Multiple Point Output, High-Speed Comparison Tables - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Ex.
Table operation is as follows when multiple HIOEN/DHIOEN instructions are executed within the same scan.
Tables 1, 2 and 4 are started at the 1st HIOEN/DHIOEN instruction.
Tables 3 and 5 are started, and 2 and 4 are stopped at the 2nd HIOEN/DHIOEN instruction.
Table 2 is started and 5 is stopped at the 3rd HIOEN/DHIOEN instruction.
Tables 1, 2 and 3 operate.
■Operation when using internal clock
Self-reset cannot be used for channels set to internal clock by pulse input mode.
■Other precautions
There are common precautions when using high-speed counters. For details, refer to Page 176 Precautions when using
high-speed counters.

Multiple point output, high-speed comparison tables

Multiple point output, high-speed comparison tables are explained below. The multiple point output, high-speed comparison
tables is not supported in high-speed pulse input/output modules.
Use to set multiple point output, high-speed comparison tables for high-speed counters.
Sets match output table comparison setting for high-speed counters.
Parameter setting
Navigation window  [Parameter]  [FX5UCPU]  [Module Parameter]  [High Speed I/O]  "Input Function"  "High
Speed counter"  "Detail Setting"  "Multi-point Output High Speed Compare Table"
Window
Displayed items
Item
Description
Table Data
Sets whether or not to use user device for table data.
Counter CH
Set Comparison Target CH.
Output Data
Sets the type of output data.
Points
Sets the number of output data points.
Enable/Disable
Sets whether to "enable" or "disable" table data.
Device
Set the device used for table data.
Comparison Value
Sets value (comparison value) to be compared with
current value of high-speed counter.
Output Device
Sets the output destination device of output data.
Output Data (HEX)
Sets output data.
Setting range
• Do Not Use Device
• Use Device
CH1 to CH8
• Bit Output
• Word Output
• Bit Output
1 to 16
• Word Output
1 to 2
• Disable
• Enable
Word device (D, R)
-2147483648Comparison
value+2147483647
• Bit Output
Y, M
• Word Output
D, R
According to output device
19 HIGH-SPEED INPUT/OUTPUT FUNCTION
19.1 High-speed Counter Function
19
Default
Do Not Use
Device
CH1
Bit Output
1
Disable