Install Server To Cabinet - Inspur NP5540M3 Manual

Table of Contents

Advertisement

according to the depth of the cabinet; adjust the long adjustment sheet on both sides of
the outer rail properly, and then fix it using 4 round head M4*6 screws and flat washers
(used below the screw). The fixing hole position is shown in figure 10. Figure 10 is just
for reference, the actual fixing hole position will be determined according to the depth
of the cabinet.
2. Confirm the installation position of the server on the cabinet.
3. Collocate short adjustment sheet (located in the inner side of the cabinet angle
hole position, one for front, the other for the rear) and fix the front and rear ends of the
outer rail to the cabinet angle rail hole position using 4 round head M5*8 screws, two
screws for both front and rear ends. Please make sure the front and rear part of the
outer rail horizontal, as shown in figure 11.
4. Repeat the above operations, install the long adjustment sheet to the front and
rear ends of another outer rail and install the outer rail with long adjustment sheet to the
cabinet.

9.6 Install Server to Cabinet

1. Pull the middle rail of the outer rail out fully, then lift the server close to the
cabinet and make the rear of the server face the front of the cabinet.
Chapter Nine Server Installation Guide
Figure 10
Figure 11
73