GE G30 Instruction Manual page 167

Generator protection system 7.6x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CHAPTER 4: INTERFACES
TROUBLE — Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under Actual Values > Records. For a beta /
pre-release, this LED is always on.
TEST MODE — Indicates that the relay is in test mode. For information, see the Test Mode section in the Settings
chapter.
TRIP — Indicates that the selected FlexLogic operand serving as a trip input has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator latches; initiate the reset
command to reset the latch.
ALARM — Indicates that the FlexLogic operand serving as an alarm switch has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator never latches.
PICKUP — Indicates that an element is picked up. This indicator never latches.
The event-cause indicators in the first column are as follows.
Event-cause LEDs are below the status LEDs. They are turned on or off by protection elements that have their respective
target setting selected as either "Enabled" or "Latched." If a protection element target setting is "Enabled," then the
corresponding event-cause LEDs remain on as long as the operand associated with the element remains asserted. If a
protection element target setting is "Latched," then the corresponding event-cause LEDs turn on when the operate
operand associated with the element is asserted and remains on until the
the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
VOLTAGE — This LED indicates voltage was involved
CURRENT — This LED indicates current was involved
FREQUENCY — This LED indicates frequency was involved
OTHER — This LED indicates a composite function was involvedThis LED indicates a composite function was involved
PHASE A — This LED indicates phase A was involved
PHASE B — This LED indicates phase B was involved
PHASE C — This LED indicates phase C was involved
NEUTRAL/GROUND — This LED indicates that neutral or ground was involved
The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is user-
defined. Support for applying a customized label beside every LED is provided. Default labels are shipped in the label
package of every G30, together with custom templates. The default labels can be replaced by user-printed labels.
User customization of LED operation is of maximum benefit in installations where languages other than English are used
to communicate with operators. See the User-Programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
4.2.4.2 Standard front panel
The standard front panel consists of three panels with LED indicators, keys, and a communications port. The
used to reset any latched LED indicator or target message, once the condition has been cleared (these latched conditions
can also be reset via the
SETTINGS  INPUT/OUTPUTS  RESETTING
computer.
The
keys are used by the breaker control feature.
USER
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
FRONT PANEL INTERFACE
button on the front panel is pressed after
RESET
menu). The RS232 port is for connection to a
4
key is
RESET
4-39

Advertisement

Table of Contents
loading

Table of Contents