Details of special relays/special registers

Details of special relays/special registers used in PWM output are explained below.
Operation monitor
This device is for monitoring the operation/stopped status of PWM output.
■Corresponding devices
The device numbers corresponding to each channel are as follows.
CPU module
CH1
CH2
CH3
SM5300
SM5301
SM5302
■Update timing
The timing of device update is as follows.
ON
• PWM output driven by HIOEN/DHIOEN instruction
• PWM/DPWM instruction ON execution
PWM output complete flag
This device is for monitoring the completion status (normal completion) of PWM output.
■Corresponding devices
The device numbers corresponding to each channel are as follows.
CPU module
CH1
CH2
CH3
SM5316
SM5317
SM5318
■Update timing
The timing of device update is as follows.
ON
• At execution of the PWM/DPWM, HIOEN/DHIOEN instruction or the END
processing after the output of the specified pulse count is output
If the number of output pulses is set to "0" (unlimited output), PWM output complete flag is not turned ON.
High-speed pulse input/output module
First module
CH4
CH5
CH6
SM5303
SM5304
SM5305
High-speed pulse input/output module
First module
CH4
CH5
CH6
SM5319
SM5320
SM5321
Second module
Third module
CH7
CH8
CH9
SM5306
SM5307
SM5308
OFF
• PWM output stopped by HIOEN/DHIOEN instruction
• After end of output of the specified number of pulses
• PWM/DPWM instruction OFF execution
• Activation contact turned OFF
• Power OFFON, reset, RUNSTOP/PAUSE
Second module
Third module
CH7
CH8
CH9
SM5322
SM5323
SM5324
OFF
• Power OFFON, reset, STOP/PAUSERUN
• When pulse output starts
• When turned OFF by the user
19 HIGH-SPEED INPUT/OUTPUT FUNCTION
Fourth module
CH10
CH11
CH12
SM5309
SM5310
SM5311
Fourth module
CH10
CH11
CH12
SM5325
SM5326
SM5327
19.7 PWM Function
19
223