SPECIFICATIONS

Testing and certification

1–14
Courtesy of NationalSwitchgear.com
ETHERNET (FIBER)
Fiber type: .............................................................. 100 MB Multi-mode
Wavelength:.......................................................... 1300 nm
Connector: ............................................................. MTRJ
Protocol:.................................................................. Modbus TCP, DNP3.0, iec 60870-5-104, IEC 61850 GOOSE
Transmit power: .................................................. -20 dBm
Receiver sensitivity: ........................................... -31 dBm
Power budget:...................................................... 9 dB
Maximum input power:.................................... -11.8 dBm
Typical distance: ................................................. 2 km (1.25 miles)
Duplex:..................................................................... half/full
USB
Standard specification:.................................... Compliant with USB 2.0
Data transfer rate: ............................................. 115 kbps
APPROVALS
Applicable Council Directive
Low voltage directive
CE compliance
EMC Directive
North America
cULus
ISO
Manufactured under a registered
quality program
TYPE TESTS
Test
Dielectric voltage withstand
Impulse voltage withstand
Damped Oscillatory
Electrostatic Discharge
RF immunity
Fast Transient Disturbance
Surge Immunity
Conducted RF Immunity
Power Frequency Immunity
Voltage interruptionand Ripple DC IEC60255-11
Radiated & Conducted Emissions CISPR11 /CISPR22/ IEC60255-25
Sinusoidal Vibration
Shock & Bump
Siesmic
Power magnetic Immunity
Pulse Magnetic Immunity
According to
EN60255-5 / EN60255-27 / EN61010-1
EN60255-26 / EN50263
EN61000-6-2
UL508
UL1053
C22.2.No 14
ISO9001
Reference Standard
EN60255-5
IEC61000-4-18IEC60255-22-1
EN61000-4-2/IEC60255-22-2
EN61000-4-3/IEC60255-22-3
EN61000-4-4/IEC60255-22-4
EN61000-4-5/IEC60255-22-5
EN61000-4-6/IEC60255-22-6
EN61000-4-7/IEC60255-22-7
IEC60255-21-1
IEC60255-21-2
IEC60255-21-3
IEC61000-4-8
IEC61000-4-9
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTION
Test Level
2.3KV
5KV
2.5KV CM, 1KV DM
Level 4
Level 3
Class A and B
Level 3 & 4
Level 3
Class A & B
15% ripple, 200ms
interupts
Class A
Class 1
Class 1
Class 2
Level 5
Level 4