SPECIFICATIONS
TYPICAL LINK DISTANCE
Emitter, fiber type
820 nm LED,
multimode
2
1300 nm LED,
multimode
1300 nm ELED,
single mode
1300 nm Laser,
single mode
1550 nm Laser,
single mode
Typical distances listed are based on the following assumptions for system loss. As actual losses vary from one
installation to another, the distance covered by your system can vary.
CONNECTOR LOSSES (Total of both ends)
ST connector:
FIBER LOSSES
820 nm multimode:
1300 nm multimode:
1300 nm single mode:
1550 nm single mode:
Splice losses:
SYSTEM MARGIN
3 dB additional loss added to calculations to compensate for all other losses.
Compensated difference in transmitting and receiving (channel asymmetry) channel delays using GPS satellite clock: 10 ms

2.5.10 CyberSentry security

OPTIONS
Software options:

2.5.11 Graphical front panel

DISPLAY
Type:
Size:
Resolution:
Pages:
2-36
Cable type
Connector
Typical distance
type
Before
January
2012
62.5/125 μm
ST
1.65 km
50/125 μm
ST
1.65 km
62.5/125 μm
ST
4 km
50/125 μm
ST
4 km
9/125 μm
ST
11.4 km
9/125 μm
ST
64 km
9/125 μm
ST
105 km
0.7 dB (each)
3 dB/km
1 dB/km
0.35 dB/km
0.25 dB/km
one splice every 2 km at 0.05 dB loss per splice
Level 1
color graphical back-lit LCD display
7 inches (17.8 cm)
800 by 480 pixels
5 single-line diagram pages with controls, status, and metering values
up to 8 annunciator pages with total of 96 annunciator windows
1 phasor metering page for each AC Source
5 tabular metering pages with dynamic metering and status
event records page with dynamic update
product information page
settings, actual values, error messages (targets)
CHAPTER 2: PRODUCT DESCRIPTION
From
January
2012
2 km
2 km
5 km
5 km
20 km
65 km
125 km
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL