Underfrequency (Ansi 81U) - GE G30 Instruction Manual

Generator protection system 7.6x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS

5.8.5 Underfrequency (ANSI 81U)

SETTINGS  CONTROL ELEMENTS  UNDERFREQUENCY  UNDERFREQUENCY 1(6)
 UNDERFREQUENCY 1
There are six identical underfrequency elements, numbered 1 through 6.
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-152: Selector switch logic
UNDFREQ 1 FUNCTION:
Disabled
UNDERFREQ 1 BLOCK:
Off
UNDERFREQ 1 SOURCE:
SRC 1
UNDERFREQ 1 MIN
VOLT/AMP: 0.10 pu
UNDERFREQ 1 PICKUP:
59.50 Hz
UNDERFREQ 1 PICKUP
DELAY: 2.000 s
UNDERFREQ 1 RESET
DELAY : 2.000 s
UNDERFREQ 1 TARGET:
Self-reset
UNDERFREQ 1 EVENTS:
Disabled
Range: Disabled, Enabled
Range: FlexLogic operand
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.10 to 1.25 pu in steps of 0.01
Range: 20.00 to 65.00 Hz in steps of 0.01
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
CONTROL ELEMENTS
5
5-277

Advertisement

Table of Contents
loading

Table of Contents