings are the starting Modbus register address for the data item in decimal format.
  • Page 179 2) connection to a network device that does not support the PTP peer delay mechanism, 3) jitter substantially greater than 1 µs in received event messages, and 4) certain non-compliant announce and sync message update rates. GE Multilin G30 Generator Protection System 5-49...
  • Page 180 It is provided in compliance with PP. As these messages have a destination address that indicates they are not to be bridged, their VLAN ID serves no function, and so may be left at its default value. 5-50 G30 Generator Protection System GE Multilin...
  • Page 181 G30 clock is closely synchronized with the SNTP/NTP server. It takes up to two minutes for the G30 to signal an SNTP self-test error if the server is offline.
  • Page 182 5.2 PRODUCT SETUP 5 SETTINGS When the is set to 0, the change takes effect when the G30 is restarted. SNTP UDP PORT NUMBER NOTE d) LOCAL TIME    PATH: SETTINGS PRODUCT SETUP REAL TIME CLOCK LOCAL TIME Range: –24.0 to 24.0 hrs in steps of 0.5...
  • Page 183: User-Programmable Fault Report

    The user programmable record contains the following information: the user-programmed relay name, detailed firmware revision (7.0x, for example) and relay model (G30), the date and time of trigger, the name of pre-fault trigger (a specific FlexLogic operand), the name of fault trigger (a specific FlexLogic operand), the active setting group at pre-fault trigger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger), and fault values of all programmed analog channels (at the fault trigger).
  • Page 184: Oscillography

    Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. 5-54 G30 Generator Protection System GE Multilin...
  • Page 185 IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. GE Multilin G30 Generator Protection System 5-55...
  • Page 186: Data Logger

    The relay automatically partitions the available memory between the channels in use. Exam- ple storage capacities for a system frequency of 60 Hz are shown in the following table. 5-56 G30 Generator Protection System GE Multilin...
  • Page 187 – entering this number via the relay keypad will cause the corresponding parameter to be displayed. • DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not selected to “Off” without over-writing old data. GE Multilin G30 Generator Protection System 5-57...
  • Page 188: User-Programmable Leds

    The test responds to the position and rising edges of the control input defined by the set- LED TEST CONTROL ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed. 5-58 G30 Generator Protection System GE Multilin...
  • Page 189 2. Once stage 2 has started, the pushbutton can be released. When stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton. GE Multilin G30 Generator Protection System 5-59...
  • Page 190 LED 19 operand LED 8 operand LED 20 operand LED 9 operand LED 21 operand LED 10 operand LED 22 operand LED 11 operand LED 23 operand LED 12 operand LED 24 operand 5-60 G30 Generator Protection System GE Multilin...
  • Page 191: User-Programmable Self Tests

    ANY SELF-TEST mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in chapter 7 for additional information on major and minor self-test alarms. GE Multilin G30 Generator Protection System 5-61...
  • Page 192: Control Pushbuttons

    The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–7: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the G30 is ordered with the twelve user-programmable pushbutton option. STATUS EVENT CAUSE...
  • Page 193: User-Programmable Pushbuttons

    PUSHBTN 1 DROP-OUT MESSAGE TIME: 0.00 s Range: FlexLogic operand PUSHBTN 1 LED CTL: MESSAGE Range: Disabled, Normal, High Priority PUSHBTN 1 MESSAGE: MESSAGE Disabled Range: Disabled, Enabled PUSHBUTTON 1 MESSAGE EVENTS: Disabled GE Multilin G30 Generator Protection System 5-63...
  • Page 194 The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the set- PUSHBTN 1 RESET ting or by directly pressing the associated active front panel pushbutton. 5-64 G30 Generator Protection System GE Multilin...
  • Page 195 This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer. GE Multilin G30 Generator Protection System 5-65...
  • Page 196 “Normal” if the setting is “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. 5-66 G30 Generator Protection System GE Multilin...
  • Page 197 Off = 0 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–12: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) GE Multilin G30 Generator Protection System 5-67...
  • Page 198 User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via EnerVista UR Setup with the Maintenance > Enable Pushbutton command. NOTE 5-68 G30 Generator Protection System GE Multilin...
  • Page 199: Flex State Parameters

    DEFAULT MESSAGE TIMEOUT • USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL setting. Any FlexLogic operand (in particular, the user-programmable pushbutton operands), can be used to navigate the programmed displays. GE Multilin G30 Generator Protection System 5-69...
  • Page 200 (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this conversion). 5-70 G30 Generator Protection System GE Multilin...
  • Page 201 If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different. NOTE GE Multilin G30 Generator Protection System 5-71...
  • Page 202: Direct Inputs/Outputs

    “Yes”), all direct output messages should be received back. If not, the direct input/output ring CH2 RING CONFIGURATION break self-test is triggered. The self-test error is signaled by the FlexLogic operand. DIRECT RING BREAK 5-72 G30 Generator Protection System GE Multilin...
  • Page 203 The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the Inputs and outputs section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged. GE Multilin G30 Generator Protection System 5-73...
  • Page 204 UR IED 1 BLOCK UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–15: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application. 5-74 G30 Generator Protection System GE Multilin...
  • Page 205 The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. GE Multilin G30 Generator Protection System 5-75...
  • Page 206 Inputs and outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This could be accomplished using a dual-ring configuration as shown below. 5-76 G30 Generator Protection System GE Multilin...
  • Page 207 EVENTS: Disabled The G30 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
  • Page 208 MESSAGE EVENTS: Disabled The G30 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre- turned messages.
  • Page 209: Teleprotection

    On two- terminals two-channel systems, the same is transmitted over LOCAL RELAY ID NUMBER both channels; as such, only the has to be programmed on the receiving end. TERMINAL 1 ID NUMBER GE Multilin G30 Generator Protection System 5-79...
  • Page 210: Installation

    "Programmed" state. UNIT NOT PROGRAMMED setting allows the user to uniquely identify a relay. This name will appear on generated reports. RELAY NAME 5-80 G30 Generator Protection System GE Multilin...
  • Page 211: Remote Resources Configuration

    Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the G30 process card and specific Brick. The relay is then configured to measure spe- cific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 212: System Setup

    1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then a pickup level of 1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). 5-82 G30 Generator Protection System GE Multilin...
  • Page 213: Power System

    PHASE ROTATION: MESSAGE Range: FlexLogic operand REVERSE PH ROTATION: MESSAGE Range: SRC 1, SRC 2, SRC 3, SRC 4 FREQUENCY AND PHASE MESSAGE REFERENCE: SRC 1 Range: Disabled, Enabled FREQUENCY TRACKING: MESSAGE Enabled GE Multilin G30 Generator Protection System 5-83...
  • Page 214: Signal Sources

    FREQUENCY TRACKING frequency applications. NOTE The frequency tracking feature functions only when the G30 is in the “Programmed” mode. If the G30 is “Not Pro- grammed”, then metering values are available but can exhibit significant errors. NOTE Systems with an ACB phase sequence require special consideration. Refer to the Phase relationships of three-phase transformers sub-section of chapter 5.
  • Page 215 CT wiring problem. A disturbance detector is provided for each source. The 50DD function responds to the changes in magnitude of the sequence currents. The disturbance detector scheme logic is as follows: GE Multilin G30 Generator Protection System 5-85...
  • Page 216 This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys- tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and the CT/VT inputs that are used to provide the data. 5-86 G30 Generator Protection System GE Multilin...
  • Page 217: Transformer

    5.4.4 TRANSFORMER a) MAIN MENU   PATH: SETTINGS SYSTEM SETUP TRANSFORMER  TRANSFORMER  GENERAL See below.    WINDING 1 MESSAGE See below.   WINDING 2 MESSAGE See below.  GE Multilin G30 Generator Protection System 5-87...
  • Page 218 The settings specific to each winding are shown above. The following discussion is applicable to the G30 device protecting the GSU, assuming that the LV winding CTs are on the neutral side of the generator and the HV winding CTs are on the system side of the step-up delta-wye transformer. It is also assumed that CTs are differentially connected as per regular transformer differential applications, as shown in the Typical wiring, VT on the LV side of the Transformer diagram in the Applications of Settings chapter.
  • Page 219 The reason the source phase sequence must be stated when describing the winding phase relationships is that these rela- tionships change when the phase sequence changes. The example shown below shows why this happens, using a trans- former described in IEC nomenclature as a type “Yd1” or in GE Multilin nomenclature as a “Y/d30.” GE Multilin...
  • Page 220 Note that the delta winding currents leads the wye winding currents by 30°, (which is a type Yd11 in IEC nomenclature and a type Y/d330 in GE Multilin nomenclature) which is in disagreement with the transformer nameplate. This is because the physical connections and hence the equations used to calculate current for the delta winding have not changed.
  • Page 221 CTs or tapped relay windings were used to minimize this error. The G30 automatically corrects for CT mismatch errors. All currents are magnitude compensated to be in units of the CTs of one winding before the calculation of differential and restraint quantities.
  • Page 222 The G30 performs this phase angle compensation and zero sequence removal automatically, based on the settings entered for the transformer. All CTs are connected Wye (polarity markings pointing away from the transformer). All currents are phase and zero sequence compensated internally before the calculation of differential and restraint quantities.
  • Page 223 ------ - I – – ------ - I ------ - I ------ - I ------ - I – – ------ - I ------ - I ------ - I ------ - I – – GE Multilin G30 Generator Protection System 5-93...
  • Page 224 = magnitude, phase and zero sequence compensated winding w phase currents = magnitude compensation factor for winding w (see previous sections) [ ] I , and = phase and zero sequence compensated winding w phase currents (see earlier) 5-94 G30 Generator Protection System GE Multilin...
  • Page 225 2 [ ] max I (EQ 5.23) 1 [ ] I 2 [ ] max I (EQ 5.24) where , and are the phase differential currents and , and are the phase restraint currents. GE Multilin G30 Generator Protection System 5-95...
  • Page 226: Breakers

    Range: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled 5-96 G30 Generator Protection System GE Multilin...
  • Page 227 1. The number of breaker control elements is dependent on the number of CT/VT modules specified with the G30. The follow- ing settings are available for each breaker control element.
  • Page 228 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–26: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the G30 is in “Programmed” mode and not in the local control mode. NOTE 5-98 G30 Generator Protection System...
  • Page 229 5 SETTINGS 5.4 SYSTEM SETUP Figure 5–27: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2) GE Multilin G30 Generator Protection System 5-99...
  • Page 230: Disconnect Switches

    For greater security in determination of the switch pole position, both the 89/a and 89/b auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches depends on the number of the CT/VT modules ordered with the G30. •...
  • Page 231 This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the G30 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin...
  • Page 232 5.4 SYSTEM SETUP 5 SETTINGS Figure 5–28: DISCONNECT SWITCH SCHEME LOGIC 5-102 G30 Generator Protection System GE Multilin...
  • Page 233: Flexcurves

    1.03 pu. It is recommended to set the two times to a similar value; otherwise, the linear approximation may result in NOTE undesired behavior for the operating quantity that is close to 1.00 pu. GE Multilin G30 Generator Protection System 5-103...
  • Page 234 The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE 5-104 G30 Generator Protection System GE Multilin...
  • Page 235 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the G30 are displayed in the following graphs. GE Multilin G30 Generator Protection System...
  • Page 236 CURRENT (multiple of pickup) 842723A1.CDR Figure 5–32: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–33: RECLOSER CURVES GE113, GE120, GE138 AND GE142 5-106 G30 Generator Protection System GE Multilin...
  • Page 237 Figure 5–34: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–35: RECLOSER CURVES GE131, GE141, GE152, AND GE200 GE Multilin G30 Generator Protection System 5-107...
  • Page 238 Figure 5–36: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–37: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 5-108 G30 Generator Protection System GE Multilin...
  • Page 239 Figure 5–38: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–39: RECLOSER CURVES GE119, GE135, AND GE202 GE Multilin G30 Generator Protection System 5-109...
  • Page 240: Flexlogic

    Figure 5–40: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the G30 are represented by flags (or FlexLogic operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an ele- ment from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output.
  • Page 241 Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper- ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 5–9: G30 FLEXLOGIC OPERAND TYPES OPERAND TYPE STATE...
  • Page 242 5.5 FLEXLOGIC 5 SETTINGS The operands available for this relay are listed alphabetically by types in the following table. Table 5–10: G30 FLEXLOGIC OPERANDS (Sheet 1 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed...
  • Page 243 5 SETTINGS 5.5 FLEXLOGIC Table 5–10: G30 FLEXLOGIC OPERANDS (Sheet 2 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: CT FAIL PKP CT fail has picked up CT fail CT FAIL OP CT fail has dropped out ELEMENT: Counter 1 HI Digital counter 1 output is ‘more than’...
  • Page 244 5.5 FLEXLOGIC 5 SETTINGS Table 5–10: G30 FLEXLOGIC OPERANDS (Sheet 3 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: NEG SEQ DIR OC1 FWD Negative-sequence directional overcurrent 1 forward has operated Negative-sequence NEG SEQ DIR OC1 REV Negative-sequence directional overcurrent 1 reverse has operated...
  • Page 245 5 SETTINGS 5.5 FLEXLOGIC Table 5–10: G30 FLEXLOGIC OPERANDS (Sheet 4 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: PHASE UV1 PKP At least one phase of phase undervoltage 1 has picked up Phase undervoltage PHASE UV1 OP At least one phase of phase undervoltage 1 has operated...
  • Page 246 5.5 FLEXLOGIC 5 SETTINGS Table 5–10: G30 FLEXLOGIC OPERANDS (Sheet 5 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: SWITCH 1 OFF CMD Disconnect switch 1 open command initiated Disconnect switch SWITCH 1 ON CMD Disconnect switch 1 close command initiated SWITCH 1 ΦA BAD ST...
  • Page 247 5 SETTINGS 5.5 FLEXLOGIC Table 5–10: G30 FLEXLOGIC OPERANDS (Sheet 6 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: XFMR PCNT DIFF PKP A Transformer percent differential protection has picked up in phase A Transformer percent XFMR PCNT DIFF PKP B...
  • Page 248 5.5 FLEXLOGIC 5 SETTINGS Table 5–10: G30 FLEXLOGIC OPERANDS (Sheet 7 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION LED INDICATORS: LED IN SERVICE Asserted when the front panel IN SERVICE LED is on Fixed front panel LED TROUBLE Asserted when the front panel TROUBLE LED is on...
  • Page 249 5 SETTINGS 5.5 FLEXLOGIC Table 5–10: G30 FLEXLOGIC OPERANDS (Sheet 8 of 8) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION USER- PUSHBUTTON 1 ON Pushbutton number 1 is in the “On” position PROGRAMMABLE PUSHBUTTON 1 OFF Pushbutton number 1 is in the “Off” position...
  • Page 250: Flexlogic Rules

    When making changes to FlexLogic entries in the settings, all FlexLogic equations are re-compiled whenever any new FlexLogic entry value is entered, and as a result of the re-compile all latches are reset automatically. 5-120 G30 Generator Protection System GE Multilin...
  • Page 251: Flexlogic Example

    DIGITAL ELEMENT 1 on Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–42: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS GE Multilin G30 Generator Protection System 5-121...
  • Page 252 Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." 5-122 G30 Generator Protection System GE Multilin...
  • Page 253 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". GE Multilin G30 Generator Protection System 5-123...
  • Page 254 In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) 5-124 G30 Generator Protection System GE Multilin...
  • Page 255: Flexlogic Equation Editor

    TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". GE Multilin G30 Generator Protection System 5-125...
  • Page 256: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. 5-126 G30 Generator Protection System GE Multilin...
  • Page 257 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS GE Multilin G30 Generator Protection System 5-127...
  • Page 258 Figure 5–49: FLEXELEMENT DIRECTION, PICKUP, AND HYSTERESIS In conjunction with the setting the element could be programmed to provide two extra charac- FLEXELEMENT 1 INPUT MODE teristics as shown in the figure below. 5-128 G30 Generator Protection System GE Multilin...
  • Page 259 = 1 Hz BASE FREQUENCY RATE OF CHANGE df/dt = 1 Hz/s BASE ϕ PHASE ANGLE = 360 degrees (see the UR angle referencing convention) BASE POWER FACTOR = 1.00 BASE RTDs BASE = 100°C GE Multilin G30 Generator Protection System 5-129...
  • Page 260: Non-Volatile Latches

    LATCH 1 TYPE: This setting characterizes Latch 1 to be Set- or Reset-dominant. • LATCH 1 SET: If asserted, the specified FlexLogic operands 'sets' Latch 1. • LATCH 1 RESET: If asserted, the specified FlexLogic operand 'resets' Latch 1. 5-130 G30 Generator Protection System GE Multilin...
  • Page 261 LATCH N LATCH N LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–51: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC GE Multilin G30 Generator Protection System 5-131...
  • Page 262: Grouped Elements

      LOSS OF MESSAGE See page 5–184.  EXCITATION  ACCIDENTAL MESSAGE See page 5-186.  ENERGIZATION  POWER MESSAGE See page 5-188.   STATOR MESSAGE See page 5-191.  GROUND 5-132 G30 Generator Protection System GE Multilin...
  • Page 263 > K, where PKP represents a percent differential pickup setting and K is a restraint factor defined by the relays settings Slope 1, Slope 2, and a transition area between breakpoint 1 and breakpoint 2 settings. GE Multilin G30 Generator Protection System 5-133...
  • Page 264 Figure 5–52: PERCENT DIFFERENTIAL CALCULATIONS The G30 percent differential element is based on a configurable dual-breakpoint / dual-slope differential restraint character- istic. The purpose of the preset characteristic is to define the differential restraint ratio for the transformer winding currents at different loading conditions and distinguish between external and internal faults.
  • Page 265 2nd harmonic ratios during inrush conditions. This may result undesired tripping of the pro- tected transformer. Reducing the 2nd harmonic inhibit threshold may jeopardize dependability and speed of protection. GE Multilin G30 Generator Protection System 5-135...
  • Page 266 The relay produces three FlexLogic operands that may be used for testing or for special applications such as building cus- tom logic (1-out-of-3) or supervising some protection functions (ground time overcurrent, for example) from the 2nd har- monic inhibit. 5-136 G30 Generator Protection System GE Multilin...
  • Page 267 Iad5 LEVEL ACTUAL VALUES XFMR PCNT DIFF 5TH B > Ibd5 LEVEL DIFF 5TH HARM XFMR PCNT DIFF 5TH C > Icd5 LEVEL Iad5 Ibd5 Icd5 828001A6.CDR Figure 5–54: PERCENT DIFFERENTIAL SCHEME LOGIC GE Multilin G30 Generator Protection System 5-137...
  • Page 268  DIRECTIONAL 1 b) INVERSE TIME OVERCURRENT CURVE CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 269 5.041 4.827 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 GE Multilin G30 Generator Protection System 5-139...
  • Page 270 0.60 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 5-140 G30 Generator Protection System GE Multilin...
  • Page 271 = characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–19: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
  • Page 272 = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The G30 uses the FlexCurve feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve section in this chapter for additional details. 5-142...
  • Page 273 (see the figure below); the pickup level is calculated as ‘Mvr’ times the setting. If the voltage restraint PHASE TOC1 PICKUP feature is disabled, the pickup level always remains at the setting value. GE Multilin G30 Generator Protection System 5-143...
  • Page 274 PHASE TOC1 C DPO Multiplier-Phase C PHASE TOC1 C OP SETTING PHASE TOC1 PKP PHASE TOC1 VOLT RESTRAINT: PHASE TOC1 OP Enabled PHASE TOC1 DPO 827072A4.CDR Figure 5–56: PHASE TIME OVERCURRENT 1 SCHEME LOGIC 5-144 G30 Generator Protection System GE Multilin...
  • Page 275 The input current is the fundamental phasor magnitude. For timing curves, see the publication Instan- taneous Overcurrent Element Response to Saturated Waveforms in UR-Series Relays (GET-8400A). Figure 5–57: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC GE Multilin G30 Generator Protection System 5-145...
  • Page 276 CTs and the line-line voltage from the VTs, based on the 90° or quadrature connection. If there is a requirement to supervise overcurrent elements for flows in opposite directions, such as can happen through a bus-tie breaker, two phase directional elements should be programmed with opposite element characteristic angle (ECA) settings. 5-146 G30 Generator Protection System GE Multilin...
  • Page 277 10 ms must be added to all the instantaneous protection elements under the supervi- sion of the phase directional element. If current reversal is of a concern, a longer delay – in the order of 20 ms – may be needed. GE Multilin G30 Generator Protection System 5-147...
  • Page 278: Neutral Current

     NEUTRAL TOC1 See page 5–149.    NEUTRAL IOC1 MESSAGE See page 5–150.   NEUTRAL MESSAGE See page 5–151.  DIRECTIONAL OC1  NEUTRAL MESSAGE See page 5–151.  DIRECTIONAL OC2 5-148 G30 Generator Protection System GE Multilin...
  • Page 279 SETTING NEUTRAL TOC1 PKP RESET: NEUTRAL TOC1 IN ≥ PICKUP NEUTRAL TOC1 DPO SOURCE: NEUTRAL TOC1 OP SETTING NEUTRAL TOC1 BLOCK: Off = 0 827034A3.VSD Figure 5–60: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC GE Multilin G30 Generator Protection System 5-149...
  • Page 280 NEUTRAL IOC1 PKP RESET DELAY : SETTING NEUTRAL IOC1 DPO NEUTRAL IOC1 OP 3( _0 - K _1 ) PICKUP NEUTRAL IOC1 BLOCK: Off=0 SETTING NEUTRAL IOC1 SOURCE: 827035A4.CDR Figure 5–61: NEUTRAL IOC1 SCHEME LOGIC 5-150 G30 Generator Protection System GE Multilin...
  • Page 281 × × (EQ 5.36) – The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from: • System unbalances under heavy load conditions. GE Multilin G30 Generator Protection System 5-151...
  • Page 282 REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation) The above bias should be taken into account when using the neutral directional overcurrent element to directionalize other protection elements. 5-152 G30 Generator Protection System GE Multilin...
  • Page 283 If “Dual” polarizing is selected, the element performs both directional comparisons as described above. A given direction is confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous forward and reverse) indication occurs, the forward direction overrides the reverse direction. GE Multilin G30 Generator Protection System 5-153...
  • Page 284 “Calculated 3I0” mode of operation. Proper application of this element requires that the operating current and the polarizing voltage (or current) be mea- sured from the same side of the transformer. NOTE 5-154 G30 Generator Protection System GE Multilin...
  • Page 285: Ground Current

     RESTRICTED GROUND MESSAGE  FAULT 4 The G30 relay contains one Ground Time Overcurrent, one Ground Instantaneous Overcurrent, and four Restricted Ground Fault elements. Refer to Inverse Time Overcurrent Curve Characteristics on page 5–138 for additional information. GE Multilin...
  • Page 286 GROUND TOC 1 SETTING RESET: GROUND TOC1 PKP GROUND TOC1 IG ≥ PICKUP GROUND TOC1 DPO SOURCE: GROUND TOC1 OP SETTING GROUND TOC1 BLOCK: 827036A3.VSD Off = 0 Figure 5–64: GROUND TOC1 SCHEME LOGIC 5-156 G30 Generator Protection System GE Multilin...
  • Page 287 Enabled = 1 SETTING DELAY: GROUND IOC1 GROUND IOC1 RESET SETTING PICKUP: DELAY: GROUND IOC1 SOURCE: IG ≥ PICKUP SETTING GROUND IOC1 BLOCK: 827037A4.VSD Off = 0 Figure 5–65: GROUND IOC1 SCHEME LOGIC GE Multilin G30 Generator Protection System 5-157...
  • Page 288 CT installed in the grounding path, or the ground current obtained by external summation of the neutral-side stator CTs. The Typical Applications of RGF Protec- tion diagram explains the basic application and wiring rules. 5-158 G30 Generator Protection System GE Multilin...
  • Page 289 The zero-sequence component of the restraining signal (IR0) is meant to provide maximum restraint during external ground faults, and therefore is calculated as a vectorial difference of the ground and neutral currents: IG IN (EQ 5.39) – – GE Multilin G30 Generator Protection System 5-159...
  • Page 290 RST RESTD GND FT1 SLOPE: RESTD GND FT1 SOURCE: Differential > SLOPE * Restraining Currents ACTUAL VALUES RGF 1 gd Mag RGF 1 gr Mag 828002A2.CDR Figure 5–68: RESTRICTED GROUND FAULT SCHEME LOGIC 5-160 G30 Generator Protection System GE Multilin...
  • Page 291 Igd = abs(3 × 3.3 + 0.0) = 10 pu, IR0 = abs(3 × 3.3 – (0.0)) = 10 pu, IR2 = 3 × 3.3 = 10 pu, IR1 = 3 × (3.33 – 3.33) = 0 pu, and Igr = 10 pu The differential current is 100% of the restraining current. GE Multilin G30 Generator Protection System 5-161...
  • Page 292: Negative Sequence Current

    The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence and zero-sequence currents resulting from: • System unbalances under heavy load conditions. • Transformation errors of current transformers (CTs). • Fault inception and switch-off transients. 5-162 G30 Generator Protection System GE Multilin...
  • Page 293 CT errors, since the current is low. The operating quantity depends on the way the test currents are injected into the G30. For single phase injection: = ⅓ × (1 – K) × I •...
  • Page 294 The element characteristic angle in the reverse direction is the angle set for the forward direction shifted by 180°. • NEG SEQ DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit angle for the forward direction. 5-164 G30 Generator Protection System GE Multilin...
  • Page 295 When NEG SEQ DIR OC1 TYPE selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique. Figure 5–70: NEGATIVE SEQUENCE DIRECTIONAL OC1 SCHEME LOGIC GE Multilin G30 Generator Protection System 5-165...
  • Page 296: Generator Unbalance

    This is set to prevent false trips for faults that would be cleared normally by system protections. • GEN UNBAL STG1 TMAX: This is the maximum operate time of the stage 1 element. This setting can be applied to limit the maximum tripping time for low level unbalances. 5-166 G30 Generator Protection System GE Multilin...
  • Page 297 GEN UNBAL STG2 PKP DELAY: This is the minimum operate time of the stage 2 element. This is set to prevent nui- sance alarms during system faults. 1000 K=15 K=40 K=100 Tmax Tmin 0.01 830714A1.CDR Figure 5–71: GENERATOR UNBALANCE INVERSE TIME CURVES Figure 5–72: GENERATOR UNBALANCE SCHEME LOGIC GE Multilin G30 Generator Protection System 5-167...
  • Page 298 The currents in the two windings are compared, any difference indicat- ing an inter-turn fault. 5-168 G30 Generator Protection System GE Multilin...
  • Page 299 In “Over” mode, the element will pickup if: > pickup ≥ min_load (EQ 5.45) – split bias load In “Over-under”, mode, the element will pickup if: GE Multilin G30 Generator Protection System 5-169...
  • Page 300: Split Phase Protection

    • SPLIT PHASE A(C) PICKUP: This setting specifies a pickup level for each phase. This should be set less than the minimum expected unbalance (split phase) current due to an inter-turn fault. 5-170 G30 Generator Protection System GE Multilin...
  • Page 301 CTs (first fig- ure above). In this instance, a time delay can be used to ride through the saturation event. Alternately, the CT saturation flag can also be used to supervise the function. GE Multilin G30 Generator Protection System 5-171...
  • Page 302: Voltage Elements

     VOLTAGE ELEMENTS  PHASE See page 5–175.   UNDERVOLTAGE1  PHASE MESSAGE See page 5–175.  UNDERVOLTAGE2  PHASE MESSAGE See page 5–176.  OVERVOLTAGE1  NEUTRAL OV1 MESSAGE See page 5–177.  5-172 G30 Generator Protection System GE Multilin...
  • Page 303  ------------------ –   pickup where: T = operating time D = undervoltage delay setting (D = 0.00 operates instantaneously) V = secondary voltage applied to the relay = pickup level pickup GE Multilin G30 Generator Protection System 5-173...
  • Page 304 5.6 GROUPED ELEMENTS 5 SETTINGS % of voltage pickup 842788A1.CDR Figure 5–77: INVERSE TIME UNDERVOLTAGE CURVES At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting. NOTE 5-174 G30 Generator Protection System GE Multilin...
  • Page 305 Source VT = Wye FLEXLOGIC OPERAND SETTING PHASE UV1 PKP PHASE UV1 MODE: FLEXLOGIC OPERAND Phase to Ground Phase to Phase PHASE UV1 OP FLEXLOGIC OPERAND PHASE UV1 DPO 827039AB.CDR Figure 5–78: PHASE UNDERVOLTAGE1 SCHEME LOGIC GE Multilin G30 Generator Protection System 5-175...
  • Page 306 FLEXLOGIC OPERAND PHASE OV1 PKP 827066A7.CDR Figure 5–79: PHASE OVERVOLTAGE SCHEME LOGIC > × If the source VT is wye-connected, then the phase overvoltage pickup condition is Pickup for V and V NOTE 5-176 G30 Generator Protection System GE Multilin...
  • Page 307 “Definite time”. The source assigned to this element must be configured for a phase VT. NEUTRAL OV1 CURVE VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to be wye-connected. Figure 5–80: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC GE Multilin G30 Generator Protection System 5-177...
  • Page 308 The negative-sequence overvoltage element may be used to detect loss of one or two phases of the source, a reversed phase sequence of voltage, or a non-symmetrical system voltage condition. Figure 5–81: NEGATIVE-SEQUENCE OVERVOLTAGE SCHEME LOGIC 5-178 G30 Generator Protection System GE Multilin...
  • Page 309 AUX UV1 EVENTS: MESSAGE Disabled The G30 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt- age conditions of the auxiliary voltage. The selects the voltage level at which the time undervoltage ele- AUX UV1 PICKUP ment starts timing.
  • Page 310 AUX OV1 EVENTS: MESSAGE Disabled The G30 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM ...
  • Page 311 “Phase-ground”, then the operating quantity for this element will be the phase-to-ground nominal volt- age. It is beneficial to use the phase-to-phase voltage mode for this element when the G30 device is applied on an iso- lated or resistance-grounded system.
  • Page 312 F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) The volts/hertz inverse A curves are shown below. Time delay setting Multiples of volts per hertz pickup 830738A1.CDR Figure 5–85: VOLTS-PER-HERTZ CURVES, INVERSE CURVE A 5-182 G30 Generator Protection System GE Multilin...
  • Page 313 T = Operating Time TDM = Time Delay Multiplier (delay in sec.) V = fundamental RMS value of voltage (pu) F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) GE Multilin G30 Generator Protection System 5-183...
  • Page 314: Loss Of Excitation

    LOSS OF EXCITATION MESSAGE PKP DELAY2: 0.500 s Range: 0.000 to 1.250 pu in steps of 0.001 LOSS OF EXCITATION MESSAGE UV SUPV: 0.700 pu Range: FlexLogic operand LOSS OF EXCIT BLK: MESSAGE 5-184 G30 Generator Protection System GE Multilin...
  • Page 315 HV side. Correspondingly, if the VTs are located on the LV side of the transformer, then the source should be configured using CTs that are also on the LV side. In both cases, the CT polarity should produce a posi- NOTE tive power measurement when the machine is generating. GE Multilin G30 Generator Protection System 5-185...
  • Page 316: Accidental Energization

    ACCDNT ENRG ARMING MODE The machine off-line status is indicated by a dedicated FlexLogic operand. Once armed, the accidental energization feature operates upon detecting an overcurrent condition in any of the stator phases. 5-186 G30 Generator Protection System GE Multilin...
  • Page 317 VT connection. • ACCDNT ENRG OFFLINE: This setting specifies the FlexLogic operand indicating that the protected generator is off- line. Figure 5–90: ACCIDENTAL ENERGIZATION SCHEME LOGIC GE Multilin G30 Generator Protection System 5-187...
  • Page 318: Sensitive Directional Power

    The operating quantity is displayed in the   actual ACTUAL VALUES METERING SENSITIVE DIRECTIONAL POWER 1(2) value. The element has two independent (as to the pickup and delay settings) stages for alarm and trip, respectively. 5-188 G30 Generator Protection System GE Multilin...
  • Page 319 RCA = 0 SMIN < 0 SMIN > 0 OPERATE RESTRAIN RESTRAIN OPERATE RCA = 90 RCA = 270 SMIN > 0 SMIN < 0 842702A1.CDR Figure 5–92: DIRECTIONAL POWER ELEMENT SAMPLE APPLICATIONS GE Multilin G30 Generator Protection System 5-189...
  • Page 320 CTs that are also on the LV side. In both cases, the CT polarity NOTE should produce a positive power measurement when the machine is generating. 5-190 G30 Generator Protection System GE Multilin...
  • Page 321: Stator Ground

    Voltage measured at the neutral of the machine shall be configured as the auxiliary VT bank. The element extracts the third harmonic of the auxiliary voltage from the source in order to operate. GE Multilin G30 Generator Protection System 5-191...
  • Page 322 CTs that are also on the LV side. In both cases, the CT polarity NOTE should produce a positive power measurement when the machine is generating. 5-192 G30 Generator Protection System GE Multilin...
  • Page 323 SOURCE: Vaux (3rd harmonic) Min < 3 Phase Power < Max 3 Phase Real Power SETTINGS 3RD HARM NTRL UV VOLT SUPV: 830005A4.CDR > Pickup Figure 5–94: THIRD HARMONIC NEUTRAL UNDERVOLTAGE SCHEME LOGIC GE Multilin G30 Generator Protection System 5-193...
  • Page 324: Control Elements

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. 5-194 G30 Generator Protection System GE Multilin...
  • Page 325 TRIP BUS 1 RESET: The trip bus output is reset when the operand assigned to this setting is asserted. Note that the operand is pre-wired to the reset gate of the latch, As such, a reset command the front panel interface or via RESET OP communications will reset the trip bus output. GE Multilin G30 Generator Protection System 5-195...
  • Page 326: Setting Groups

    The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPED settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energized ELEMENTS LED) is in service. 5-196 G30 Generator Protection System GE Multilin...
  • Page 327 CONT IP 1 ON (H5A) OR (2) AND (3) = VIRT OP 1 (VO1) PHASE TOC1 PKP PHASE TOC2 PKP AND (3) = VIRT OP 1 (VO1) 842789A1.CDR Figure 5–97: EXAMPLE FLEXLOGIC CONTROL OF A SETTINGS GROUP GE Multilin G30 Generator Protection System 5-197...
  • Page 328: Selector Switch

    1 to the . If the control word is outside the range, an alarm is established SELECTOR FULL RANGE by setting the FlexLogic operand for 3 seconds. SELECTOR ALARM 5-198 G30 Generator Protection System GE Multilin...
  • Page 329 SELECTOR 1 3BIT ACK: This setting specifies an acknowledging input for the three-bit control input. The pre- selected position is applied on the rising edge of the assigned FlexLogic operand. This setting is active only under the GE Multilin G30 Generator Protection System 5-199...
  • Page 330 The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. 5-200 G30 Generator Protection System GE Multilin...
  • Page 331 3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–98: TIME-OUT MODE GE Multilin G30 Generator Protection System 5-201...
  • Page 332 Make the following changes to selector switch element in the    SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 5-202 G30 Generator Protection System GE Multilin...
  • Page 333 3-bit acknowledge SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–100: SELECTOR SWITCH LOGIC GE Multilin G30 Generator Protection System 5-203...
  • Page 334: Underfrequency

    SETTING ≤ 0 < f PICKUP UNDERFREQ 1 OP UNDERFREQ 1 ACTUAL VALUES MIN VOLT / AMP: UNDERFREQ 1 SOURCE: ≥ Level Minimum VOLT / AMP Frequency 827079A8.CDR Figure 5–101: UNDERFREQUENCY SCHEME LOGIC 5-204 G30 Generator Protection System GE Multilin...
  • Page 335: Overfrequency

    OVERFREQ 1 BLOCK: OVERFREQ 1 RESET OVERFREQ 1 PKP DELAY : Off = 0 OVERFREQ 1 DPO OVERFREQ 1 OP SETTING ≥ PICKUP OVERFREQ 1 SOURCE: Frequency 827832A5.CDR Figure 5–102: OVERFREQUENCY SCHEME LOGIC GE Multilin G30 Generator Protection System 5-205...
  • Page 336: Frequency Rate Of Change

    FREQ RATE 1 OC SUPV PICKUP: This setting defines minimum current level required for operation of the element. The supervising function responds to the positive-sequence current. Typical application includes load shedding. Set the pickup threshold to zero if no overcurrent supervision is required. 5-206 G30 Generator Protection System GE Multilin...
  • Page 337 SETTINGS FREQ RATE 1 PKP FREQ RATE 1 MIN FREQUENCY: FREQ RATE 1 MAX FREQUENCY: F > MIN & F < MAX Calculate df/dt 832023A2.CDR Figure 5–103: FREQUENCY RATE OF CHANGE SCHEME LOGIC GE Multilin G30 Generator Protection System 5-207...
  • Page 338: Frequency Out-Of-Band Accumulation

    • FREQ ACCUM BLOCK: This setting selects a FlexLogic operand to block out-of-band frequency accumulation in all bands. This is typically required to avoid unnecessary accumulation when relay testing is being performed. 5-208 G30 Generator Protection System GE Multilin...
  • Page 339 FREQ OOB BAND 3 PKP FREQ OOB ACCUM PKP FREQ OOB BAND 4 PKP FREQ OOB BAND 5 PKP FREQ OOB BAND 6 PKP FREQ OOB BAND 7 PKP 830008A1.CDR Figure 5–104: FREQUENCY OUT-OF-BAND ACCUMULATION LOGIC GE Multilin G30 Generator Protection System 5-209...
  • Page 340: Synchrocheck

    ΔF. This time can be calculated by: ------------------------------- - (EQ 5.54) 360° ----------------- - × ΔF 2 ΔΦ × where: ΔΦ = phase angle difference in degrees; ΔF = frequency difference in Hz. 5-210 G30 Generator Protection System GE Multilin...
  • Page 341 (SOURCE Z) COMBINATION SOURCE Y SOURCE Z Phase VTs and Phase VTs and Phase Phase Auxiliary VT Auxiliary VT Phase VTs and Phase VT Phase Phase Auxiliary VT Phase VT Phase VT Phase Phase GE Multilin G30 Generator Protection System 5-211...
  • Page 342 The relay will use the phase channel of a three-phase set of voltages if pro- grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as part of the Source and a three-phase set is not. 5-212 G30 Generator Protection System GE Multilin...
  • Page 343 5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–105: SYNCHROCHECK SCHEME LOGIC GE Multilin G30 Generator Protection System 5-213...
  • Page 344: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”. • DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to “Disabled”, the operation of the pickup LED is blocked. 5-214 G30 Generator Protection System GE Multilin...
  • Page 345 Using the contact input settings, this input will be given an ID name, for example, “Cont Ip 1", and will be set “On” when the breaker is closed. The settings to use digital element 1 to monitor the breaker trip circuit are indicated below (EnerVista UR GE Multilin G30 Generator Protection System 5-215...
  • Page 346 “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). Figure 5–108: TRIP CIRCUIT EXAMPLE 2 The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and solid-state contact with voltage monitoring. NOTE 5-216 G30 Generator Protection System GE Multilin...
  • Page 347: Digital Counters

    –2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic operand for blocking the counting operation. All counter operands are blocked. GE Multilin G30 Generator Protection System 5-217...
  • Page 348 COUNTER 1 RESET: COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–109: DIGITAL COUNTER SCHEME LOGIC 5-218 G30 Generator Protection System GE Multilin...
  • Page 349 The CT failure logic (see below) is based on the presence of the zero-sequence current in the supervised CT source and the absence of one of three or all of the three following conditions. GE Multilin G30 Generator Protection System 5-219...
  • Page 350: Monitoring Elements

    Figure 5–110: CT FAILURE DETECTOR SCHEME LOGIC c) VT FUSE FAILURE    PATH: SETTINGS CONTROL ELEMENTS MONITORING ELEMENTS VT FUSE FAILURE 1(4) Range: Disabled, Enabled  VT FUSE FAILURE 1 VT FUSE FAILURE 1  FUNCTION: Disabled 5-220 G30 Generator Protection System GE Multilin...
  • Page 351 An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized; positive- sequence voltage and current are both below threshold levels. The function setting enables and disables the fuse failure feature for each source. GE Multilin G30 Generator Protection System 5-221...
  • Page 352 20 c cles Enabled = 1 SOURCE FLEX-A ALOG 3V_0(3rd Harmonic) SRC1 3V0 3rd Harmonic Note 3V_0 is the sample summation 827093AN.CDR of Va, Vb, and Vc. Figure 5–111: VT FUSE FAIL SCHEME LOGIC 5-222 G30 Generator Protection System GE Multilin...
  • Page 353 I = measured overload RMS current. • = measured load RMS current before overload occurs. • k= IEC 255-8 k-factor applied to I , defining maximum permissible current above nominal current. • = protected element base (nominal) current. GE Multilin G30 Generator Protection System 5-223...
  • Page 354 The thermal overload protection element estimates accumulated thermal energy E using the following equations calculated each power cycle. When current is greater than the pickup level, I > k × I , element starts increasing the thermal energy: t Δ -------------- - (EQ 5.58) – op In 5-224 G30 Generator Protection System GE Multilin...
  • Page 355 30 minutes Busbar 60 minutes 20 minutes Underground cable 20 to 60 minutes 60 minutes The logic for the thermal overload protection element is shown below. Figure 5–113: THERMAL OVERLOAD PROTECTION SCHEME LOGIC GE Multilin G30 Generator Protection System 5-225...
  • Page 356: Inputs And Outputs

    The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the G30 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
  • Page 357 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. GE Multilin G30 Generator Protection System 5-227...
  • Page 358: Virtual Inputs

    SETTING “Virtual Input 1 to OFF = 0” VIRTUAL INPUT 1 ID: (Flexlogic Operand) SETTING Virt Ip 1 VIRTUAL INPUT 1 TYPE: Latched Self - Reset 827080A2.CDR Figure 5–115: VIRTUAL INPUTS SCHEME LOGIC 5-228 G30 Generator Protection System GE Multilin...
  • Page 359: Contact Outputs

    The most dependable protection of the initiating contact is provided by directly measuring current in the tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in. This can be realized in the G30 using the FlexLogic operand to seal-in the contact output as follows: CONT OP 1 ION “Cont Op 1"...
  • Page 360 5 SETTINGS The G30 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop- ulates the setting menu accordingly.
  • Page 361: Virtual Outputs

    Logic equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings would be programmed as follows: GE Multilin G30 Generator Protection System 5-231...
  • Page 362: Remote Devices

    32 “DNA” bit pairs that represent the state of two pre-defined events and 30 user-defined events. All remaining bit pairs are “UserSt” bit pairs, which are status bits representing user-definable events. The G30 implementation provides 32 of the 96 available UserSt bit pairs.
  • Page 363: Remote Inputs

    The remote input/output facility provides for 32 remote inputs and 64 remote outputs. b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES In a G30 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the ...
  • Page 364: Remote Double-Point Status Inputs

    LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic oper- and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted. 5-234 G30 Generator Protection System GE Multilin...
  • Page 365: Resetting

    DIRECT INPUT MESSAGE DEVICE ID: 1 Range: 1 to 32 DIRECT INPUT MESSAGE BIT NUMBER: Range: On, Off, Latest/On, Latest/Off DIRECT INPUT MESSAGE DEFAULT STATE: Off Range: Enabled, Disabled DIRECT INPUT MESSAGE EVENTS: Disabled GE Multilin G30 Generator Protection System 5-235...
  • Page 366 The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. EXAMPLE 1: EXTENDING INPUT/OUTPUT CAPABILITIES OF A G30 RELAY Consider an application that requires additional quantities of contact inputs or output contacts or lines of programmable logic that exceed the capabilities of a single UR-series chassis.
  • Page 367 . Upon losing communications or a device, the scheme is inclined to block (if any default state is set to “On”), or to trip the bus on any overcurrent condition (all default states set to “Off”). GE Multilin G30 Generator Protection System 5-237...
  • Page 368 DIRECT OUT 2 OPERAND: " " (forward a message from 1 to 3) DIRECT INPUT 5 DIRECT OUT 3 OPERAND: " " (forward a message from 3 to 1) DIRECT INPUT 6 DIRECT OUT 4 OPERAND: 5-238 G30 Generator Protection System GE Multilin...
  • Page 369: Teleprotection Inputs And Outputs

    Setting the setting to “On” defaults the input to logic 1 when the channel fails. A value of “Off” TELEPROT INPUT ~~ DEFAULT defaults the input to logic 0 when the channel fails. GE Multilin G30 Generator Protection System 5-239...
  • Page 370 (On 3-terminal system or 2-terminal (same for 1-2...1-16) SETTING with redundant channel) FLEXLOGIC OPERAND TELEPROT OUTPUT 2-1: (same for 2-2...2-16) Fail TELEPRO INPUT 2-1 On Off (Flexlogic Operand) (same for 1-2...1-16) 842750A2.CDR Figure 5–121: TELEPROTECTION INPUT/OUTPUT PROCESSING 5-240 G30 Generator Protection System GE Multilin...
  • Page 371: Iec 61850 Goose Analogs

    GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log values in other G30 features, such as FlexElements. The base factor is applied to the GOOSE analog input Flex- Analog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
  • Page 372: Iec 61850 Goose Integers

    (Xfmr Iar, Ibr, and Icr Mag) (CT primary for source currents, and transformer reference primary current for transformer differential currents) The GOOSE analog input FlexAnalog values are available for use in other G30 functions that use FlexAnalog values. 5.8.13 IEC 61850 GOOSE INTEGERS ...
  • Page 373: Transducer Inputs And Outputs

    –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT F1 MIN VALUE DCMA INPUT F1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE GE Multilin G30 Generator Protection System 5-243...
  • Page 374: Rtd Inputs

    1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. 5-244 G30 Generator Protection System GE Multilin...
  • Page 375 15.61 168.47 280.77 233.97 16.00 172.46 291.96 243.30 16.39 175.84 303.46 252.88 16.78 179.51 315.31 262.76 17.17 183.17 327.54 272.94 17.56 186.82 340.14 283.45 17.95 190.45 353.14 294.28 18.34 194.08 366.53 305.44 18.73 GE Multilin G30 Generator Protection System 5-245...
  • Page 376: Dcma Outputs

    – The feature is intentionally inhibited if the settings are entered incorrectly, e.g. when – MAX VAL MIN VAL MAX VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure. 5-246 G30 Generator Protection System GE Multilin...
  • Page 377 The minimum and maximum power values to be monitored (in pu) are: 20.65 MW 20.65 MW – ------------------------------ -------------------------- - minimum power 1.247 pu, maximum power 1.247 pu (EQ 5.65) – 16.56 MW 16.56 MW The following settings should be entered: GE Multilin G30 Generator Protection System 5-247...
  • Page 378 The minimum and maximum voltage values to be monitored (in pu) are: 161.66 kV 254.03 kV -------------------------- - -------------------------- - minimum voltage 0.404 pu, maximum voltage 0.635 pu (EQ 5.71) 400 kV 400 kV The following settings should be entered: 5-248 G30 Generator Protection System GE Multilin...
  • Page 379 254.03 kV 1.27 kV – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. GE Multilin G30 Generator Protection System 5-249...
  • Page 380 TEST MODE FORCING: MESSAGE The G30 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.
  • Page 381 Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a G30 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.
  • Page 382: Testing 5.10.1 Test Mode

    PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu:   SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: 5-252 G30 Generator Protection System GE Multilin...
  • Page 383: Overview

    See page 6-10.  STATUS  TELEPROT CH TESTS See page 6-11.   COMM STATUS See page 6-11.  REMAINING CONNECT  ACTUAL VALUES  SOURCE SRC 1 See page 6-15.  METERING  GE Multilin G30 Generator Protection System...
  • Page 384  FAULT REPORTS  EVENT RECORDS See page 6-24.   OSCILLOGRAPHY See page 6-24.   DATA LOGGER See page 6-25.   ACTUAL VALUES  MODEL INFORMATION See page 6-26.  PRODUCT INFO  G30 Generator Protection System GE Multilin...
  • Page 385 6 ACTUAL VALUES 6.1 OVERVIEW  FIRMWARE REVISIONS See page 6-26.  GE Multilin G30 Generator Protection System...
  • Page 386 The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. G30 Generator Protection System GE Multilin...
  • Page 387: Teleprotection Inputs

    The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of the display indicates the logic state of the contact output. GE Multilin G30 Generator Protection System...
  • Page 388: Virtual Outputs

    GSSE/GOOSE message, without a state change, is sent. When the GSSE/GOOSE message trasmits a state change, the resets to 0. This number rolls over to zero when a count of 4,294,967,295 is incre- SQNUM mented. G30 Generator Protection System GE Multilin...
  • Page 389: Digital Counters

    PATH: ACTUAL VALUES STATUS ETHERNET Range: Fail, OK  ETHERNET ETHERNET PRI LINK  STATUS: Fail Range: Fail, OK ETHERNET SEC LINK MESSAGE STATUS: Fail Range: Fail, OK ETHERNET TRD LINK MESSAGE STATUS: Fail GE Multilin G30 Generator Protection System...
  • Page 390: Real Time Clock Synchronizing

    PTP-— IRIG-B DELTA being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-B time. G30 Generator Protection System GE Multilin...
  • Page 391: Direct Inputs

     STATUS STATUS: Offline Range: Offline, Online DIRECT DEVICE 2 MESSAGE STATUS: Offline ↓ Range: Offline, Online DIRECT DEVICE 16 MESSAGE STATUS: Offline These actual values represent the state of direct devices 1 through 16. GE Multilin G30 Generator Protection System...
  • Page 392: Iec 61850 Goose Integers

    UINT INPUT 16 MESSAGE The G30 Generator Protection System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap- ter 2 for additional details.
  • Page 393: Teleprotection Channel Tests

    UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP status shows 4. Note that the maximum number of PMU TCP connections matches the number of aggregators. GE Multilin G30 Generator Protection System 6-11...
  • Page 394: Metering Conventions

    PF = Lag WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS 6-12 G30 Generator Protection System GE Multilin...
  • Page 395 ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. GE Multilin G30 Generator Protection System 6-13...
  • Page 396 The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a relative matter. It is important to remember that the G30 displays are always referenced as specified under SETTINGS ...
  • Page 397: Sources

    SRC 1 RMS Ic: MESSAGE 0.000 SRC 1 RMS In: MESSAGE 0.000 SRC 1 PHASOR Ia: MESSAGE 0.000 0.0° SRC 1 PHASOR Ib: MESSAGE 0.000 0.0° SRC 1 PHASOR Ic: MESSAGE 0.000 0.0° GE Multilin G30 Generator Protection System 6-15...
  • Page 398 0.0° SRC 1 PHASOR Vcg: MESSAGE 0.000 0.0° SRC 1 RMS Vab: MESSAGE 0.00 SRC 1 RMS Vbc: MESSAGE 0.00 SRC 1 RMS Vca: MESSAGE 0.00 SRC 1 PHASOR Vab: MESSAGE 0.000 0.0° 6-16 G30 Generator Protection System GE Multilin...
  • Page 399 REACTIVE PWR MESSAGE φa: 0.000 SRC 1 REACTIVE PWR MESSAGE φb: 0.000 SRC 1 REACTIVE PWR MESSAGE φc: 0.000 SRC 1 APPARENT PWR MESSAGE 3φ: 0.000 SRC 1 APPARENT PWR MESSAGE φa: 0.000 GE Multilin G30 Generator Protection System 6-17...
  • Page 400 S = V x Î x Î x Î (EQ 6.1) When VTs are configured in delta, the G30 does not calculate power in each phase and three-phase power is measured as S = V x Î x Î (EQ 6.2)
  • Page 401 = 1, 2,..., N – 1 is the index over one cycle for the Fast Fourier Transform (FFT) m is the last sample number for the sliding window h = 1, 2,..., 25 is the harmonic number The short-time Fourier transform is applied to the unfiltered signal: GE Multilin G30 Generator Protection System 6-19...
  • Page 402: Synchrocheck

    CHANGE 2: 0.00 Hz/s FREQUENCY RATE OF MESSAGE CHANGE 3: 0.00 Hz/s FREQUENCY RATE OF MESSAGE CHANGE 4: 0.00 Hz/s The metered frequency rate of change for the frequency rate of change elements is shown here. 6-20 G30 Generator Protection System GE Multilin...
  • Page 403: Frequency Out-Of-Band Accumulation

    XFMR RESTRAINING CURRENT = maximum primary RMS value of the +IN and -IN inputs BASE (Xfmr Iar, Ibr, and Icr Mag) (CT primary for source currents, and transformer reference primary current for transformer differential currents) GE Multilin G30 Generator Protection System 6-21...
  • Page 404: Iec 61580 Goose Analog Values

    MESSAGE 0.000 The G30 Generator Protection System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap- ter 2 for additional details.
  • Page 405: Volts Per Hertz

    RTD INPUT xx  -50 °C Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value. GE Multilin G30 Generator Protection System 6-23...
  • Page 406: Records

    This menu allows the user to view the number of triggers involved and number of oscillography traces available. The value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog- CYCLES PER RECORD raphy section of chapter 5 for additional details. 6-24 G30 Generator Protection System GE Multilin...
  • Page 407: Data Logger

    It counts up at the defined sampling rate. If the data logger channels are defined, then both values are static. Refer to the  menu for clearing data logger records. COMMANDS CLEAR RECORDS GE Multilin G30 Generator Protection System 6-25...
  • Page 408: Product Information

    6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION   PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE Multilin order code format;  MODEL INFORMATION ORDER CODE LINE 1: example order code shown  G30-E00-HCH-F8G-H6B Range: standard GE Multilin order code format...
  • Page 409: Commands And

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin G30 Generator Protection System...
  • Page 410 The complete date, as a minimum, must be entered to allow execution of this command. The new time (if entered) and date will take effect at the moment the ENTER key is clicked. The timescale of the entered time should be local time, including daylight time where and when applicable. G30 Generator Protection System GE Multilin...
  • Page 411: Relay Maintenance

    Various self-checking diagnostics are performed in the background while the G30 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the G30 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances.
  • Page 412: Security

    Operator Logoff: Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session. • Clear Security Data: Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the operands associated with the self-tests. G30 Generator Protection System GE Multilin...
  • Page 413: Targets Menu

     MESSAGE Each G30 element with a TARGET setting has a target message that when activated by its element is displayed in sequence with any other currently active target messages in the menu. In the example shown, the Phase TOC4 TARGETS and Digital Element 48 target settings are active and so have their targets displayed.
  • Page 414 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the G30 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).
  • Page 415 • What to do: Verify that all the items in the GOOSE data set are supported by the G30. The EnerVista UR Setup soft- ware will list the valid items. An IEC61850 client will also show which nodes are available for the G30.
  • Page 416 MAINTENANCE ALERT: 4L Discrepancy • Latched target message: No. • Description of problem: A discrepancy has been detected between the actual and desired state of a latching contact output of an installed type “4L” module. G30 Generator Protection System GE Multilin...
  • Page 417 Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the G30 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
  • Page 418 Bricks, or faults in the Brick input conditioning hardware. If the error was annunciated the first time significant signal was encountered, suspect the former cause and check the copper connections external to the Brick. Where multiple UR-series devices have self-test errors, look for common causes. 7-10 G30 Generator Protection System GE Multilin...
  • Page 419 Brick output failing to respond to an output command can only be detected while the command is active, and so in this case the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended, however the output may still be non-functional. GE Multilin G30 Generator Protection System 7-11...
  • Page 420 7.2 TARGETS 7 COMMANDS AND TARGETS 7-12 G30 Generator Protection System GE Multilin...
  • Page 421: Security

    To add user accounts: Select the Security > User Management menu item to open the user management window. Enter a username in the User field. The username must be 4 to 20 characters in length. GE Multilin G30 Generator Protection System...
  • Page 422: Modifying User Privileges

    • The EnerVista security management system must be enabled To modify user privileges: Select the Security > User Management menu item to open the user management window. Locate the username in the User field. G30 Generator Protection System GE Multilin...
  • Page 423: Password Requirements

    Password must contain characters from all of the following four categories: - English uppercase characters (A through Z) - English lowercase characters (a through z) - Base 10 digits (0 through 9) - Non-alphabetic characters (for example, ~, !, @, #, $,%, &) GE Multilin G30 Generator Protection System...
  • Page 424: Cybersentry

    (Administrator, Engineer, Supervisor, Observer, Operator) as login names and the associated passwords are stored on the UR device. As such, when using the local accounts, access is not user-attributable. G30 Generator Protection System GE Multilin...
  • Page 425 All the other ports are closed. For example, Modbus is on by default, so its TCP port number, 502, is open. But if Modbus is disabled, port 502 is closed. This function has been tested and no unused ports have been found NOTE open. GE Multilin G30 Generator Protection System...
  • Page 426: Security Menu

    This setting must following (Shared) Secret meet the CyberSentry password password requirements. section for requirements RADIUS Authentication method used by RADIUS EAP-TTLS EAP-TTLS EAP-TTLS Administrator Authentication server. Currently fixed to EAP-TTLS. Method G30 Generator Protection System GE Multilin...
  • Page 427 See the Change Text The specified role protected. All RADIUS users are password- following following Me1# and Administrator, protected. password password except for section for section for Supervisor, where requirements requireme it is only itself GE Multilin G30 Generator Protection System...
  • Page 428 |--------------- Oscillography |--------------- Data Logger |--------------- Demand User Programmable |--------------- LEDs User Programmable |--------------- self test |--------------- Control Pushbuttons User programmable |--------------- Pushbuttons |--------------- Flex states User definable dis- |--------------- plays |--------------- Direct I/O G30 Generator Protection System GE Multilin...
  • Page 429 |------------ Clear Records |------------ Set date and time User Displays Targets Actual Values |------------ Front Panel Labels Designer |------------ Status |------------ Metereing |------------ Transducer I/O |------------ Records |------------ Product Info Maintenance |------------ Modbus Analyzer GE Multilin G30 Generator Protection System...
  • Page 430 Remote user IDs must reside on an external RADIUS server, and must be provided with the requisite user role (see the fol- lowing example). Users are specified in the RADIUS server configuration file for users. Roles are specified in the RADIUS server dictionary. Example: In the file ‘users’: exampleusername User-Password == "examplepassword" 8-10 G30 Generator Protection System GE Multilin...
  • Page 431: Application Of Settings

    The GSU is lagging by –30° (from the line side to the generator side). Take note of the CT polarities in wiring diagram. These are necessary to correctly meter forward power. Loss of excitation and reverse power will be assigned to source 2. GE Multilin G30 Generator Protection System...
  • Page 432 IN-ZONE TRANSFORMER WITH VT ON THE LV SIDE Consider the generator protection system shown below, with an in-zone transformer with VT on the low-voltage (LV) side: Figure 9–2: TYPICAL WIRING, VT ON THE LV SIDE OF THE TRANSFORMER G30 Generator Protection System GE Multilin...
  • Page 433 The GSU is again lagging by –30° (from the line side to the generator side). Loss of excitation and reverse power will be assigned to source 1. In this case, the only phase shift that must be accounted for is the phase shift of the transformer. Winding 2 is therefore shifted by –30°. GE Multilin G30 Generator Protection System...
  • Page 434 9.1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS d) NO IN-ZONE TRANSFORMER Consider the generator protection system shown below, with no in-zone transformer: Figure 9–3: TYPICAL WIRING, NO IN-ZONE TRANSFORMER The two sources are configured as follows: G30 Generator Protection System GE Multilin...
  • Page 435: System Setup

    9.1 SETTING EXAMPLE The G30 requires the use of the transformer windings settings for the differential element, even if the differential is applied only as a stator differential for the generator. These settings ensure that the differential element operates with the correct phase shifts, and applies the correct magnitude compensation.
  • Page 436: Power System

    8% and the I T capability is 10. The generator nominal current is: primary 6800 A -------------------------------- - ------------------ - 0.85 pu (EQ 9.5) nom pu CT primary 8000 A G30 Generator Protection System GE Multilin...
  • Page 437: Loss Of Excitation

    -------------------- - --------------------- - 15.28 Ω (EQ 9.14) The voltage supervision setting will be determined by a system study and may be disabled on either element if required. VT fuse failure should supervise this element. GE Multilin G30 Generator Protection System...
  • Page 438: Reverse Power

    Make the following changes in EnerVista UR Setup or through the  SETTINGS    menu: GROUPED ELEMENTS SETTING GROUP 1 SENSITIVE DIRECTIONAL POWER DIRECTIONAL POWER 1 G30 Generator Protection System GE Multilin...
  • Page 439: System Backup Overcurrent

    A = 28.2, B = 0.1217, and p = 2. Solving for TDM, we have: 0.75 ------------------------------------------------------------------------------ - 0.88 (EQ 9.24) 28.2 ----------------------------------------------------- - 0.1217 2.64   ----------------------------------- - –   × 1.275 0.329 GE Multilin G30 Generator Protection System...
  • Page 440: Overexcitation

    The volts per hertz 1 pickup will be used to generate an alarm. Either source may be assigned in this example. Make the following changes in EnerVista UR Setup or through the   SETTINGS GROUPED ELEMENTS SET- 9-10 G30 Generator Protection System GE Multilin...
  • Page 441: Inputs/Outputs

       SETTINGS INPUTS/OUTPUTS VIRTUAL OUTPUTS menus: VIRTUAL OUTPUT 1(4) Make the following changes in EnerVista UR Setup or through the    SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS menus: CONTACT OUTPUT H1(H4) GE Multilin G30 Generator Protection System 9-11...
  • Page 442: Frequency

    Make the following changes in EnerVista UR Setup or through the   SETTINGS GROUPED ELEMENTS SETTING GROUP  menu: ACCIDENTAL ENERGIZATION 9-12 G30 Generator Protection System GE Multilin...
  • Page 443: Flexlogic

    9.1 SETTING EXAMPLE 9.1.13 FLEXLOGIC The following logic as given as an example only. The logic for each specific application depends on system design, protec- tion philosophies, and operating practices. Figure 9–6: APPLICATION EXAMPLE FLEXLOGIC GE Multilin G30 Generator Protection System 9-13...
  • Page 444 9.1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9-14 G30 Generator Protection System GE Multilin...
  • Page 445: Commissioning

    Injection to a particular G30 frequency element must be to its configured source and to the channels the source uses for frequency measurement. For frequency measurement, a source will use the first quantity configured in the following order:...
  • Page 446 1 second from test set time reading of ramp start to relay operation. Note that the G30 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time taken by the frequency responding component to pickup.
  • Page 447: Maintenance

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the G30. 842812A1.CDR Figure 11–1: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE)
  • Page 448 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. CPU connections must be individually disconnected from the module before the module can be removed from the chassis. NOTE 11-2 G30 Generator Protection System GE Multilin...
  • Page 449: Batteries

    10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit. 11. Power on the unit. 12. Dispose of the old battery as outlined in the next section. GE Multilin G30 Generator Protection System 11-3...
  • Page 450: Dispose Of Battery

    La batterie est marqué de ce symbole, qui comprennent les indications cadmium (Cd), plomb (Pb), ou mercure (Hg). Pour le recyclage, retourner la batterie à votre fournisseur ou à un point de collecte. Pour plus d'informations, voir: www.recyclethis.info. 11-4 G30 Generator Protection System GE Multilin...
  • Page 451 Baterija je označena s tem simbolom, ki lahko vključuje napise, ki označujejo kadmij (Cd), svinec (Pb) ali živo srebro (Hg). Za ustrezno recikliranje baterijo vrnite dobavitelju ali jo odstranite na določenem zbirališču. Za več informacij obiščite spletno stran: www.recyclethis.info. GE Multilin G30 Generator Protection System 11-5...
  • Page 452 Latin America +55 11 3614 1700 Europe, Middle East, Africa +(34) 94 485 88 00 Asia +86 21 2401 3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574 11-6 G30 Generator Protection System GE Multilin...
  • Page 453: Uninstall And Clear Files And Data

    Other files can be in standard formats, such as COMTRADE or .csv. You cannot erase directly the flash memory, but all records and settings in that memory can be deleted. Do this using the   command. SETTINGS PRODUCT SETUP CLEAR RELAY RECORDS GE Multilin G30 Generator Protection System 11-7...
  • Page 454: Repairs

    Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Digital Energy service department in Canada at +1 905 927 5098. Use the detailed return procedure outlined at https://www.gedigitalenergy.com/multilin/support/ret_proc.htm...
  • Page 455: Storage

    Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range outlined in the Specifications. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. GE Multilin G30 Generator Protection System 11-9...
  • Page 456: Disposal

    European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove the modules as outlined earlier, dismantle the unit, and recycle the metal when possible. 11-10 G30 Generator Protection System GE Multilin...
  • Page 457: Parameter Lists

    Freq Rate 4 Value Hz/s Frequency rate of change 4 actual value 6144 SRC 1 Ia RMS Amps Source 1 phase A current RMS 6146 SRC 1 Ib RMS Amps Source 1 phase B current RMS GE Multilin G30 Generator Protection System...
  • Page 458 SRC 3 Ia RMS Amps Source 3 phase A current RMS 6274 SRC 3 Ib RMS Amps Source 3 phase B current RMS 6276 SRC 3 Ic RMS Amps Source 3 phase C current RMS G30 Generator Protection System GE Multilin...
  • Page 459 SRC 1 Vbg RMS Volts Source 1 phase BG voltage RMS 6660 SRC 1 Vcg RMS Volts Source 1 phase CG voltage RMS 6662 SRC 1 Vag Mag Volts Source 1 phase AG voltage magnitude GE Multilin G30 Generator Protection System...
  • Page 460 Source 2 auxiliary voltage angle 6755 SRC 2 V_0 Mag Volts Source 2 zero-sequence voltage magnitude 6757 SRC 2 V_0 Angle Degrees Source 2 zero-sequence voltage angle 6758 SRC 2 V_1 Mag Volts Source 2 positive-sequence voltage magnitude G30 Generator Protection System GE Multilin...
  • Page 461 SRC 4 Vbc Mag Volts Source 4 phase BC voltage magnitude 6874 SRC 4 Vbc Angle Degrees Source 4 phase BC voltage angle 6875 SRC 4 Vca Mag Volts Source 4 phase CA voltage magnitude GE Multilin G30 Generator Protection System...
  • Page 462 Source 3 phase A real power 7236 SRC 3 Pb Watts Source 3 phase B real power 7238 SRC 3 Pc Watts Source 3 phase C real power 7240 SRC 3 Q Vars Source 3 three-phase reactive power G30 Generator Protection System GE Multilin...
  • Page 463 SRC 1 Va Harm[12] Source 1 phase A voltage fourteenth harmonic 8078 SRC 1 Va Harm[13] Source 1 phase A voltage fifteenth harmonic 8079 SRC 1 Va Harm[14] Source 1 phase A voltage sixteenth harmonic GE Multilin G30 Generator Protection System...
  • Page 464 SRC 1 Vc Harm[9] Source 1 phase C voltage eleventh harmonic 8125 SRC 1 Vc Harm[10] Source 1 phase C voltage twelfth harmonic 8126 SRC 1 Vc Harm[11] Source 1 phase C voltage thirteenth harmonic G30 Generator Protection System GE Multilin...
  • Page 465 SRC 2 Vb Harm[6] Source 2 phase B voltage eighth harmonic 8172 SRC 2 Vb Harm[7] Source 2 phase B voltage ninth harmonic 8173 SRC 2 Vb Harm[8] Source 2 phase B voltage tenth harmonic GE Multilin G30 Generator Protection System...
  • Page 466 SRC 3 Va Harm[3] Source 3 phase A voltage fifth harmonic 8219 SRC 3 Va Harm[4] Source 3 phase A voltage sixth harmonic 8220 SRC 3 Va Harm[5] Source 3 phase A voltage seventh harmonic A-10 G30 Generator Protection System GE Multilin...
  • Page 467 SRC 3 Vc Harm[0] Source 3 phase C voltage second harmonic 8266 SRC 3 Vc Harm[1] Source 3 phase C voltage third harmonic 8267 SRC 3 Vc Harm[2] Source 3 phase C voltage fourth harmonic GE Multilin G30 Generator Protection System A-11...
  • Page 468 Source 4 phase A voltage twenty-fourth harmonic 8313 SRC 4 Va Harm[23] Source 4 phase A voltage twenty-fifth harmonic 8314 SRC 4 Vb THD Source 4 phase B voltage total harmonic distortion (THD) A-12 G30 Generator Protection System GE Multilin...
  • Page 469 SRC 4 Vc Harm[19] Source 4 phase C voltage twenty-first harmonic 8360 SRC 4 Vc Harm[20] Source 4 phase C voltage twenty-second harmonic 8361 SRC 4 Vc Harm[21] Source 4 phase C voltage twenty-third harmonic GE Multilin G30 Generator Protection System A-13...
  • Page 470 SRC 1 Ia Harm[4] Source 1 phase A current sixth harmonic 10246 SRC 1 Ia Harm[5] Source 1 phase A current seventh harmonic 10247 SRC 1 Ia Harm[6] Source 1 phase A current eighth harmonic A-14 G30 Generator Protection System GE Multilin...
  • Page 471 SRC 1 Ic Harm[1] Source 1 phase C current third harmonic 10309 SRC 1 Ic Harm[2] Source 1 phase C current fourth harmonic 10310 SRC 1 Ic Harm[3] Source 1 phase C current fifth harmonic GE Multilin G30 Generator Protection System A-15...
  • Page 472 SRC 2 Ia Harm[23] Source 2 phase A current twenty-fifth harmonic 10372 SRC 2 Ib THD Source 2 phase B current total harmonic distortion 10373 SRC 2 Ib Harm[0] Source 2 phase B current second harmonic A-16 G30 Generator Protection System GE Multilin...
  • Page 473 SRC 2 Ic Harm[20] Source 2 phase C current twenty-second harmonic 10427 SRC 2 Ic Harm[21] Source 2 phase C current twenty-third harmonic 10428 SRC 2 Ic Harm[22] Source 2 phase C current twenty-fourth harmonic GE Multilin G30 Generator Protection System A-17...
  • Page 474 SRC 3 Ib Harm[17] Source 3 phase B current nineteenth harmonic 10490 SRC 3 Ib Harm[18] Source 3 phase B current twentieth harmonic 10491 SRC 3 Ib Harm[19] Source 3 phase B current twenty-first harmonic A-18 G30 Generator Protection System GE Multilin...
  • Page 475 SRC 4 Ia Harm[14] Source 4 phase A current sixteenth harmonic 10553 SRC 4 Ia Harm[15] Source 4 phase A current seventeenth harmonic 10554 SRC 4 Ia Harm[16] Source 4 phase A current eighteenth harmonic GE Multilin G30 Generator Protection System A-19...
  • Page 476 SRC 4 Ic Harm[11] Source 4 phase C current thirteenth harmonic 10616 SRC 4 Ic Harm[12] Source 4 phase C current fourteenth harmonic 10617 SRC 4 Ic Harm[13] Source 4 phase C current fifteenth harmonic A-20 G30 Generator Protection System GE Multilin...
  • Page 477 RTD input 9 actual value 13561 RTD Inputs 10 Value RTD input 10 actual value 13562 RTD Inputs 11 Value RTD input 11 actual value 13563 RTD Inputs 12 Value RTD input 12 actual value GE Multilin G30 Generator Protection System A-21...
  • Page 478 FlexElement 2 actual value 39172 FlexElement 3 Value FlexElement 3 actual value 39174 FlexElement 4 Value FlexElement 4 actual value 39176 FlexElement 5 Value FlexElement 5 actual value 39178 FlexElement 6 Value FlexElement 6 actual value A-22 G30 Generator Protection System GE Multilin...
  • Page 479: Flexinteger Items

    IEC61850 GOOSE UInteger input 6 9980 GOOSE UInt Input 7 IEC61850 GOOSE UInteger input 7 9982 GOOSE UInt Input 8 IEC61850 GOOSE UInteger input 8 9984 GOOSE UInt Input 9 IEC61850 GOOSE UInteger input 9 GE Multilin G30 Generator Protection System A-23...
  • Page 480 IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 A-24 G30 Generator Protection System GE Multilin...
  • Page 481: Modbus Communications

    See the Supported Function Codes section for complete details. An exception response from the slave is indi- cated by setting the high order bit of the function code in the response packet. See the Exception Responses section for further details. GE Multilin G30 Generator Protection System...
  • Page 482: Modbus Rtu Crc-16 Algorithm

    This algorithm requires the characteristic polynomial to be reverse bit ordered. The most significant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder. A C programming language implementation of the CRC algorithm will be provided upon request. G30 Generator Protection System GE Multilin...
  • Page 483 No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC GE Multilin G30 Generator Protection System...
  • Page 484: Modbus Function Codes

    DATA #1 - low NUMBER OF REGISTERS - low DATA #2 - high CRC - low DATA #2 - low CRC - high DATA #3 - high DATA #3 - low CRC - low CRC - high G30 Generator Protection System GE Multilin...
  • Page 485: Execute Operation (Function Code 05H

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high GE Multilin G30 Generator Protection System...
  • Page 486: Store Multiple Settings (Function Code 10H

    PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte G30 Generator Protection System GE Multilin...
  • Page 487: B.3.1 Obtaining Relay Files Via Modbus

    Familiarity with the data logger feature is required to understand this description. Refer to the Data Logger section of Chap- ter 5 for details. To read the entire data logger in binary COMTRADE format, read the following files. GE Multilin G30 Generator Protection System...
  • Page 488: File Transfers

    EVTnnn.TXT (replace nnn with the desired starting record number) To read from a specific record to another specific record, use the following filename: EVT.TXT xxxxx yyyyy (replace xxxxx with the starting record number and yyyyy with the ending record number) G30 Generator Protection System GE Multilin...
  • Page 489: Memory Mapping

    0 (Off) 040E Virtual Input 15 State 0 to 1 F108 0 (Off) 040F Virtual Input 16 State 0 to 1 F108 0 (Off) 0410 Virtual Input 17 State 0 to 1 F108 0 (Off) GE Multilin G30 Generator Protection System...
  • Page 490 Digital Counter 1 Frozen -2147483647 to F004 2147483647 0804 Digital Counter 1 Frozen Time Stamp 0 to 4294967295 F050 0806 Digital Counter 1 Frozen Time Stamp us (microsecond part 0 to 4294967295 F003 of time stamp) B-10 G30 Generator Protection System GE Multilin...
  • Page 491 Field Unit Contact Input Output Operand States (8 items) 0 to 65535 F500 15EB Field Contact Output Physical States (8 items) 0 to 65535 F500 15F3 Field Contact Output Current States (8 items) 0 to 65535 F500 GE Multilin G30 Generator Protection System B-11...
  • Page 492 ...Repeated for Field Transducer 3 16CE ...Repeated for Field Transducer 4 16D0 ...Repeated for Field Transducer 5 16D2 ...Repeated for Field Transducer 6 16D4 ...Repeated for Field Transducer 7 16D6 ...Repeated for Field Transducer 8 B-12 G30 Generator Protection System GE Multilin...
  • Page 493 Source 1 Phase CA or CB Voltage Magnitude 0 to 999999.999 0.001 F060 1A1D Source 1 Phase CA or CB Voltage Angle -359.9 to 0 degrees F002 1A1E Source 1 Auxiliary Voltage RMS 0 to 999999.999 0.001 F060 GE Multilin G30 Generator Protection System B-13...
  • Page 494 ...Repeated for Source 4 Energy Commands (Read/Write Command) 1D60 Energy Clear Command 0 to 1 F126 0 (No) Source Frequency (Read Only) (4 modules) 1D80 Frequency for Source 1 2 to 90 0.001 F003 B-14 G30 Generator Protection System GE Multilin...
  • Page 495 6 (H1a) 2461 Field Raw Data Freeze 0 to 1 F102 0 (Disabled) Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 modules) 2620 Remote Double-Point Status Input 1 Device 1 to 32 F001 GE Multilin G30 Generator Protection System B-15...
  • Page 496 Ic Harmonics for Source 1 - 2nd to 25th (24 items) 0 to 99.9 F001 285B Reserved (8 items) 0 to 0.1 F001 2863 ...Repeated for Source 2 28C6 ...Repeated for Source 3 2929 ...Repeated for Source 4 B-16 G30 Generator Protection System GE Multilin...
  • Page 497 Security (Read/Write) 32A0 Supervisor Alphanumeric Password Entry F202 (none) Security (Read/Write Setting) 32AA Engineer Alphanumeric Password Setting F202 (none) Security (Read Only) 32B4 Engineer Alphanumeric Password Status 0 to 1 F102 0 (Disabled) GE Multilin G30 Generator Protection System B-17...
  • Page 498 DCmA Input Values (Read Only) (24 modules) 34C0 DCmA Inputs 1 Value -9999.999 to 9999.999 0.001 F004 34C2 DCmA Inputs 2 Value -9999.999 to 9999.999 0.001 F004 34C4 DCmA Inputs 3 Value -9999.999 to 9999.999 0.001 F004 B-18 G30 Generator Protection System GE Multilin...
  • Page 499 -32768 to 32767 °C F002 350D RTD Input 30 Value -32768 to 32767 °C F002 350E RTD Input 31 Value -32768 to 32767 °C F002 350F RTD Input 32 Value -32768 to 32767 °C F002 GE Multilin G30 Generator Protection System B-19...
  • Page 500 0 to 999999999 F003 3766 PTP Port 1 State (3 items) 0 to 4 F625 0 (Disabled) 3769 RTC Offset 0 to 999999999 F004 376B PTP - IRIG-B Delta -500000000 to 500000000 F004 B-20 G30 Generator Protection System GE Multilin...
  • Page 501 1 (Vag) 389E Remote Auxiliary VT 1 Secondary 25 to 240 F001 389F Remote Auxiliary VT 1 Ratio 1 to 24000 F060 38A1 ...Repeated for module number 2 38B2 ...Repeated for module number 3 GE Multilin G30 Generator Protection System B-21...
  • Page 502 Field Shared Input 1 Unit Origin 1 0 to 8 F256 0 (None) 3B07 Field Shared Input 1 Channel Origin 1 1 to 15 F001 3B08 Field Shared Input 1 Events 0 to 1 F102 1 (Enabled) B-22 G30 Generator Protection System GE Multilin...
  • Page 503 ...Repeated for Field Shared Output 3 3E57 ...Repeated for Field Shared Output 4 3E64 ...Repeated for Field Shared Output 5 3E71 ...Repeated for Field Shared Output 6 3E7E ...Repeated for Field Shared Output 7 GE Multilin G30 Generator Protection System B-23...
  • Page 504 (none) Passwords (Read/Write Setting) 400A Setting Password Setting 0 to 4294967295 F202 (none) Passwords (Read/Write) 4014 Command Password Entry 0 to 4294967295 F202 (none) 401E Setting Password Entry 0 to 4294967295 F202 (none) B-24 G30 Generator Protection System GE Multilin...
  • Page 505 F001 40A6 Main UDP Port Number for the TFTP Protocol 0 to 65535 F001 40A7 Data Transfer UDP Port Numbers for the TFTP Protocol 0 to 65535 F001 (zero means “automatic”) (2 items) GE Multilin G30 Generator Protection System B-25...
  • Page 506 0 (Disabled) 413F High Enet Traffic Events 0 to 1 F102 0 (Disabled) 4140 DNP Object 1 Default Variation 1 to 2 F001 4141 DNP Object 2 Default Variation 1 to 3 F001 B-26 G30 Generator Protection System GE Multilin...
  • Page 507 Daylight Savings Time (DST) Function 0 to 1 F102 0 (Disabled) 41AA Daylight Savings Time (DST) Start Month 0 to 11 F237 0 (January) 41AB Daylight Savings Time (DST) Start Day 0 to 6 F238 0 (Sunday) GE Multilin G30 Generator Protection System B-27...
  • Page 508 ...Repeated for User-Programmable LED 29 4317 ...Repeated for User-Programmable LED 30 431A ...Repeated for User-Programmable LED 31 431D ...Repeated for User-Programmable LED 32 4320 ...Repeated for User-Programmable LED 33 4323 ...Repeated for User-Programmable LED 34 B-28 G30 Generator Protection System GE Multilin...
  • Page 509 1 to 24000 F060 4508 ...Repeated for VT Bank 2 4510 ...Repeated for VT Bank 3 4518 ...Repeated for VT Bank 4 4520 ...Repeated for VT Bank 5 4528 ...Repeated for VT Bank 6 GE Multilin G30 Generator Protection System B-29...
  • Page 510 0 to 4294967295 F300 47DF Breaker 1 External Alarm 0 to 4294967295 F300 47E1 Breaker 1 Alarm Delay 0 to 65.535 0.001 F003 47E3 Breaker 1 Pushbutton Control 0 to 1 F102 0 (Disabled) B-30 G30 Generator Protection System GE Multilin...
  • Page 511 4E12 Raw Field Data AC7 Mag 0 to 0.001 0.001 F003 4E14 Raw Field Data AC7 Angle 0 to 0.01 degree F002 4E15 Raw Field Data AC8 Mag 0 to 0.001 0.001 F003 GE Multilin G30 Generator Protection System B-31...
  • Page 512 ...Repeated for RTD Input 17 5554 ...Repeated for RTD Input 18 5568 ...Repeated for RTD Input 19 557C ...Repeated for RTD Input 20 5590 ...Repeated for RTD Input 21 55A4 ...Repeated for RTD Input 22 B-32 G30 Generator Protection System GE Multilin...
  • Page 513 ...Repeated for FlexLogic Timer 19 5898 ...Repeated for FlexLogic Timer 20 58A0 ...Repeated for FlexLogic Timer 21 58A8 ...Repeated for FlexLogic Timer 22 58B0 ...Repeated for FlexLogic Timer 23 58B8 ...Repeated for FlexLogic Timer 24 GE Multilin G30 Generator Protection System B-33...
  • Page 514 F300 5C07 Neutral Instantaneous Overcurrent 1 Target 0 to 2 F109 0 (Self-reset) 5C08 Neutral Instantaneous Overcurrent 1 Events 0 to 1 F102 0 (Disabled) 5C09 Reserved (8 items) 0 to 1 F001 B-34 G30 Generator Protection System GE Multilin...
  • Page 515 1 to 65535 F001 items) 5F5B Frequency Out-Of-Band Accumulator Time Preset Array (7 0 to 65535 F001 items) 5F62 Frequency Out-Of-Band Accumulator Upper Frequency 20 to 70 0.01 F001 6000 Array (7 items) GE Multilin G30 Generator Protection System B-35...
  • Page 516 0 to 2 F109 0 (Self-reset) 6478 Overfrequency 1 Events 0 to 1 F102 0 (Disabled) 6479 Reserved (4 items) 0 to 1 F001 647D ...Repeated for Overfrequency 2 648A ...Repeated for Overfrequency 3 B-36 G30 Generator Protection System GE Multilin...
  • Page 517 F300 66E5 Third Harmonic Neutral Undervoltage Target 0 to 2 F109 0 (Self-reset) 66E6 Third Harmonic Neutral Undervoltage Events 0 to 1 F102 0 (Disabled) 66E7 Reserved (4 items) 0 to 65535 F001 GE Multilin G30 Generator Protection System B-37...
  • Page 518 Phase Undervoltage 1 Signal Source 0 to 5 F167 0 (SRC 1) 7002 Phase Undervoltage 1 Pickup 0 to 3 0.001 F001 1000 7003 Phase Undervoltage 1 Curve 0 to 1 F111 0 (Definite Time) B-38 G30 Generator Protection System GE Multilin...
  • Page 519 0 to 5 F167 0 (SRC 1) 7262 Negative Sequence Directional Overcurrent 1 Type 0 to 1 F179 0 (Neg Sequence) 7263 Neg Sequence Directional Overcurrent 1 Forward ECA 0 to 90 ° Lag F002 GE Multilin G30 Generator Protection System B-39...
  • Page 520 0 to 1000 min. F001 778F Thermal Protection 1 Reset 0 to 4294967295 F300 7791 Thermal Protection 1 Block 0 to 4294967295 F300 7793 Thermal Protection 1 Target 0 to 2 F109 0 (Self-reset) B-40 G30 Generator Protection System GE Multilin...
  • Page 521 ...Repeated for User Programmable Pushbutton 10 7D40 ...Repeated for User Programmable Pushbutton 11 7D70 ...Repeated for User Programmable Pushbutton 12 7DA0 ...Repeated for User Programmable Pushbutton 13 7DD0 ...Repeated for User Programmable Pushbutton 14 GE Multilin G30 Generator Protection System B-41...
  • Page 522 0 to 4294967295 F003 81CC Reserved Register T8 0 to 4294967295 F003 EGD Fast Production Status (Read Only Non-Volatile and Read Only) 83E0 EGD Fast Producer Exchange 1 Signature 0 to 65535 F001 B-42 G30 Generator Protection System GE Multilin...
  • Page 523 ...Repeated for Digital Element 17 8B76 ...Repeated for Digital Element 18 8B8C ...Repeated for Digital Element 19 8BA2 ...Repeated for Digital Element 20 8BB8 ...Repeated for Digital Element 21 8BCE ...Repeated for Digital Element 22 GE Multilin G30 Generator Protection System B-43...
  • Page 524 0.1 to 50 F001 900A FlexElement 1 Pickup -90 to 90 0.001 F004 1000 900C FlexElement 1 DeltaT Units 0 to 2 F518 0 (Milliseconds) 900D FlexElement 1 DeltaT 20 to 86400 F003 B-44 G30 Generator Protection System GE Multilin...
  • Page 525 “Dir Ip 1” 9406 Direct Output 1 Name 1 to 96 F205 “Dir Out 1” 940C ...Repeated for Direct Input/Output 2 9418 ...Repeated for Direct Input/Output 3 9424 ...Repeated for Direct Input/Output 4 GE Multilin G30 Generator Protection System B-45...
  • Page 526 FlexElement 3 Actual -2147483.647 to 2147483.647 0.001 F004 9906 FlexElement 4 Actual 0.001 F004 -2147483.647 to 2147483.647 9908 FlexElement 5 Actual 0.001 F004 -2147483.647 to 2147483.647 990A FlexElement 6 Actual -2147483.647 to 2147483.647 0.001 F004 B-46 G30 Generator Protection System GE Multilin...
  • Page 527 F001 Selector Switch Settings (Read/Write) (2 modules) A280 Selector 1 Function 0 to 1 F102 0 (Disabled) A281 Selector 1 Range 1 to 7 F001 A282 Selector 1 Timeout 3 to 60 F001 GE Multilin G30 Generator Protection System B-47...
  • Page 528 Volts Per Hertz 2 0 to 65.535 0.001 F001 FlexCurves C and D (Read/Write Setting) A600 FlexCurve C (120 items) 0 to 65535 F011 A680 FlexCurve D (120 items) 0 to 65535 F011 B-48 G30 Generator Protection System GE Multilin...
  • Page 529 Restricted Ground Fault 1 Target 0 to 2 F109 0 (Self-reset) A969 Restricted Ground Fault 1 Events 0 to 1 F102 0 (Disabled) A96A ...Repeated for Restricted Ground Fault 2 A974 ...Repeated for Restricted Ground Fault 3 GE Multilin G30 Generator Protection System B-49...
  • Page 530 0 to 65534 F206 (none) AB33 IEC 61850 Logical Node PIOCx Name Prefix (72 items) 0 to 65534 F206 (none) AC0B IEC 61850 Logical Node PTOCx Name Prefix (24 items) 0 to 65534 F206 (none) B-50 G30 Generator Protection System GE Multilin...
  • Page 531 ...Repeated for IEC 61850 GGIO4 Analog Input 29 AFDB ...Repeated for IEC 61850 GGIO4 Analog Input 30 AFE2 ...Repeated for IEC 61850 GGIO4 Analog Input 31 AFE9 ...Repeated for IEC 61850 GGIO4 Analog Input 32 GE Multilin G30 Generator Protection System B-51...
  • Page 532 0.001 to 100 0.001 F003 10000 B0F4 IEC 61850 MMXU PF.phsC Deadband 1 0.001 to 100 0.001 F003 10000 B0F6 ...Repeated for Deadband 2 B12C ...Repeated for Deadband 3 B162 ...Repeated for Deadband 4 B-52 G30 Generator Protection System GE Multilin...
  • Page 533 ...Repeated for module number 10 B38E ...Repeated for module number 11 B391 ...Repeated for module number 12 B394 ...Repeated for module number 13 B397 ...Repeated for module number 14 B39A ...Repeated for module number 15 GE Multilin G30 Generator Protection System B-53...
  • Page 534 ...Repeated for module number 15 BAE0 ...Repeated for module number 16 Contact Inputs (Read/Write Setting) (96 modules) BB00 Contact Input 1 Name F205 “Cont Ip 1“ BB06 Contact Input 1 Events 0 to 1 F102 0 (Disabled) B-54 G30 Generator Protection System GE Multilin...
  • Page 535 ...Repeated for Contact Input 49 BC88 ...Repeated for Contact Input 50 BC90 ...Repeated for Contact Input 51 BC98 ...Repeated for Contact Input 52 BCA0 ...Repeated for Contact Input 53 BCA8 ...Repeated for Contact Input 54 GE Multilin G30 Generator Protection System B-55...
  • Page 536 0 to 1 F102 0 (Disabled) BE39 Reserved (3 items) F001 BE3C ...Repeated for Virtual Input 2 BE48 ...Repeated for Virtual Input 3 BE54 ...Repeated for Virtual Input 4 BE60 ...Repeated for Virtual Input 5 B-56 G30 Generator Protection System GE Multilin...
  • Page 537 ...Repeated for Virtual Input 54 C0B8 ...Repeated for Virtual Input 55 C0C4 ...Repeated for Virtual Input 56 C0D0 ...Repeated for Virtual Input 57 C0DC ...Repeated for Virtual Input 58 C0E8 ...Repeated for Virtual Input 59 GE Multilin G30 Generator Protection System B-57...
  • Page 538 ...Repeated for Virtual Output 41 C278 ...Repeated for Virtual Output 42 C280 ...Repeated for Virtual Output 43 C288 ...Repeated for Virtual Output 44 C290 ...Repeated for Virtual Output 45 C298 ...Repeated for Virtual Output 46 B-58 G30 Generator Protection System GE Multilin...
  • Page 539 Mandatory (Read/Write Setting or Command) C430 Test Mode Function 0 to 2 F245 0 (Disabled) C431 Force VFD and LED 0 to 1 F126 0 (No) C432 Test Mode Initiate 0 to 4294967295 F300 GE Multilin G30 Generator Protection System B-59...
  • Page 540 ...Repeated for Direct Output 29 C657 ...Repeated for Direct Output 30 C65A ...Repeated for Direct Output 31 C65D ...Repeated for Direct Output 32 Reset (Read/Write Setting) C750 FlexLogic operand which initiates a reset 0 to 4294967295 F300 B-60 G30 Generator Protection System GE Multilin...
  • Page 541 ...Repeated for Direct Input 25 C8F4 ...Repeated for Direct Input 26 C8F8 ...Repeated for Direct Input 27 C8FC ...Repeated for Direct Input 28 C900 ...Repeated for Direct Input 29 C904 ...Repeated for Direct Input 30 GE Multilin G30 Generator Protection System B-61...
  • Page 542 CFA0 Remote Input 1 Device 1 to 32 F001 CFA1 Remote Input 1 Bit Pair 0 to 96 F156 0 (None) CFA2 Remote Input 1 Default State 0 to 3 F086 0 (Off) B-62 G30 Generator Protection System GE Multilin...
  • Page 543 ...Repeated for Remote Output 14 D258 ...Repeated for Remote Output 15 D25C ...Repeated for Remote Output 16 D260 ...Repeated for Remote Output 17 D264 ...Repeated for Remote Output 18 D268 ...Repeated for Remote Output 19 GE Multilin G30 Generator Protection System B-63...
  • Page 544 IEC 61850 GGIO2.CF.SPCSO2.ctlModel Value 0 to 2 F001 D322 IEC 61850 GGIO2.CF.SPCSO3.ctlModel Value 0 to 2 F001 D323 IEC 61850 GGIO2.CF.SPCSO4.ctlModel Value 0 to 2 F001 D324 IEC 61850 GGIO2.CF.SPCSO5.ctlModel Value 0 to 2 F001 B-64 G30 Generator Protection System GE Multilin...
  • Page 545 IEC 61850 GGIO2.CF.SPCSO56.ctlModel Value 0 to 2 F001 D358 IEC 61850 GGIO2.CF.SPCSO57.ctlModel Value 0 to 2 F001 D359 IEC 61850 GGIO2.CF.SPCSO58.ctlModel Value 0 to 2 F001 D35A IEC 61850 GGIO2.CF.SPCSO59.ctlModel Value 0 to 2 F001 GE Multilin G30 Generator Protection System B-65...
  • Page 546 ...Repeated for Contact Output 18 DD9E ...Repeated for Contact Output 19 DDAD ...Repeated for Contact Output 20 DDBC ...Repeated for Contact Output 21 DDCB ...Repeated for Contact Output 22 DDDA ...Repeated for Contact Output 23 B-66 G30 Generator Protection System GE Multilin...
  • Page 547 0.001 F004 20000 E063 ...Repeated for DCmA Inputs 2 E076 ...Repeated for DCmA Inputs 3 E089 ...Repeated for DCmA Inputs 4 E09C ...Repeated for DCmA Inputs 5 E0AF ...Repeated for DCmA Inputs 6 GE Multilin G30 Generator Protection System B-67...
  • Page 548 ED01 Reserved F205 (none) Setting File Template (Read Only Non-Volatile) ED07 Last Settings Change Date 0 to 4294967295 F050 Settings File Template (Read/Write Setting) ED09 Template Bitmask (750 items) 0 to 65535 F001 B-68 G30 Generator Protection System GE Multilin...
  • Page 549: Data Formats

    F052 0 = Disabled, 1 = Enabled UR_UINT32 TIME in SR format (alternate format for F050) First 16 bits are Hours/Minutes (HH:MM:xx.xxx). Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm; Minutes: 0 to 59 in steps of 1 GE Multilin G30 Generator Protection System B-69...
  • Page 550 19.00 F113 0.84 2.70 5.70 19.50 ENUMERATION: PARITY 0.86 2.80 5.80 20.00 0 = None, 1 = Odd, 2 = Even F122 ENUMERATION: ELEMENT INPUT SIGNAL TYPE 0 = Phasor, 1 = RMS B-70 G30 Generator Protection System GE Multilin...
  • Page 551 Split Phase Protection FlexElement 11 SRC1 VT Fuse Failure FlexElement 12 SRC2 VT Fuse Failure FlexElement 13 SRC3 VT Fuse Failure FlexElement 14 SRC4 VT Fuse Failure FlexElement 15 SRC1 50DD (Disturbance Detection) FlexElement 16 GE Multilin G30 Generator Protection System B-71...
  • Page 552 RTD Input 19 Digital Element 21 RTD Input 20 Digital Element 22 RTD Input 21 Digital Element 23 RTD Input 22 Digital Element 24 RTD Input 23 Digital Element 25 RTD Input 24 B-72 G30 Generator Protection System GE Multilin...
  • Page 553 0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles Disconnect switch 8 3 = 3 x 64 cycles, 4 = 1 x 128 cycles Disconnect switch 9 GE Multilin G30 Generator Protection System B-73...
  • Page 554 SRAM Data Error Relay Out Of Service Program Memory Watchdog Reset Watchdog Error Oscillography Clear Low On Memory Reboot Command Prototype Firmware LED Test Initiated Module Failure 01 Flash Programming Module Failure 02 B-74 G30 Generator Protection System GE Multilin...
  • Page 555 Dataset Item 3 UserSt-1 ↓ ↓ UserSt-2 Dataset Item 32 F157 ENUMERATION: BREAKER MODE 0 = 3-Pole, 1 = 1-Pole F160 ENUMERATION: TRANSFORMER PHASE COMPENSATION 0 = Internal (software), 1 = External (with CTs) GE Multilin G30 Generator Protection System B-75...
  • Page 556 0 = Neg Sequence, 1 = Zero Sequence F172 F183 ENUMERATION: SLOT LETTERS ENUMERATION: AC INPUT WAVEFORMS Bitmask Slot Bitmask Slot Bitmask Slot Bitmask Slot Bitmask Definition 8 samples/cycle 16 samples/cycle 32 samples/cycle 64 samples/cycle B-76 G30 Generator Protection System GE Multilin...
  • Page 557 User-programmable key 10 TEXT6: 6-CHARACTER ASCII TEXT Value Up User-programmable key 11 Value Down User-programmable key 12 F207 Message Up User 4 (control pushbutton) TEXT4: 4-CHARACTER ASCII TEXT Message Down User 5 (control pushbutton) GE Multilin G30 Generator Protection System B-77...
  • Page 558 IEC 61850 Tx dataset item MMXU2.MX.PPV.phsBC.cVal.mag.f None MMXU2.MX.PPV.phsBC.cVal.ang.f GGIO1.ST.Ind1.q MMXU2.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind1.stVal MMXU2.MX.PPV.phsCA.cVal.ang.f GGIO1.ST.Ind2.q MMXU2.MX.PhV.phsA.cVal.mag.f GGIO1.ST.Ind2.stVal MMXU2.MX.PhV.phsA.cVal.ang.f ↓ ↓ MMXU2.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind128.q MMXU2.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind128.stVal MMXU2.MX.PhV.phsC.cVal.mag.f MMXU1.MX.TotW.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU1.MX.TotVAr.mag.f MMXU2.MX.A.phsA.cVal.mag.f MMXU1.MX.TotVA.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU1.MX.TotPF.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU1.MX.Hz.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU1.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.A.phsC.cVal.mag.f B-78 G30 Generator Protection System GE Multilin...
  • Page 559 MMXU5.MX.TotW.mag.f MMXU3.MX.A.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f MMXU3.MX.A.neut.cVal.mag.f MMXU5.MX.TotVA.mag.f MMXU3.MX.A.neut.cVal.ang.f MMXU5.MX.TotPF.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU3.MX.W.phsB.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.VA.phsA.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f GE Multilin G30 Generator Protection System B-79...
  • Page 560 GGIO5.ST.UIntIn1.q MMXU6.MX.A.phsA.cVal.mag.f GGIO5.ST.UIntIn1.stVal MMXU6.MX.A.phsA.cVal.ang.f GGIO5.ST.UIntIn2.q MMXU6.MX.A.phsB.cVal.mag.f GGIO5.ST.UIntIn2.stVal MMXU6.MX.A.phsB.cVal.ang.f GGIO5.ST.UIntIn3.q MMXU6.MX.A.phsC.cVal.mag.f GGIO5.ST.UIntIn3.stVal MMXU6.MX.A.phsC.cVal.ang.f GGIO5.ST.UIntIn4.q MMXU6.MX.A.neut.cVal.mag.f GGIO5.ST.UIntIn4.stVal MMXU6.MX.A.neut.cVal.ang.f GGIO5.ST.UIntIn5.q MMXU6.MX.W.phsA.cVal.mag.f GGIO5.ST.UIntIn5.stVal MMXU6.MX.W.phsB.cVal.mag.f GGIO5.ST.UIntIn6.q MMXU6.MX.W.phsC.cVal.mag.f GGIO5.ST.UIntIn6.stVal MMXU6.MX.VAr.phsA.cVal.mag.f GGIO5.ST.UIntIn7.q MMXU6.MX.VAr.phsB.cVal.mag.f GGIO5.ST.UIntIn7.stVal MMXU6.MX.VAr.phsC.cVal.mag.f GGIO5.ST.UIntIn8.q MMXU6.MX.VA.phsA.cVal.mag.f GGIO5.ST.UIntIn8.stVal MMXU6.MX.VA.phsB.cVal.mag.f GGIO5.ST.UIntIn9.q B-80 G30 Generator Protection System GE Multilin...
  • Page 561 GGIO3.ST.UIntIn8.stVal GGIO3.MX.AnIn5.mag.f GGIO3.ST.UIntIn9.q GGIO3.MX.AnIn6.mag.f GGIO3.ST.UIntIn9.stVal GGIO3.MX.AnIn7.mag.f GGIO3.ST.UIntIn10.q GGIO3.MX.AnIn8.mag.f GGIO3.ST.UIntIn10.stVal GGIO3.MX.AnIn9.mag.f GGIO3.ST.UIntIn11.q GGIO3.MX.AnIn10.mag.f GGIO3.ST.UIntIn11.stVal GGIO3.MX.AnIn11.mag.f GGIO3.ST.UIntIn12.q GGIO3.MX.AnIn12.mag.f GGIO3.ST.UIntIn12.stVal GGIO3.MX.AnIn13.mag.f GGIO3.ST.UIntIn13.q GGIO3.MX.AnIn14.mag.f GGIO3.ST.UIntIn13.stVal GGIO3.MX.AnIn15.mag.f GGIO3.ST.UIntIn14.q GGIO3.MX.AnIn16.mag.f GGIO3.ST.UIntIn14.stVal GGIO3.MX.AnIn17.mag.f GGIO3.ST.UIntIn15.q GGIO3.MX.AnIn18.mag.f GGIO3.ST.UIntIn15.stVal GGIO3.MX.AnIn19.mag.f GGIO3.ST.UIntIn16.q GGIO3.MX.AnIn20.mag.f GGIO3.ST.UIntIn16.stVal GE Multilin G30 Generator Protection System B-81...
  • Page 562 4 = FlexCurve A, 5 = FlexCurve B, 6 = FlexCurve C, U7/AC1..3 7 = FlexCurve D U7/AC5..7 U8/AC1..3 F243 U8/AC5..7 ENUMERATION: FIELD UNIT TYPE 0 = CC-05, 1 = CV-05, 2 = CC-01, 3 = CV-01 B-82 G30 Generator Protection System GE Multilin...
  • Page 563 ENUMERATION: BRICK RTD TYPE [50] ASSIGN VIRTUAL OUTPUT (1 to 64) 0 = 100 Ohm Nickel, 1 = 120 Ohm Nickel, 2 = 100 Ohm Platinum [52] ONE SHOT [54] SELF-TEST ERROR (see F141 for range) GE Multilin G30 Generator Protection System B-83...
  • Page 564 LED and bit 7 the bottom LED. A bit value of 1 indicates ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION the LED is on, 0 indicates the LED is off. 0 = Off, 1 = On Bitmask Default variation B-84 G30 Generator Protection System GE Multilin...
  • Page 565 (basically all metering quantities used in protection). None PDIF1.ST.Str.general PDIF1.ST.Op.general F601 PDIF2.ST.Str.general ENUMERATION: COM2 PORT USAGE PDIF2.ST.Op.general Enumeration COM2 port usage PDIF3.ST.Str.general RS485 PDIF3.ST.Op.general RRTD PDIF4.ST.Str.general GPM-F PDIF4.ST.Op.general RRTD and GPM-F PDIS1.ST.Str.general PDIS1.ST.Op.general PDIS2.ST.Str.general PDIS2.ST.Op.general GE Multilin G30 Generator Protection System B-85...
  • Page 566 PIOC37.ST.Op.general PIOC11.ST.Op.general PIOC38.ST.Str.general PIOC12.ST.Str.general PIOC38.ST.Op.general PIOC12.ST.Op.general PIOC39.ST.Str.general PIOC13.ST.Str.general PIOC39.ST.Op.general PIOC13.ST.Op.general PIOC40.ST.Str.general PIOC14.ST.Str.general PIOC40.ST.Op.general PIOC14.ST.Op.general PIOC41.ST.Str.general PIOC15.ST.Str.general PIOC41.ST.Op.general PIOC15.ST.Op.general PIOC42.ST.Str.general PIOC16.ST.Str.general PIOC42.ST.Op.general PIOC16.ST.Op.general PIOC43.ST.Str.general PIOC17.ST.Str.general PIOC43.ST.Op.general PIOC17.ST.Op.general PIOC44.ST.Str.general PIOC18.ST.Str.general PIOC44.ST.Op.general PIOC18.ST.Op.general PIOC45.ST.Str.general PIOC19.ST.Str.general PIOC45.ST.Op.general B-86 G30 Generator Protection System GE Multilin...
  • Page 567 PTOC18.ST.Op.general PIOC64.ST.Op.general PTOC19.ST.Str.general PIOC65.ST.Str.general PTOC19.ST.Op.general PIOC65.ST.Op.general PTOC20.ST.Str.general PIOC66.ST.Str.general PTOC20.ST.Op.general PIOC66.ST.Op.general PTOC21.ST.Str.general PIOC67.ST.Str.general PTOC21.ST.Op.general PIOC67.ST.Op.general PTOC22.ST.Str.general PIOC68.ST.Str.general PTOC22.ST.Op.general PIOC68.ST.Op.general PTOC23.ST.Str.general PIOC69.ST.Str.general PTOC23.ST.Op.general PIOC69.ST.Op.general PTOC24.ST.Str.general PIOC70.ST.Str.general PTOC24.ST.Op.general PIOC70.ST.Op.general PTOV1.ST.Str.general PIOC71.ST.Str.general PTOV1.ST.Op.general PIOC71.ST.Op.general PTOV2.ST.Str.general PIOC72.ST.Str.general PTOV2.ST.Op.general GE Multilin G30 Generator Protection System B-87...
  • Page 568 RBRF18.ST.OpIn.general PTUV5.ST.Op.general RBRF19.ST.OpEx.general PTUV6.ST.Str.general RBRF19.ST.OpIn.general PTUV6.ST.Op.general RBRF20.ST.OpEx.general PTUV7.ST.Str.general RBRF20.ST.OpIn.general PTUV7.ST.Op.general RBRF21.ST.OpEx.general PTUV8.ST.Str.general RBRF21.ST.OpIn.general PTUV8.ST.Op.general RBRF22.ST.OpEx.general PTUV9.ST.Str.general RBRF22.ST.OpIn.general PTUV9.ST.Op.general RBRF23.ST.OpEx.general PTUV10.ST.Str.general RBRF23.ST.OpIn.general PTUV10.ST.Op.general RBRF24.ST.OpEx.general PTUV11.ST.Str.general RBRF24.ST.OpIn.general PTUV11.ST.Op.general RFLO1.MX.FltDiskm.mag.f PTUV12.ST.Str.general RFLO2.MX.FltDiskm.mag.f PTUV12.ST.Op.general RFLO3.MX.FltDiskm.mag.f PTUV13.ST.Str.general RFLO4.MX.FltDiskm.mag.f B-88 G30 Generator Protection System GE Multilin...
  • Page 569 GGIO1.ST.Ind14.stVal CSWI11.ST.Pos.stVal GGIO1.ST.Ind15.stVal CSWI12.ST.Loc.stVal GGIO1.ST.Ind16.stVal CSWI12.ST.Pos.stVal GGIO1.ST.Ind17.stVal CSWI13.ST.Loc.stVal GGIO1.ST.Ind18.stVal CSWI13.ST.Pos.stVal GGIO1.ST.Ind19.stVal CSWI14.ST.Loc.stVal GGIO1.ST.Ind20.stVal CSWI14.ST.Pos.stVal GGIO1.ST.Ind21.stVal CSWI15.ST.Loc.stVal GGIO1.ST.Ind22.stVal CSWI15.ST.Pos.stVal GGIO1.ST.Ind23.stVal CSWI16.ST.Loc.stVal GGIO1.ST.Ind24.stVal CSWI16.ST.Pos.stVal GGIO1.ST.Ind25.stVal CSWI17.ST.Loc.stVal GGIO1.ST.Ind26.stVal CSWI17.ST.Pos.stVal GGIO1.ST.Ind27.stVal CSWI18.ST.Loc.stVal GGIO1.ST.Ind28.stVal CSWI18.ST.Pos.stVal GGIO1.ST.Ind29.stVal CSWI19.ST.Loc.stVal GGIO1.ST.Ind30.stVal GE Multilin G30 Generator Protection System B-89...
  • Page 570 GGIO1.ST.Ind120.stVal GGIO1.ST.Ind68.stVal GGIO1.ST.Ind121.stVal GGIO1.ST.Ind69.stVal GGIO1.ST.Ind122.stVal GGIO1.ST.Ind70.stVal GGIO1.ST.Ind123.stVal GGIO1.ST.Ind71.stVal GGIO1.ST.Ind124.stVal GGIO1.ST.Ind72.stVal GGIO1.ST.Ind125.stVal GGIO1.ST.Ind73.stVal GGIO1.ST.Ind126.stVal GGIO1.ST.Ind74.stVal GGIO1.ST.Ind127.stVal GGIO1.ST.Ind75.stVal GGIO1.ST.Ind128.stVal GGIO1.ST.Ind76.stVal MMXU1.MX.TotW.mag.f GGIO1.ST.Ind77.stVal MMXU1.MX.TotVAr.mag.f GGIO1.ST.Ind78.stVal MMXU1.MX.TotVA.mag.f GGIO1.ST.Ind79.stVal MMXU1.MX.TotPF.mag.f GGIO1.ST.Ind80.stVal MMXU1.MX.Hz.mag.f GGIO1.ST.Ind81.stVal MMXU1.MX.PPV.phsAB.cVal.mag.f GGIO1.ST.Ind82.stVal MMXU1.MX.PPV.phsAB.cVal.ang.f GGIO1.ST.Ind83.stVal MMXU1.MX.PPV.phsBC.cVal.mag.f B-90 G30 Generator Protection System GE Multilin...
  • Page 571 MMXU3.MX.A.neut.cVal.mag.f MMXU2.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.A.neut.cVal.ang.f MMXU2.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU2.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.W.phsB.cVal.mag.f MMXU2.MX.PhV.phsA.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU2.MX.PhV.phsA.cVal.ang.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU2.MX.PhV.phsB.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f MMXU2.MX.PhV.phsB.cVal.ang.f MMXU3.MX.VAr.phsC.cVal.mag.f MMXU2.MX.PhV.phsC.cVal.mag.f MMXU3.MX.VA.phsA.cVal.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU2.MX.A.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU2.MX.A.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU2.MX.A.phsC.cVal.ang.f MMXU4.MX.TotVAr.mag.f MMXU2.MX.A.neut.cVal.mag.f MMXU4.MX.TotVA.mag.f GE Multilin G30 Generator Protection System B-91...
  • Page 572 MMXU6.MX.A.phsA.cVal.ang.f MMXU5.MX.TotPF.mag.f MMXU6.MX.A.phsB.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU6.MX.A.phsB.cVal.ang.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU6.MX.A.phsC.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU6.MX.A.phsC.cVal.ang.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU6.MX.A.neut.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU6.MX.A.neut.cVal.ang.f MMXU5.MX.PPV.phsCA.cVal.mag.f MMXU6.MX.W.phsA.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU6.MX.W.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU6.MX.W.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU6.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU6.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU6.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU6.MX.VA.phsA.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f MMXU6.MX.VA.phsB.cVal.mag.f MMXU5.MX.A.phsA.cVal.mag.f MMXU6.MX.VA.phsC.cVal.mag.f MMXU5.MX.A.phsA.cVal.ang.f MMXU6.MX.PF.phsA.cVal.mag.f B-92 G30 Generator Protection System GE Multilin...
  • Page 573 XCBR1.ST.Pos.stVal GGIO4.MX.AnIn30.mag.f XCBR2.ST.Loc.stVal GGIO4.MX.AnIn31.mag.f XCBR2.ST.Pos.stVal GGIO4.MX.AnIn32.mag.f XCBR3.ST.Loc.stVal XSWI1.ST.Loc.stVal XCBR3.ST.Pos.stVal XSWI1.ST.Pos.stVal XCBR4.ST.Loc.stVal XSWI2.ST.Loc.stVal XCBR4.ST.Pos.stVal XSWI2.ST.Pos.stVal XCBR5.ST.Loc.stVal XSWI3.ST.Loc.stVal XCBR5.ST.Pos.stVal XSWI3.ST.Pos.stVal XCBR6.ST.Loc.stVal XSWI4.ST.Loc.stVal XCBR6.ST.Pos.stVal XSWI4.ST.Pos.stVal XSWI5.ST.Loc.stVal XSWI5.ST.Pos.stVal XSWI6.ST.Loc.stVal XSWI6.ST.Pos.stVal XSWI7.ST.Loc.stVal XSWI7.ST.Pos.stVal XSWI8.ST.Loc.stVal XSWI8.ST.Pos.stVal XSWI9.ST.Loc.stVal XSWI9.ST.Pos.stVal XSWI10.ST.Loc.stVal GE Multilin G30 Generator Protection System B-93...
  • Page 574 GGIO1.ST.Ind43.q GGIO1.ST.Ind17.q GGIO1.ST.Ind43.stVal GGIO1.ST.Ind17.stVal GGIO1.ST.Ind44.q GGIO1.ST.Ind18.q GGIO1.ST.Ind44.stVal GGIO1.ST.Ind18.stVal GGIO1.ST.Ind45.q GGIO1.ST.Ind19.q GGIO1.ST.Ind45.stVal GGIO1.ST.Ind19.stVal GGIO1.ST.Ind46.q GGIO1.ST.Ind20.q GGIO1.ST.Ind46.stVal GGIO1.ST.Ind20.stVal GGIO1.ST.Ind47.q GGIO1.ST.Ind21.q GGIO1.ST.Ind47.stVal GGIO1.ST.Ind21.stVal GGIO1.ST.Ind48.q GGIO1.ST.Ind22.q GGIO1.ST.Ind48.stVal GGIO1.ST.Ind22.stVal GGIO1.ST.Ind49.q GGIO1.ST.Ind23.q GGIO1.ST.Ind49.stVal GGIO1.ST.Ind23.stVal GGIO1.ST.Ind50.q GGIO1.ST.Ind24.q GGIO1.ST.Ind50.stVal GGIO1.ST.Ind24.stVal GGIO1.ST.Ind51.q B-94 G30 Generator Protection System GE Multilin...
  • Page 575 GGIO1.ST.Ind96.q GGIO1.ST.Ind70.q GGIO1.ST.Ind96.stVal GGIO1.ST.Ind70.stVal GGIO1.ST.Ind97.q GGIO1.ST.Ind71.q GGIO1.ST.Ind97.stVal GGIO1.ST.Ind71.stVal GGIO1.ST.Ind98.q GGIO1.ST.Ind72.q GGIO1.ST.Ind98.stVal GGIO1.ST.Ind72.stVal GGIO1.ST.Ind99.q GGIO1.ST.Ind73.q GGIO1.ST.Ind99.stVal GGIO1.ST.Ind73.stVal GGIO1.ST.Ind100.q GGIO1.ST.Ind74.q GGIO1.ST.Ind100.stVal GGIO1.ST.Ind74.stVal GGIO1.ST.Ind101.q GGIO1.ST.Ind75.q GGIO1.ST.Ind101.stVal GGIO1.ST.Ind75.stVal GGIO1.ST.Ind102.q GGIO1.ST.Ind76.q GGIO1.ST.Ind102.stVal GGIO1.ST.Ind76.stVal GGIO1.ST.Ind103.q GGIO1.ST.Ind77.q GGIO1.ST.Ind103.stVal GGIO1.ST.Ind77.stVal GGIO1.ST.Ind104.q GE Multilin G30 Generator Protection System B-95...
  • Page 576 MMXU2.MX.TotPF.mag.f GGIO1.ST.Ind123.q MMXU2.MX.Hz.mag.f GGIO1.ST.Ind123.stVal MMXU2.MX.PPV.phsAB.cVal.mag.f GGIO1.ST.Ind124.q MMXU2.MX.PPV.phsAB.cVal.ang.f GGIO1.ST.Ind124.stVal MMXU2.MX.PPV.phsBC.cVal.mag.f GGIO1.ST.Ind125.q MMXU2.MX.PPV.phsBC.cVal.ang.f GGIO1.ST.Ind125.stVal MMXU2.MX.PPV.phsCA.cVal.mag.f GGIO1.ST.Ind126.q MMXU2.MX.PPV.phsCA.cVal.ang.f GGIO1.ST.Ind126.stVal MMXU2.MX.PhV.phsA.cVal.mag.f GGIO1.ST.Ind127.q MMXU2.MX.PhV.phsA.cVal.ang.f GGIO1.ST.Ind127.stVal MMXU2.MX.PhV.phsB.cVal.mag.f GGIO1.ST.Ind128.q MMXU2.MX.PhV.phsB.cVal.ang.f GGIO1.ST.Ind128.stVal MMXU2.MX.PhV.phsC.cVal.mag.f MMXU1.MX.TotW.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU1.MX.TotVAr.mag.f MMXU2.MX.A.phsA.cVal.mag.f MMXU1.MX.TotVA.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU1.MX.TotPF.mag.f MMXU2.MX.A.phsB.cVal.mag.f B-96 G30 Generator Protection System GE Multilin...
  • Page 577 MMXU4.MX.PF.phsB.cVal.mag.f MMXU3.MX.A.phsB.cVal.ang.f MMXU4.MX.PF.phsC.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU3.MX.A.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f MMXU3.MX.A.neut.cVal.mag.f MMXU5.MX.TotVA.mag.f MMXU3.MX.A.neut.cVal.ang.f MMXU5.MX.TotPF.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU3.MX.W.phsB.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.VAr.phsC.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.VA.phsA.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f GE Multilin G30 Generator Protection System B-97...
  • Page 578 GGIO4.MX.AnIn31.mag.f MMXU6.MX.PhV.phsC.cVal.mag.f GGIO4.MX.AnIn32.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f GGIO5.ST.UIntIn1.q MMXU6.MX.A.phsA.cVal.mag.f GGIO5.ST.UIntIn1.stVal MMXU6.MX.A.phsA.cVal.ang.f GGIO5.ST.UIntIn2.q MMXU6.MX.A.phsB.cVal.mag.f GGIO5.ST.UIntIn2.stVal MMXU6.MX.A.phsB.cVal.ang.f GGIO5.ST.UIntIn3.q MMXU6.MX.A.phsC.cVal.mag.f GGIO5.ST.UIntIn3.stVal MMXU6.MX.A.phsC.cVal.ang.f GGIO5.ST.UIntIn4.q MMXU6.MX.A.neut.cVal.mag.f GGIO5.ST.UIntIn4.stVal MMXU6.MX.A.neut.cVal.ang.f GGIO5.ST.UIntIn5.q MMXU6.MX.W.phsA.cVal.mag.f GGIO5.ST.UIntIn5.stVal MMXU6.MX.W.phsB.cVal.mag.f GGIO5.ST.UIntIn6.q MMXU6.MX.W.phsC.cVal.mag.f GGIO5.ST.UIntIn6.stVal MMXU6.MX.VAr.phsA.cVal.mag.f GGIO5.ST.UIntIn7.q MMXU6.MX.VAr.phsB.cVal.mag.f GGIO5.ST.UIntIn7.stVal MMXU6.MX.VAr.phsC.cVal.mag.f GGIO5.ST.UIntIn8.q B-98 G30 Generator Protection System GE Multilin...
  • Page 579 PIOC23.ST.Str.general PDIS7.ST.Str.general PIOC23.ST.Op.general PDIS7.ST.Op.general PIOC24.ST.Str.general PDIS8.ST.Str.general PIOC24.ST.Op.general PDIS8.ST.Op.general PIOC25.ST.Str.general PDIS9.ST.Str.general PIOC25.ST.Op.general PDIS9.ST.Op.general PIOC26.ST.Str.general PDIS10.ST.Str.general PIOC26.ST.Op.general PDIS10.ST.Op.general PIOC27.ST.Str.general PIOC1.ST.Str.general PIOC27.ST.Op.general PIOC1.ST.Op.general PIOC28.ST.Str.general PIOC2.ST.Str.general PIOC28.ST.Op.general PIOC2.ST.Op.general PIOC29.ST.Str.general PIOC3.ST.Str.general PIOC29.ST.Op.general PIOC3.ST.Op.general PIOC30.ST.Str.general PIOC4.ST.Str.general PIOC30.ST.Op.general PIOC4.ST.Op.general PIOC31.ST.Str.general GE Multilin G30 Generator Protection System B-99...
  • Page 580 PTOC4.ST.Str.general PIOC50.ST.Str.general PTOC4.ST.Op.general PIOC50.ST.Op.general PTOC5.ST.Str.general PIOC51.ST.Str.general PTOC5.ST.Op.general PIOC51.ST.Op.general PTOC6.ST.Str.general PIOC52.ST.Str.general PTOC6.ST.Op.general PIOC52.ST.Op.general PTOC7.ST.Str.general PIOC53.ST.Str.general PTOC7.ST.Op.general PIOC53.ST.Op.general PTOC8.ST.Str.general PIOC54.ST.Str.general PTOC8.ST.Op.general PIOC54.ST.Op.general PTOC9.ST.Str.general PIOC55.ST.Str.general PTOC9.ST.Op.general PIOC55.ST.Op.general PTOC10.ST.Str.general PIOC56.ST.Str.general PTOC10.ST.Op.general PIOC56.ST.Op.general PTOC11.ST.Str.general PIOC57.ST.Str.general PTOC11.ST.Op.general PIOC57.ST.Op.general PTOC12.ST.Str.general B-100 G30 Generator Protection System GE Multilin...
  • Page 581 RBRF4.ST.OpEx.general PTOV7.ST.Str.general RBRF4.ST.OpIn.general PTOV7.ST.Op.general RBRF5.ST.OpEx.general PTOV8.ST.Str.general RBRF5.ST.OpIn.general PTOV8.ST.Op.general RBRF6.ST.OpEx.general PTOV9.ST.Str.general RBRF6.ST.OpIn.general PTOV9.ST.Op.general RBRF7.ST.OpEx.general PTOV10.ST.Str.general RBRF7.ST.OpIn.general PTOV10.ST.Op.general RBRF8.ST.OpEx.general PTRC1.ST.Tr.general RBRF8.ST.OpIn.general PTRC1.ST.Op.general RBRF9.ST.OpEx.general PTRC2.ST.Tr.general RBRF9.ST.OpIn.general PTRC2.ST.Op.general RBRF10.ST.OpEx.general PTRC3.ST.Tr.general RBRF10.ST.OpIn.general PTRC3.ST.Op.general RBRF11.ST.OpEx.general PTRC4.ST.Tr.general RBRF11.ST.OpIn.general PTRC4.ST.Op.general RBRF12.ST.OpEx.general GE Multilin G30 Generator Protection System B-101...
  • Page 582 CSWI23.ST.Loc.stVal RREC3.ST.Op.general CSWI23.ST.Pos.stVal RREC3.ST.AutoRecSt.stVal CSWI24.ST.Loc.stVal RREC4.ST.Op.general CSWI24.ST.Pos.stVal RREC4.ST.AutoRecSt.stVal CSWI25.ST.Loc.stVal RREC5.ST.Op.general CSWI25.ST.Pos.stVal RREC5.ST.AutoRecSt.stVal CSWI26.ST.Loc.stVal RREC6.ST.Op.general CSWI26.ST.Pos.stVal RREC6.ST.AutoRecSt.stVal CSWI27.ST.Loc.stVal CSWI1.ST.Loc.stVal CSWI27.ST.Pos.stVal CSWI1.ST.Pos.stVal CSWI28.ST.Loc.stVal CSWI2.ST.Loc.stVal CSWI28.ST.Pos.stVal CSWI2.ST.Pos.stVal CSWI29.ST.Loc.stVal CSWI3.ST.Loc.stVal CSWI29.ST.Pos.stVal CSWI3.ST.Pos.stVal CSWI30.ST.Loc.stVal CSWI4.ST.Loc.stVal CSWI30.ST.Pos.stVal CSWI4.ST.Pos.stVal XSWI1.ST.Loc.stVal B-102 G30 Generator Protection System GE Multilin...
  • Page 583 XSWI19.ST.Pos.stVal Administrator XSWI20.ST.Loc.stVal Supervisor XSWI20.ST.Pos.stVal Engineer XSWI21.ST.Loc.stVal Operator XSWI21.ST.Pos.stVal XSWI22.ST.Loc.stVal XSWI22.ST.Pos.stVal F621 XSWI23.ST.Loc.stVal ENUMERATION: MODBUS LOGIN ROLES XSWI23.ST.Pos.stVal Enumeration Role XSWI24.ST.Loc.stVal None XSWI24.ST.Pos.stVal Administrator XCBR1.ST.Loc.stVal Supervisor XCBR1.ST.Pos.stVal Engineer XCBR2.ST.Loc.stVal Operator 1000 XCBR2.ST.Pos.stVal Observer GE Multilin G30 Generator Protection System B-103...
  • Page 584 ENUMERATION: NETWORK PORT FOR REMOTE DEVICE SOURCE ACTUALS Enumeration Item Enumeration Item None None Network Port 1 Port 1 PTP Clock Network Port 2 Port 2 PTP Clock Network Port 3 Port 3 PTP Clock IRIG-B SNTP B-104 G30 Generator Protection System GE Multilin...
  • Page 585: Iec 61850

    LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract ser- vices in IEC 61850-8-1. The G30 relay supports IEC 61850 server services over TCP/IP. The TCP/IP profile requires the G30 to have an IP address to establish communications. These addresses are located in the ...
  • Page 586: File Transfer By Iec 61850

    APPENDIX C C.1.3 FILE TRANSFER BY IEC 61850 The G30 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as an example. In the AX-S4 61850 Explorer window, click the Tools menu and access the SISCO File Transfer Utility.
  • Page 587: Server Data Organization

    C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the G30 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.
  • Page 588: Mmxu: Analog Measured Values

    C.2.6 MMXU: ANALOG MEASURED VALUES A limited number of measured analog values are available through the MMXU logical nodes. Each MMXU logical node provides data from a G30 current and voltage source. There is one MMXU available for each configurable source (programmed in the ...
  • Page 589 The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the G30 protection elements, these flags take their values from the pickup and operate FlexLogic operands for the corresponding element.
  • Page 590: Server Features And Configuration

    C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the G30. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the settings.
  • Page 591: Logical Node Name Prefixes

    A built-in TCP/IP connection timeout of two minutes is employed by the G30 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the G30. This frees up the con- nection to be used by other clients.
  • Page 592: Generic Substation Event Services: Gsse And Goose

    MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the G30 will use the source Ether- net MAC address as the destination, with the multicast bit set.
  • Page 593 The G30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 594 REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic equations or other settings. The G30 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
  • Page 595: Ethernet Mac Address For Gsse/Goose

    GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the G30 is configured to use an automated multicast MAC scheme. If the G30 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.
  • Page 596: Iec 61850 Implementation Via Enervista Ur Setup

    An ICD file is generated for the G30 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 597: Configuring Iec 61850 Settings

    Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the G30 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.
  • Page 598: About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
  • Page 599 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. GE Multilin G30 Generator Protection System C-15...
  • Page 600 RptEnabled Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure C–4: ICD FILE STRUCTURE, IED NODE C-16 G30 Generator Protection System GE Multilin...
  • Page 601 BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure C–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE GE Multilin G30 Generator Protection System C-17...
  • Page 602: Creating An Icd File With Enervista Ur Setup

    The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline G30 settings file is typically much quicker than create an ICD file directly from the relay.
  • Page 603 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE GE Multilin G30 Generator Protection System C-19...
  • Page 604 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. C-20 G30 Generator Protection System GE Multilin...
  • Page 605: Importing An Scd File With Enervista Ur Setup

    Figure C–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the G30 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
  • Page 606 The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
  • Page 607: Acsi Basic Conformance Statement

    Setting group control REPORTING Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion GE Multilin G30 Generator Protection System C-23...
  • Page 608: Acsi Services Conformance Statement

    SERVER/ UR FAMILY PUBLISHER SERVER (CLAUSE 7) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 8) Associate Abort Release LOGICAL DEVICE (CLAUSE 9) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 10) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 11) GetDataValues SetDataValues GetDataDirectory GetDataDefinition C-24 G30 Generator Protection System GE Multilin...
  • Page 609 LOGGING (CLAUSE 17) LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 18, ANNEX C) GOOSE-CONTROL-BLOCK (CLAUSE 18) SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK (ANNEX C) SendGSSEMessage GetReference GetGSSEElementNumber GetGsCBValues GE Multilin G30 Generator Protection System C-25...
  • Page 610 (QueryLogByTime or QueryLogAfter) c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) NOTE c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) C-26 G30 Generator Protection System GE Multilin...
  • Page 611: C.7.1 Logical Nodes Table

    GGIO: Generic process I/O GLOG: Generic log GSAL: Generic security application I: LOGICAL NODES FOR INTERFACING AND ARCHIVING IARC: Archiving IHMI: Human machine interface ISAF: Safety alarm function ITCI: Telecontrol interface ITMI: Telemonitoring interface GE Multilin G30 Generator Protection System C-27...
  • Page 612 PRTR: Rotor protection PSCH: Protection scheme PSDE: Sensitive directional earth fault PTEF: Transient earth fault PTOC: Time overcurrent PTOF: Overfrequency PTOV: Overvoltage PTRC: Protection trip conditioning PTTR: Thermal overload PTUC: Undercurrent PTUF: Underfrequency PTUV: Undervoltage C-28 G30 Generator Protection System GE Multilin...
  • Page 613 T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TANG: Angle TAXD: Axial displacement TCTR: Current transformer TDST: Distance TFLW: Liquid flow TFRQ: Frequency TGSN: Generic sensor THUM: Humidity TLVL: Media level TMGF: Magnetic field TMVM: Movement sensor GE Multilin G30 Generator Protection System C-29...
  • Page 614 ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRES: Resistor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZSCR: Semi-conductor controlled rectifier ZSMC: Synchronous machine ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component C-30 G30 Generator Protection System GE Multilin...
  • Page 615: Iec 60870-5-104

    Balanced Transmission Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin G30 Generator Protection System...
  • Page 616  <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 G30 Generator Protection System GE Multilin...
  • Page 617  <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin G30 Generator Protection System...
  • Page 618 •Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 G30 Generator Protection System GE Multilin...
  • Page 619 <34> M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin G30 Generator Protection System...
  • Page 620 <120> F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure G30 Generator Protection System GE Multilin...
  • Page 621  Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin G30 Generator Protection System...
  • Page 622 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs G30 Generator Protection System GE Multilin...
  • Page 623: Iec 60870-5-104 Point List

    D.1.2 IEC 60870-5-104 POINT LIST The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin G30 Generator Protection System...
  • Page 624 D.1 IEC 60870-5-104 APPENDIX D D-10 G30 Generator Protection System GE Multilin...
  • Page 625: Device Profile Document

    2048 Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin G30 Generator Protection System...
  • Page 626 FlexLogic. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. G30 Generator Protection System GE Multilin...
  • Page 627  16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin G30 Generator Protection System...
  • Page 628: E.1.2 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the G30 is not restarted, but the DNP process is restarted. G30 Generator Protection System GE Multilin...
  • Page 629 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the G30 is not restarted, but the DNP process is restarted. GE Multilin G30 Generator Protection System...
  • Page 630 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the G30 is not restarted, but the DNP process is restarted. G30 Generator Protection System GE Multilin...
  • Page 631 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the G30 is not restarted, but the DNP process is restarted. GE Multilin G30 Generator Protection System...
  • Page 632: Dnp Point Lists

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 G30 Generator Protection System GE Multilin...
  • Page 633: Binary And Control Relay Output

    Virtual Input 27 Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin G30 Generator Protection System...
  • Page 634: Counters

    Events Since Last Clear A counter freeze command has no meaning for counters 8 and 9. G30 Digital Counter values are represented as 32-bit integers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values.
  • Page 635: E.2.4 Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin G30 Generator Protection System E-11...
  • Page 636 E.2 DNP POINT LISTS APPENDIX E E-12 G30 Generator Protection System GE Multilin...
  • Page 637: Change Notes

    7.0x 30 April 2013 13-0167 1601-0166-Y4 7.0x 31 August 2015 12-0025 F.1.2 CHANGES TO THE G30 MANUAL Table F–2: MAJOR UPDATES FOR G30 MANUAL REVISION Y4 (Sheet 1 of 2) PAGE PAGE CHANGE DESCRIPTION (Y3) (Y4) Update General revision throughout document...
  • Page 638 F.1 CHANGE NOTES APPENDIX F Table F–2: MAJOR UPDATES FOR G30 MANUAL REVISION Y4 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (Y3) (Y4) 5-18 5-18 Added Syslog Format section 5-26 5-26 Added Far-End Fault Indication (FEFI) section 5-112 5-112...
  • Page 639 APPENDIX F F.1 CHANGE NOTES Table F–5: MAJOR UPDATES FOR G30 MANUAL REVISION Y1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (X2) (Y1) 5-16 5-16 Delete Deleted references to COM 1 RS485 port in section 5.2.4b Serial Ports 5-16 5-16 Added section 5.2.4c Ethernet Network Topology...
  • Page 640: Abbreviations

    F ..... Field MTA....Maximum Torque Angle FAIL....Failure MTR ....Motor FD ....Fault Detector MVA ....MegaVolt-Ampere (total 3-phase) FDH....Fault Detector high-set MVA_A ... MegaVolt-Ampere (phase A) FDL ....Fault Detector low-set G30 Generator Protection System GE Multilin...
  • Page 641 ....With Option ROD ....Remote Open Detector WRT....With Respect To RST ....Reset RSTR ..... Restrained X .....Reactance RTD....Resistance Temperature Detector XDUCER..Transducer RTU....Remote Terminal Unit XFMR....Transformer RX (Rx) ..Receive, Receiver Z......Impedance, Zone GE Multilin G30 Generator Protection System...
  • Page 642: Warranty

    F.3.1 GE MULTILIN WARRANTY For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Digital Energy Terms and Conditions at https://www.gedigitalenergy.com/multilin/warranty.htm...
  • Page 643: Index

    ..............5-44 replace ................11-3 COMTRADE ..............B-7 BATTERY FAILURE ............7-7 CONDUCTED RFI ............2-22 BINARY INPUT POINTS ............. E-8 CONTACT INFORMATION ..........1-2 BINARY OUTPUT POINTS ..........E-9 BLOCK DIAGRAM .............. 1-3 GE Multilin G30 Generator Protection System...
  • Page 644 ............... 7-7 DATA FORMATS, MODBUS ..........B-69 DIRECT OUTPUTS application example ........... 5-236, 5-238 clearing counters ............. 7-2 Modbus registers ......... B-11, B-61, B-62 settings ................ 5-236 DIRECTIONAL OVERCURRENT see PHASE, GROUND, and NEUTRAL DIRECTIONAL entries G30 Generator Protection System GE Multilin...
  • Page 645 ..............5-128 EQUIPMENT MISMATCH ERROR ........7-6 FlexLogic operands ............5-113 hysteresis ..............5-128 Modbus registers ..........B-44, B-46 pickup ................. 5-128 scheme logic ............... 5-127 settings ..........5-126, 5-127, 5-130 specifications ..............2-16 GE Multilin G30 Generator Protection System...
  • Page 646 G.703 WIRE SIZE ............3-33 IED SETUP ............... 1-6 G30 ...................F-1 IEEE C37.94 COMMUNICATIONS ....3-39, 3-41, 3-45 GE TYPE IAC CURVES ..........5-141 IEEE CURVES ..............5-138 IMPORTANT CONCEPTS ..........1-5 IN SERVICE INDICATOR ...........1-18, 7-6 INCIPIENT CABLE FAULT DETECTOR Modbus registers ............
  • Page 647 Modbus registers ............B-37 NEGATIVE SEQUENCE DIRECTIONAL OVERCURRENT settings ............. 5-184, 5-185 characteristics ............. 5-164 specifications ..............2-15 FlexLogic operands ............5-114 LOST PASSWORD ............5-9 logic ................5-165 settings ............5-162, 5-165 specifications ..............2-13 GE Multilin G30 Generator Protection System...
  • Page 648 ..............2-12 via COMTRADE .............. B-7 PERMISSIVE FUNCTIONS ..........5-173 via EnerVista software ............. 4-2 PER-UNIT QUANTITY ............5-4 OUT OF SERVICE ............. 5-9 PHASE ANGLE METERING ..........6-13 PHASE COMPENSATION ..........5-93 PHASE CURRENT METERING .........6-15 G30 Generator Protection System GE Multilin...
  • Page 649 SAVING SETTING DOES NOT TAKE RELAY OUT OF SERVICE REAR TERMINAL ASSIGNMENTS ........3-7 RECLOSER CURVES .......... 5-106, 5-142 SCAN OPERATION ............1-4 RELAY ACTIVATION ............4-28 SECURITY RELAY ARCHITECTURE ..........5-110 delete files and records ..........11-7 GE Multilin G30 Generator Protection System...
  • Page 650 SOURCE FREQUENCY ............ 6-19 THERMAL OVERLOAD PROTECTION SOURCE TRANSFER SCHEMES ........5-173 Modbus registers ............B-40 SOURCES settings ................ 5-223 description............... 5-5 specifications ..............2-15 example use of .............. 5-86 metering ................ 6-15 settings ..............5-84, 5-85 viii G30 Generator Protection System GE Multilin...
  • Page 651 UNINSTALL ..............11-7 VT FUSE FAILURE UNIT NOT PROGRAMMED ........5-80, 7-6 logic ................5-222 UNPACKING THE RELAY ..........1-2 settings ............... 5-220 UNRETURNED MESSAGES ALARM ......... 5-78 VT INPUTS ............3-13, 5-6, 5-83 GE Multilin G30 Generator Protection System...
  • Page 652 WITHDRAWAL FROM OPERATION ........11-7 WARNINGS ............... 1-1 WARRANTY ...............F-6 WATT-HOURS ............2-17, 6-18 WEB SERVER PROTOCOL ..........5-44 ZERO SEQUENCE CORE BALANCE .........3-13 WEBSITE ................1-2 ZERO-SEQUENCE COMPENSATION ....... 5-93, 5-94 WINDINGS Modbus registers ............B-30 G30 Generator Protection System GE Multilin...

Table of Contents