Service and Troubleshooting
August 2017
Table 6-3. Maintenance Alerts (M:)
Message
Supply Voltage Low
Electronics Temperature
Out of Limits
Level Measurement Lost
Interface Measurement
Lost
Low Signal Quality
Capacity Denied
PV Out of Limits
Non-PV Out of Limits
88
PRELIMINARY
Description
The supply voltage is low and may affect
Device Operation.
The temperature of the electronics board
has exceeded the transmitter's operating
range.
No valid Level reading. Reasons may be
multiple:
No valid surface echo peak in the
measuring range.
Incorrect transmitter configuration.
No valid Interface reading. Reasons may be
multiple:
No valid surface echo peak in the
measuring range.
Incorrect transmitter configuration.
The Signal Quality is below the defined alert
limit.
The device has failed to acquire the wireless
communication bandwidth necessary to
support the configured update rates.
The primary measurement is outside the
sensor limits and may be unreliable.
One of the non-primary measurements is
outside the associated sensor limits and
may be unreliable.
00809-0100-4308, Rev CA
Recommended actions
1. Replace the Power Module, see
replacement" on page
106.
1. Verify that ambient temperature is within the
operating range.
2. Restart the device.
3. Remote mount the transmitter head away from the
process and environmental conditions.
4. If the condition persists, replace the device.
1. Analyze the Echo Curve for reason and check device
configuration, especially thresholds, Near Zone,
Maximum Level Rate and settings on the Lost
Measurement tab in the Alert Setup.
2. Check device physical installation (for instance probe
contamination).
3. Restart level measurement.
4. Restore default settings and reconfigure the device.
5. If the condition persists, replace the device.
1. Analyze the Echo Curve for reason and check device
configuration, especially thresholds, false echoes,
Near Zone, Maximum Level Rate and settings on the
Lost Measurement tab in the Alert Setup.
2. Check device physical installation (for instance probe
contamination).
3. Restart measurement.
4. Restore the default settings and reconfigure device.
5. If the condition persists, replace the device.
1. Take action based on your intended use of this alert.
2. Clean the probe.
3. If no actions were necessary, consider to change the limit.
1. Obtaining the bandwidth may take some time
depending on the configured update rates and other
devices in the network. Wait several minutes to see if
the error resolves itself.
2. There may be too many devices attached to the
®
WirelessHART
network, or the update rates may be
too fast. Try using a different network, or slowing
down the update rate on one or more devices.
1. Bring the system to a safe state.
2. Verify that the primary measurement is within
specified limits.
3. Restart the device.
4. If the condition persists, replace the device.
1. Bring the system to a safe state.
2. Verify that all non-primary measurements are within
specified limits.
3. Restart the device.
4. If the condition persists, replace the device
Reference Manual
"Power module
Service and Troubleshooting