CHAPTER 2: INTRODUCTION
2.2.2

Outputs

489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
Accuracy: ...........................................................Fundamental:+/-0.5% of Full Scale
Max. continuous:
280 V AC
OUTPUT AND NEUTRAL END CURRENT INPUTS
CT primary:
10 to 50000 A
CT secondary:
1 A or 5 A (specify with order)
Conversion range:
0.02 to 20 × CT
Accuracy:
at < 2 × CT: ±0.5% of 2 × CT
at ≥ 2 × CT: ±1% of 20 × CT
Burden:
Less than 0.2 VA at rated load
CT withstand:
1 s at 80 × rated current
2 s at 40 × rated current
continuous at 3 × rated current
PHASE VOLTAGE INPUTS
VT ratio:
1.00 to 300.00:1 in steps of 0.01
VT secondary:
200 V AC (full-scale)
Conversion range:
0.02 to 1.00 × full-scale
Accuracy:
±0.5% of full-scale
Max. continuous:
280 V AC
Burden:
> 500 KΩ
RTD INPUTS
100 Ω Platinum (DIN.43760)
RTDs (3-wire type):
100 Ω Nickel, 120 Ω Nickel,
10 Ω Copper
RTD sensing current:
5 mA
Isolation:
36 Vpk (isolated with analog inputs and outputs)
Range:
–50 to +250°C
Accuracy:
±2°C/±4°F for Pt and Ni
±5°C/±9°F for Cu
Lead resistance:
25 Ω max. per lead (Pt and Ni types); 3 Ω max. per lead (Cu type)
NO sensor:
>1 kΩ
Short/low alarm:
<–50°C
ANALOG CURRENT OUTPUT
Type:
Active
Range:
4 to 20mA, 0 to 1 mA
(must be specified with order)
Accuracy:
±1% of full scale
4 to 20 mA max. load:
1.2 kΩ
0 to 1 mA max. load:
10 kΩ
Isolation:
36 Vpk (isolated with RTDs and analog inputs)
4 assignable outputs:
phase A, B, C output current, three-phase average current,
negative sequence current, generator load, hottest stator RTD,
hottest bearing RTD, RTDs 1 to 12, voltage (AB, BC, and CA),
average phase-phase voltage, volts/hertz, frequency, third
harmonic neutral voltage, power (3-phase Mvar, MW, and MVA),
power factor, analog inputs 1 to 4, tachometer, thermal
capacity used, demand (I, Mvar, MW, and MVA), torque
3rd Harmonic at >3V secondary: +/-5% of reading
3rd Harmonic at < 3V secondary: +/- 0.15% of full scale
2–7