GE G30 Instruction Manual page 577

Generator protection system 7.6x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CHAPTER 7: COMMANDS AND TARGETS
Description of problem: The
programmed.
How often the test is performed: On power up and whenever the
setting is altered
.
What to do: Program all settings and then set
DIAGNOSTIC FAILURE___:
Self Test Error
Latched target message: No.
Description of problem: Internal recovery failure detected.
How often the test is performed: Upon recovery.
What to do: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
SYSTEM FAILURE___:
with 2nd line detail
Latched target message: Yes.
Description of problem: Relay system failure detected.
How often the test is performed: Continuous.
What to do: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
7.2.2.3 Minor self-test error messages
Most of the minor self-test errors can be disabled. See the settings in the User-programmable Self-tests section in chapter
5.
DIAGNOSTIC ALARM:
with 2nd line detail
Latched target message: Yes.
Description of problem: Transient communication failure detected.
How often the test is performed: Module dependent.
What to do: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
MAINTENANCE ALERT:
Replace Battery
Latched target message: Yes.
Description of problem: The battery is weak or not functioning. It powers the real time clock. This message displays as
Battery Fail in the event records. When the battery weakness reaches a critical level, the message displays persistently
on the front panel and no front panel key navigation is possible.
How often the test is performed: The battery is monitored every five seconds. The error message displays after 60
seconds if the problem persists
What to do: Replace the battery as outlined in the Maintenance chapter.
MAINTENANCE ALERT:
Direct I/O Ring Break
Latched target message: No.
Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring.
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
.
setting indicates the G30 is not
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
TARGETS MENU
to "Programmed."
7
7-7