The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, 'Cont Op 1' refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn.
For form-C contact outputs, the state is displayed as Off or On.

6.3.7 Virtual outputs

ACTUAL VALUES  STATUS  VIRTUAL OUTPUTS
 VIRTUAL OUTPUTS
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, 'Virt Op 1' refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.

6.3.8 Autoreclose

ACTUAL VALUES  STATUS  AUTORECLOSE
 AUTORECLOSE
The automatic reclosure shot count is shown here, where the shot count is the number of reclosures that can be
6
attempted before reclosure goes to lockout.
If the status reads "not available," try enabling and configuring the function under
AUTORECLOSE  AUTORECLOSE

6.3.9 RxGOOSE status

ACTUAL VALUES  STATUS  RxGOOSE STATUS
 RxGOOSE
 STATUS
The C60 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The
All RxGOOSE Online
Input.
6-6
Cont Op xx
Off
Virt Op 1
Off
Virt Op 96
Off
AUTORECLOSE
SHOT COUNT:
. If that does not work, the feature is not supported on your device.
All RxGOOSE Online:
Yes
RxGOOSE 1 Status:
Offline
RxGOOSE 64 Status:
Offline
actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
Range: On, Off, VOff, VOn, IOn, IOff
Range: On, Off
Range: On, Off
Range: 0, 1, 2, 3, 4
0
SETTINGS  CONTROL ELEMENTS 
Range: Yes, No
Range: Online, Offline
Range: Online, Offline
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES