BACK UP AND RESTORE SETTINGS
11
3.
Two prompts are possible, first that the URS file does not include the complete IEC 61850 configuration and that it
needs to be recreated if you continue. This means that the URS file is from UR version 7.30 or higher, has the IEC 61850
software option in the order code, but any IEC 61850 content will be compromised and will need to be configured.
Second, a message can display that the URS file is part of a device folder and to use the device's CID file. This means
that the URS file is from UR version 7.3 or higher, has the IEC 61850 software option in the order code, and is part of the
device folder. The user is trying to add a URS file from inside a device's folder. Instead, the user needs to use the CID file
from the device folder.
These messages display because the roles of the protection engineer and network engineer can be separate. The
former can require a URS file, while the latter can require stored Modbus settings and protection schemes.
4.
Manually copy the remaining settings, outlined as follows.
To restore settings from an IID file using EnerVista software:
1.
In Windows, make a copy the IID file with a cid extension.
2.
Connect to the device in the Online Window area.
3.
In the Offline Window area, right-click Devices and select Import Devices from SCD.
11-12
Figure 11-9: Restoring a URS settings file
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 11: MAINTENANCE