Advertisement

CHAPTER 5: SETTINGS

5.7.9 Split phase protection (ANSI 50SP)

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  SPLIT PHASE
 SPLIT PHASE
Some generators, due to physical construction, have windings that consist of multiple adjacent turns. It is therefore
possible for faults to develop between turns on the same phase (inter-turn faults). These faults are not detected by the
stator differential protection, as there is no difference between the neutral and at-terminal currents. Split phase protection
can be applied to detect inter-turn faults when the generator is wound with two three-phase windings, each brought
separately out of the machine and connected in parallel. The currents in the two windings are compared, any difference
indicating an inter-turn fault.
The split phase element allows a separate pickup setting to be applied for each phase. Additionally, the pickup can be
biased by the load current (slope characteristic). Two modes of operation are supported (over and over-under).
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SPLIT PHASE
FUNCTION: Disabled
SPLIT PHASE SOURCE:
SRC 1
SPLIT PHASE LOAD
SOURCE: SRC 2
SPLIT PHASE A
PICKUP: 0.200 pu
SPLIT PHASE A
OFFSET: 0.000 pu
SPLIT PHASE A SLOPE:
0.0%
SPLIT PHASE B
PICKUP: 0.200 pu
SPLIT PHASE B
OFFSET: 0.000 pu
SPLIT PHASE B SLOPE:
0.0%
SPLIT PHASE C
PICKUP: 0.200 pu
SPLIT PHASE C
OFFSET: 0.000 pu
SPLIT PHASE C SLOPE:
0.0%
SPLIT PHASE MIN
LOAD: 0.00 pu
SPLIT PHASE MODE:
Over
SPLIT PHASE DELAY:
0.000 s
SPLIT PHASE BLK:
Off
SPLIT PHASE TARGET:
Self-Reset
SPLIT PHASE EVENTS:
Disabled
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.020 to 1.500 pu in steps of 0.001
Range: 0.000 to 1.000 pu in steps of 0.001
Range: 0.0 to 100% in steps of 0.1
Range: 0.020 to 1.500 pu in steps of 0.001
Range: 0.000 to 1.000 pu in steps of 0.001
Range: 0.0 to 100% in steps of 0.1
Range: 0.020 to 1.500 pu in steps of 0.001
Range: 0.000 to 1.000 pu in steps of 0.001
Range: 0.0 to 100% in steps of 0.1
Range: 0.00 to 1.00 pu in steps of 0.01
Range: Over, Over-Under
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: Self-reset, Latched
,
Disabled
Range: Enabled
,
Disabled
5
5-241