Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 150

Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

High-speed counter (1-phase 1-input S/W) (internal clock) count direction switch
Device for switching counter direction when using 1-phase 1-input (S/W) counter or internal clock.
■Corresponding devices
The device numbers corresponding to each channel are as follows.
CPU module
CH1
CH2
SM4580
SM4581
High-speed pulse input/output module
First module
CH9
CH10
SM4588
SM4589
■Operation Description
The content of the operation when ON and when OFF is as follows.
Operation when ON
High-speed counter current value counted -1 when input A phase ON
• Setting is ignored for counter other than 1-phase 1-input (S/W), internal clock.
• These devices also operate when the FX3 compatible high-speed counter function is valid.
■Update timing
The timing of device update is as follows.
ON
When ON by the user (update by END processing)
Can also be modified while the high-speed counter is operating.
High-speed counter preset input logic
These devices are used for setting the preset input logic.
■Corresponding devices
The device numbers corresponding to each channel are as follows.
CPU module
CH1
CH2
SM4596
SM4597
High-speed pulse input/output module
First module
CH9
CH10
SM4604
SM4605
19 HIGH-SPEED INPUT/OUTPUT FUNCTION
148
19.1 High-speed Counter Function
CH3
CH4
SM4582
SM4583
Second module
CH11
CH12
SM4590
SM4591
CH3
CH4
SM4598
SM4599
Second module
CH11
CH12
SM4606
SM4607
CH5
CH6
SM4584
SM4585
Third module
CH13
CH14
SM4592
SM4593
Operation when OFF
High-speed counter current value counted +1 when input A phase ON
OFF
• When OFF by the user (update by END processing)
• Power ON, reset
• STOP/PAUSERUN
CH5
CH6
SM4600
SM4601
Third module
CH13
CH14
SM4608
SM4609
CH7
CH8
SM4586
SM4587
Fourth module
CH15
CH16
SM4594
SM4595
CH7
CH8
SM4602
SM4603
Fourth module
CH15
CH16
SM4610
SM4611

Advertisement