] AUX RELAY 1 CONFIG
]
NOTE
5–32
PATH: S4 CONTROL
AUX RELAY 1(2) CONFIG
The MM3 Motor Manager 3 has two auxiliary programmable output relays. These two
outputs can be assigned any of the functions listed below. Once a function has been
assigned to one of the auxiliary relays it cannot be assigned to the other with the
exception of the serial control function which can be set to both auxiliary relays.
The setpoints listed under the
the setpoints shown below for
The auxiliary relay configuration settings are programmed as follows:
AUX RELAY 1 FUNCTION: The dual form-C auxiliary relay 1 can be configured to
activate on various conditions as described below:
• "SERIAL CONTROL": Auxiliary relay 1 can be energized or de-energized via the serial
port.
• "TRIPS": Auxiliary relay 1 will be energized when the MM3 Motor Manager 3 is
tripped. Resetting the MM3 Motor Manager 3 will de-energize auxiliary relay 1.
• "ALARMS": Auxiliary relay 1 will be energized while any alarm is present.
• "PRE CONTACTOR A": Auxiliary relay 1 will energize when the MM3 Motor Manager 3
receives a start command. The contactor A relay will start the motor after the
delay specified in the
de-energize after the
A de-energizes.
• "PRE CONTACTOR B": Auxiliary relay 1 will energize when the MM3 Motor Manager 3
receives a start B command. The contactor B relay will start the motor after the
delay specified in the
de-energize after the
B de-energizes. Pre contactor B is active for the two-speed, full-voltage reversing,
and duty/standby starter types only.
AUX RELAY 1 FUNCTION:
SERIAL CONTROL
AUX RELAY 1 DELAY
5 s
AUX RELAY 1 PRE
START DELAY: 5 s
AUX RELAY 1 POST
START DELAY: OFF s
ENERGIZE ON MOTOR
START DELAY: 5 s
DE-ENERGIZE ON MOTOR
STOP DELAY: 5 s
AUX 1 OPERATION:
NON-FAILSAFE
DELAY CONTACTOR G/F
TRIP BY: 0 ms
page operate in the same manner as
AUX RELAY 2 CONFIG
.
AUX RELAY 1 CONFIG
AUX RELAY 1 PRE START DELAY
AUX RELAY 1 POST START DELAY
AUX RELAY 1 PRE START DELAY
AUX RELAY 1 POST START DELAY
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
Range:
see below
Range:
0 to 125 s in steps of 1
Range:
0 to 900 s in steps of 1
Range:
0 to 125 s or OFF in steps of 1
Range:
0 to 125 s or OFF in steps of 1
Range:
0 to 125 s or OFF in steps of 1
Range:
FAILSAFE, NON-FAILSAFE
Range:
0 to 1000 ms in steps of 100
setpoint. Auxiliary relay 1 will
times out or when contactor
setpoint. Auxiliary relay 1 will
times out or when contactor