STATUS
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, 'Cont Op 1' refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn.
For form-C contact outputs, the state is displayed as Off or On.
6.3.7 Virtual outputs
ACTUAL VALUES STATUS VIRTUAL OUTPUTS
VIRTUAL OUTPUTS
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, 'Virt Op 1' refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.
6.3.8 Autoreclose
ACTUAL VALUES STATUS AUTORECLOSE
AUTORECLOSE
The automatic reclosure shot count is shown here, where the shot count is the number of reclosures that can be
6
attempted before reclosure goes to lockout.
If the status reads "not available," try enabling and configuring the function under
AUTORECLOSE AUTORECLOSE
6.3.9 RxGOOSE status
ACTUAL VALUES STATUS RxGOOSE STATUS
RxGOOSE
STATUS
The C60 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The
All RxGOOSE Online
Input.
6-6
Cont Op xx
Off
Virt Op 1
Off
Virt Op 96
Off
AUTORECLOSE
SHOT COUNT:
. If that does not work, the feature is not supported on your device.
All RxGOOSE Online:
Yes
RxGOOSE 1 Status:
Offline
RxGOOSE 64 Status:
Offline
actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
Range: On, Off, VOff, VOn, IOn, IOff
Range: On, Off
Range: On, Off
Range: 0, 1, 2, 3, 4
0
SETTINGS CONTROL ELEMENTS
Range: Yes, No
Range: Online, Offline
Range: Online, Offline
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES