Transformer - GE G30 Instruction Manual

Generator protection system 7.6x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CHAPTER 6: ACTUAL VALUES

6.4.2 Transformer

6.4.2.1 Differential and restraint currents
ACTUAL VALUES  METERING  TRANSFORMER  DIFFERENTIAL AND RESTRAINT
 DIFFERENTIAL AND
 RESTRAINT
The metered differential current, restraint current, second harmonic current, and fifth harmonic current are displayed for
each phase. See the Percent Differential section in chapter 5 for details on how these values are calculated.
If differential current in any phase is below the hard-coded cutoff of 0.04 pu, then the differential, 2nd harmonic, and 5th
harmonic currents are forced to zero.
6.4.2.2 Thermal elements
ACTUAL VALUES  METERING  TRANSFORMER  THERMAL ELEMENTS
 THERMAL
 ELEMENTS
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
REFERENCE WINDING:
Winding 1
DIFF PHASOR Iad:
0.000 pu
0.0°
REST PHASOR Iar:
0.000 pu
0.0°
DIFF 2ND HARM Iad:
0.0% fo
0.0°
DIFF 5TH HARM Iad:
0.0% fo
0.0°
DIFF PHASOR Ibd:
0.000 pu
0.0°
REST PHASOR Ibr:
0.000 pu
0.0°
DIFF 2ND HARM Ibd:
0.0% fo
0.0°
DIFF 5TH HARM Ibd:
0.0% fo
0.0°
DIFF PHASOR Icd:
0.000 pu
0.0°
REST PHASOR Icr:
0.000 pu
0.0°
DIFF 2ND HARM Icd:
0.0% fo
0.0°
DIFF 5TH HARM Icd:
0.0% fo
0.0°
TOP OIL °C:
70°C
HOTTEST-SPOT °C:
130°
AGING FACTOR:
1.2
DAILY RATE LOL:
15 hrs
XFMR LIFE LOST:
100000 hrs
METERING
6
6-17