Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 280

Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

No.
Name
SD113 to
Detailed information 2
SD143
APPENDIX
278
Appendix 2 Special Register List
Description
• Detailed information 2 corresponding to the error code (SD0) is
stored.
• There are four types of information to be stored as shown in the
following figures.
• The type of detailed information 2 can be obtained using SD112 (the
value of the "Detailed information 2 information category code" stored
in SD112 corresponds to the following figures (2) to (5)).
(2) Drive number and file name
b15
b0
SD113
With or without specification
SD114
Drive No.
SD115
1st character
2nd character
3rd character
File name
4th character
(first 8 characters of
Unicode character
5th character
string)
6th character
7th character
SD122
8th character
(3) Annunciator number
b15
b0
SD113
With or without specification
SD114
Annunciator No.
(4) Parameter information
SD113
With or without specification
Parameter
SD114
Parameter Type
storage destination
SD115
Module position
SD116
Parameter No.
SD117
Network No.
SD118
Station No.
SD119
SD120
SD121
SD122
SD123
System information
SD124
SD125
SD126
SD127
SD128
SD129
(5) System configuration information
b15
b8 b7
b0
b15
SD113
With or without specification
Head Y No.  8 Head X No.  8
SD114
SD115
Function No. Module position
SD116
Free (Fixed to 0) Intel l i gent module No.
SD117
Network No.
SD118
Station No.
b15
b2
b1b0
Drive No.
File name
b15
b1 b0
Annunciator No.
b15
b7
b6
b5
b4
b3
b2
b1b0
Parameter storage
destination
Parameter type
Module position
Parameter No.
Network No.
Station No.
System information
b15
b8
b7
b0
Parameter
Parameter Type
storage destination
Parameter Type
1: System parameter
2: CPU parameter
3: Module parameter
4: Module extension parameter
5: Memory card parameter
Parameter storage destination
2: SD memory card
4: Data memory
CPU module
: 0H
Extension module 1 to 16: 1H to 10H
Built-in RS-485
: 41H
Built-in analog
: 42H
Expansion board
: 60H
Expansion adapter 1 to 6: 71H to 76H
b7
b6
b5
b4
b3
b2
b1b0
Head X No.
Head Y No.
Module position
Function No.
Intelligent module No.
Free
Network No.
Station No.
Module position
CPU module
: 0H
Extension module 1 to 16 : 1H to 10H
Built-in RS-485
: 41H
Built-in analog
: 42H
Expansion board
: 60H
Expansion adapter 1 to 6: 71H to 76H
Function No.
System/Sequence operation : 0
Analog input
: 1
Analog output
: 2
Positioning, PWM
: 10
High-speed counter,
Pulse width measurement : 20
Serial communication
: 30
Either XY head No. or intelligent
module No. is set.
R/W
R

Advertisement

Table of Contents
loading

Table of Contents