Control Elements; Overview - GE G30 Instruction Manual

Generator protection system 7.6x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CONTROL ELEMENTS

For example, a setting of 20% for a 200 MW machine, is 0.20 × 200 MW = 40 MW. If 7.967 kV is a primary VT voltage and 10
kA is a primary CT current, the source pu quantity is 239 MVA, and thus, the pu power setting is 40 MW / 239 MVA = 0.167
pu.
3RD HARM NTRL UV MIN POWER
the measured power is above this setting but below the
operate. If the
3RD HARMONIC NTRL UV MIN POWER
less than the
3RD HARM NTRL UV MAX POWER
This setting applies to three-phase power and is entered in pu. The base quantity is three-phase power on the primary side,
which is calculated as
as 3 x Phase CT Primary x Phase VT Ratio x Phase VT Secondary in case of wye connected VTs.
If the VTs are located on the high-voltage (HV) side of the transformer, then configure the source using CTs that
are also on the HV side. Correspondingly, if the VTs are located on the low-voltage (LV) side of the transformer,
then configure the source using CTs that are also on the LV side. In both cases, the CT polarity produces a
positive power measurement when the machine is generating.
5
5.8 Control elements

5.8.1 Overview

Control elements are used for control rather than protection. See the Introduction to Elements section at the beginning of
this chapter for information.
5-266
— This setting specifies the minimum active power that inhibits this protection function. If
is set to "0.00 pu", then the element does not operate for all power values
setting.
3
x Phase CT Primary x Phase VT Ratio x Phase VT Secondary in case of delta connected VTs and
Figure 5-146: Third harmonic neutral undervoltage logic
3RD HARM NTRL UV MAX POWER
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
setting, the element does not

Advertisement

Table of Contents
loading

Table of Contents