PRODUCT SETUP
The G30 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the G30 can connect. A maximum of two simultaneous connections are supported at any given time.
5.3.5.16 EGD protocol
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  EGD PROTOCOL
 EGD PROTOCOL
The G30 is provided with optional Ethernet Global Data (EGD) communications capability. This feature is
specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
Ethernet Global Data (EGD) is a suite of protocols used for the real-time transfer of data for display and control purposes.
The relay can be configured to 'produce' EGD data exchanges, and other devices can be configured to 'consume' EGD data
exchanges. The number of produced exchanges (up to three), the data items in each exchange (up to 50), and the
exchange production rate can be configured.
The relay supports one fast EGD exchange and two slow EGD exchanges. There are 20 data items in the fast-produced
EGD exchange and 50 data items in each slow-produced exchange.
EGD cannot be used to transfer data between UR series relays. The relay supports EGD production only. An EGD exchange
5
is not be transmitted unless the destination address is non-zero, and at least the first data item address is set to a valid
Modbus register address. The default setting value of "0" is considered invalid.
Fast exchanges (50 to 1000 ms) are generally used in control schemes. The G30 has one fast exchange (exchange 1) and
two slow exchanges (exchange 2 and 3).
The settings menu for the fast EGD exchange follows.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  EGD PROTOCOL FAST PROD EXCH 1 CONFIGURATION
 FAST PROD EXCH 1
 CONFIGURATION
The settings menu for the slow EGD exchanges follows.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  EGD PROTOCOL SLOW PROD EXCH 1(2) CONFIGURATION
 SLOW PROD EXCH 1
 CONFIGURATION
5-102
 FAST PROD EXCH 1
 CONFIGURATION
 SLOW PROD EXCH 1
 CONFIGURATION
 SLOW PROD EXCH 2
 CONFIGURATION
EXCH 1 FUNCTION:
Disable
EXCH 1 DESTINATION:
0.0.0.0
EXCH 1 DATA RATE:
1000 ms
EXCH 1 DATA ITEM 1:
0
EXCH 1 DATA ITEM 20:
0
EXCH 1 FUNCTION:
Disable
EXCH 1 DESTINATION:
0.0.0.0
EXCH 1 DATA RATE:
1000 ms
See below
See below
See below
Range: Disable, Enable
Range: standard IP address
Range: 50 to 1000 ms in steps of 1
Range: 0 to 65535 in steps of 1 (Modbus register
address range)
Range: 0 to 65535 in steps of 1 (Modbus register
address range)
Range: Disable, Enable
Range: standard IP address
Range: 50 to 1000 ms in steps of 1
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL