BACK UP AND RESTORE SETTINGS
To create a new settings file in the URS format in EnerVista Offline Window:
1.
In EnerVista, right-click in the Offline Window area and select New Device. A window opens.
11
2.
Change the file name at the end of the Path field, keeping the .urs extension.
3.
From the Associate File with Device drop-down list, select the UR device. Other fields complete automatically.
Otherwise, when you do not select a device from the drop-down list, all fields need to be completed manually and
only devices that match the entered order code and version display in the list.
4.
The Serial # Lock field is the serial number of the intended device. It ensures that the settings file is sent only to the
specific relay that matches the serial number.
5.
Click the OK button to create the .urs file in the Offline Window area.
To save settings in the IID format in EnerVista Online Window:
1.
In EnerVista, connect to the device in the Online Window area.
2.
Right-click the device name in the Online Window area and select Read IID File. The option is not present when the
device does not have the IEC 61850 option. A window opens when successful.
3.
Select or enter a file name and location, and click the Receive button. A .iid file is created.
To save settings in the IID format in EnerVista Offline Window:
1.
In EnerVista, right-click the device in the Offline Window area.
2.
Select the Create IID File option for firmware below 7.3. The option is not always available. Select the Save As option
for firmware 7.3 and later, and select the IID option from drop-down list.
No file is generated. The IID file on the computer is copied to the location specified.
3.
If the Do not update IID file when updating SCL files preference is enabled under File > Preferences > IEC 61850,
then a message displays to that effect. This means that there is no IID file available on the computer to be copied, so
a new one is generated.
To save settings in the IID format using TFTP:
1.
On a computer on the same subnetwork as the UR device, open a command window.
2.
Enter
TFTP <IP address> GET ur.iid <destination>
where
<IP address> is the IP address of the UR device
ur.iid is the internal name of the IID file in the UR device
<destination> is the path and file name of the IID file. If omitted, the file is saved as ur.iid in the command window
default directory.
An example is
TFTP 192.168.1.101 GET ur.iid Feeder1.iid
To save settings in the ICD format in EnerVista Online Window:
1.
In EnerVista, right-click the device in the Online Window area.
2.
Select the Read ICD File option. A window opens.
3.
Enter a path/name for the file, and click the Save button.
To save settings in the ICD format in EnerVista Offline Window:
1.
In EnerVista, right-click the device in the Offline Window area.
2.
Select the Create ICD File option. Or select the Save As option, and select the ICD option from drop-down list.
11-10