GE G30 Instruction Manual page 666

Generator protection system 7.6x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

RADIUS SERVER CONFIGURATION
BEGIN-VENDOR
# Role ID
ATTRIBUTE
# GE-UR-ROLE values
VALUE GE-UR-Role
VALUE GE-UR-Role
VALUE GE-UR-Role
B
VALUE GE-UR-Role
VALUE GE-UR-Role
END-VENDOR
#############################################################
6.
In the dictionary file in the <Path_to_Radius>\etc\raddb folder, add the following line.
$INCLUDE dictionary.ge
For example, the file can look like the following:
$INCLUDE ../shareéfreeradius/dictionary
$INCLUDE dictionary.ge
7.
For the first start, run the RADIUS server in debug mode to ensure that there are no compiling errors.
<Path_to_Radius>/start_radiusd_debug.bat
8.
Set up the RADIUS parameters on the UR as follows.
8.1.
If logging in, select Device for the Authentication Type, and use Administrator for the User Name. The default
password is "ChangeMe1#".
8.2.
Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave
the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf
file. Restart the relay for the IP address and port changes to take effect.
9.
Verify operation. Log in to the UR software as follows. In the login window, select Server as the Authentication Type,
enter the user name entered (for example user name Tester and password "testpw"). Check that the RADIUS server log
file shows the access with an "Access-Accept" entry.
Recall that if you tried another third-party tool and it did not work, you can use the FreeRADIUS software from
freeradius.net.
B-2
GE
GE-UR-Role
1
Administrator
1
Supervisor
2
Engineer
3
Operator
4
Observer
5
GE
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
APPENDIX B: RADIUS SERVER CONFIGURATION
integer

Advertisement

Table of Contents
loading

Table of Contents