GE G30 Instruction Manual page 579

Generator protection system 7.6x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

CHAPTER 7: COMMANDS AND TARGETS
What to do: The "xxx" text denotes the data item that has been detected as oscillating. Evaluate all logic pertaining to
this item.
MAINTENANCE ALERT:
Setting Changed
Latched target message: No.
Description of problem: Any device settings were changed over any available interface.
How often the test is performed: On any setting changes, when new settings were written to device.
What to do: Verify that the setting change was legitimate and essential for proper functioning of the protection and
control system.
MAINTENANCE ALERT:
Front Panel Trouble
Latched target message: No.
Description of problem: The graphical front panel is not communicating with the CPU module.
How often the test is performed: Every five seconds.
What to do: Open the graphical front panel and check the connection between the CPU module and the front panel, then
restart the relay in EnerVista under Commands > Relay Maintenance > Reboot Relay or by powering the relay off and on.
If trouble persists, contact the factory.
MAINTENANCE ALERT:
GFP Version Mismatch
Latched target message: No.
Description of problem: The graphical front panel firmware revision is not synchronized with that of the CPU module in
the relay.
How often the test is performed: Whenever connection is established between the graphical front panel and the CPU
module in the relay.
What to do: Perform UR firmware upgrade with the graphical front panel connected to the CPU module in the relay. It
can be done using any communication interface (Ethernet or USB). This synchronizes the graphical firmware revision
with that of the relay. If trouble persists, contact the factory.
DIRECT I/O FAILURE:
COMM Path Incomplete
Latched target message: No.
Description of problem: A direct device is configured but not connected.
How often the test is performed: Every second.
What to do: Check direct input and output configuration and wiring.
RxGOOSE FAIL:
Missing messages
Latched target message: No.
Description of problem: One or more RxGOOSE messages are not being received.
How often the test is performed: The self-test is activated when no message is received within the expected time
interval, which is the time-to-live time in the previous message. This time can be from milliseconds to minutes.
What to do: Check GOOSE setup.
TEMP MONITOR:
OVER TEMPERATURE
Latched target message: Yes.
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
TARGETS MENU
7
7-9

Advertisement

Table of Contents
loading

Table of Contents