SPECIFICATIONS
Carry continuous:
Break (DC inductive, L/R = 40 ms):
Voltage
Current
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
2
Operate time:
Contact material:
LATCHING RELAY
Make and carry for 0.2 s:
Carry continuous:
Break (DC resistive as per IEC61810-1):
Voltage
Current
24 V
6 A
48 V
1.6 A
125 V
0.4 A
250 V
0.2 A
Operate time:
Contact material:
Control:
Control mode:
FORM-A VOLTAGE MONITOR
Applicable voltage:
Trickle current:
FORM-A CURRENT MONITOR
Threshold current:
FORM-C AND CRITICAL FAILURE RELAY
Make and carry for 0.2 s:
Carry continuous:
Break (DC inductive, L/R = 40 ms):
Voltage
Current
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
Operate time:
Contact material:
FAST FORM-C RELAY
Make and carry:
2-32
6 A
< 4 ms
silver alloy
30 A as per ANSI C37.90
6 A as per IEEE C37.90
< 4 ms
silver alloy
separate operate and reset inputs
operate-dominant or reset-dominant
approx. 15 to 250 V DC
approx. 1 to 2.5 mA
approx. 80 to 100 mA
30 A as per ANSI C37.90
8 A
< 8 ms
silver alloy
0.1 A max. (resistive load)