Advertisement

GROUPED ELEMENTS
5
The split phase element principle of operation is as follows. First, define the following parameters:
I
= split-phase current
split
I
= load current
load
pickup = pickup setting
min_load = minimum load supervision setting
Then, the expected value of the steady state unbalance (defined as bias current) is expressed as follows:
where
and offset is the split phase current at no-load. In "Over" mode, the element picks up if
5-242
Figure 5-125: Split phase protection for two CTs
Figure 5-126: Split phase protection for one CT
I
= slope x I
+ offset
bias
load
(I
- I
> pickup) and (I
split
bias
load
≥ min_load)
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Eq. 5-49
Eq. 5-50
Eq. 5-51