Parameter - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

9.5

Parameter

Set item
(s3)
Sampling time (TS)
(s3)+1
Operation setting
(ACT)
(s3)+2
Input filter constant ()
(s3)+3
Proportional gain (KP)
(s3)+4
Integral time (TI)
(s3)+5
Differential gain (KD)
(s3)+6
Differential time (TD)
(s3)+7 to
These devices are occupied for internal processing of PID operation. Do not change data.
(s3)+19
*1
(s3)+20
Input variation (incremental)
alarm set value
*1
(s3)+21
Input variation (decremental)
alarm set value
*1
(s3)+22
Output variation (incremental)
alarm set value
Output upper limit set value
*1
(s3)+23
Output variation (decremental)
alarm set value
Output lower limit set value
*1
(s3)+24
Alarm output
(s3)+25
PV value threshold
(hysteresis) width (SHPV)
(s3)+26
Output value upper limit (ULV)
(s3)+27
Output value lower limit (LLV)
(s3)+28
Wait setting from end of tuning
cycle to start of PID control
(KW)
*1 (s3)+20 to +24 become used only if b1, b2, or b5 are set to "1" to determine the action (ACT) (s3) of +1.
9 PID CONTROL FUNCTION
58
9.5 Parameter
Description/Setting range
1 to 32767 (ms)
b0
0: Forward operation
1: Backward operation
b1
0: Input variation alarm is invalid
1: Input variation alarm is valid
b2
0: Output variation alarm is invalid
1: Output variation alarm is valid
b3
Not used
b4
0: Auto-tuning is not executed.
1: Auto-tuning is executed
b5
0: Upper and lower limits of output value are not
valid
1: Upper and lower limits of output value are valid
b6
0: Step response method
1: Limit cycle method
b7 to b15
Not used
0 to 99 [%]
1 to 32767 [%]
0 to 32767 [100 ms]
0 to 100 [%]
0 to 32767 [10 ms]
0 to 32767
0 to 32767
0 to 32767
-32768 to +32767
0 to 32767
-32768 to +32767
b0
0: Input variation (incremental) is not exceeded.
1: Input variation (incremental) is exceeded.
b1
0: Input variation (decremental) is not exceeded.
1: Input variation (decremental) is exceeded.
b2
0: Output variation (incremental) is not exceeded.
1: Output variation (incremental) is exceeded.
b3
0: Output variation (decremental) is not exceeded.
1: Output variation (decremental) is exceeded.
Set it according to measured value (PV)
fluctuation.
Set maximum value (ULV) of output value (MV).
Set minimum value (LLV) of output value (MV).
-50 to +32717 [%]
Remarks
It cannot be shorter than operation cycle of the PLC.
Operation direction
Do not set b2 and b5 to ON at the same time.
Do not set b2 and b5 to ON at the same time.
Select auto-tuning mode.
When "0" is set, input filter is not provided.
When "0" is set, it is handled as "" (no integration).
When "0" is set, differential gain is not provided.
When "0" is set, differential is not executed.
It is valid when operation setting (ACT) (b1 of (s3)+1) is
"1".
It is valid when operation setting (ACT) (b1 of (s3)+1) is
"1".
It is valid when operation setting (ACT) (b2 of (s3)+1) is
"1" and (ACT) (b5 of (s3)+1) is "0".
It is valid when operation setting (ACT) (b2 of (s3)+1) is
"0" and (ACT) (b5 of (s3)+1) is "1".
It is valid when operation setting (ACT) (b2 of (s3)+1) is
"1" and (ACT) (b5 of (s3)+1) is "0".
It is valid when operation setting (ACT) (b2 of (s3)+1) is
"0" and (ACT) (b5 of (s3)+1) is "1".
It is valid when operation setting (ACT) (b1 or b2 of
(s3)+1) is "1".
The setting below is required when the limit cycle method
is used (when the operation setting (ACT) b6 is set to
ON).