DIRECT INPUT AND OUTPUT COMMUNICATIONS
3
3.4.4 G.703 interface
3.4.4.1 Description
G.703 is an International Telecommunications Union (ITU) standard for the transmission of data and voice signals. Modules
7R (one channel) and 7S (two channels) apply.
The following figure shows the 64K ITU G.703 co-directional interface configuration. This is module 7S.
The G.703 module is fixed at 64 kbps. The
applicable to this module.
AWG 24 twisted shielded pair wiring is recommended for external connections, with the shield grounded only at one end.
Connecting the shield to pin X1a or X6a grounds the shield since these pins are connected internally to ground. Thus, if
pin X1a or X6a is used to ground the shield at one end, do not ground the shield at the other end. This interface module is
protected by surge suppression devices.
3-40
Figure 3-42: 2I and 2J laser fiber modules
Observing any fiber transmitter output can injure the eye.
When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the
maximum optical input power to the receiver.
SETTINGS  PRODUCT SETUP  DIRECT I/O  DIRECT I/O DATA RATE
Figure 3-43: G.703 interface configuration
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
setting is not